    Centrifugal W ater Chillers Model CVGF W ater -Cooled Hermetic Centrifugal Refrigeration Capacities fr om 400 to 1000 T ons (1400 ∼ 3510 kW) 50 and 60 Hz October 2008 CTV -PRC001-E4 ...

  • Trane CVGF - page 2

    Introducing T rane’ s Model CVGF Centrifugal Water Chiller Introduction The basic gear driven centrifugal water chiller design was introduced in 1976 and has been pr oven in thousands of installations. T rane continues to deliver its r eliability and energy fi tness commitment on its newest line of gear -drive centrifugal water chillers, the Mod ...

  • Trane CVGF - page 3

    Introduction ………………………………………………………………………… 2 Features and Benefi ts …………………………………………………………… 9 Application Considerations …………………………………………………… 10 General Data …………………………………………? ...

  • Trane CVGF - page 4

    Standard CVGF Featur es The following features ar e provided as standar d with all T rane Model CVGFchillers: • Hermetic two-stage centrifugal compressor -motor assembly with integral lubrication system and economizer cycle • Evaporator and condenser assembly • Prewir ed instrument and control panel • Oil charge • Integral oil heaters • ...

  • Trane CVGF - page 5

    Advanced Heat T ransfer Surfaces • Evaporator and condenser tubes use the latest heat transfer surfaces • Less refrigerant needed due to advanced patented evaporator design Compact Size • Designed with the retr ofi t and replacement market in mind • The 400 to 500 NTON sizes can fi t through most double-width doors • Small footprint of ...

  • Trane CVGF - page 6

    T racer AdaptiView TM Control Operator Interface T racer AdaptiView TM contr ol is the unit-mounted operator interface with a touch sensitive 12/1" display . The display pr esents information through an intuitive navigation system. Alternate languages are also available for the contr ol panel display . T racer AdaptiView TM contr ol receives i ...

  • Trane CVGF - page 7

    7 Features and Benefi ts T racer TU Interface The T racer chiller contr oller adds a level of sophistication better served by a PC application to improve service technician effectiveness and minimize chiller downtime. T racer AdaptiView™ c ontrol is intended to serve only typical daily tasks. The portable PC-based service-tool software, T racer ...

  • Trane CVGF - page 8

    T racer AdaptiView TM Controller T oday's centrifugal chillers offer predictive contr ols that anticipate and compensate for load changes. Other control strategies made possible with the T racer AdaptiView TM controls are: Feedforward Adaptive Contr ol Feedforward is an open-loop, pr edictive control strategy designed to anticipate and compens ...

  • Trane CVGF - page 9

    • Time of day scheduling: allows the end user to defi ne the occupancy period, i.e. time of the day , holiday periods and exception schedules. • Optimization of the start/stop time of the installation: based on the programmed schedule of occupancy and on the historical temperature r ecords, T racer Summit TM calculates the optimal start/stop t ...

  • Trane CVGF - page 10

    T wo-Stage Compr essor Widens the Application Range Why Centrifugal Compressors Surge Centrifugal compressors pr oduce their pressur e differential (head) by converting the kinetic energy of the gas leaving the impeller into static pressur e. The velocity of this gas is the result of two components: • The radial velocity component V r , which is ...

  • Trane CVGF - page 11

    Condenser W ater Limitations T emperature T rane centrifugal chillers start and operate over a range of load conditions with controlled water temperatures. Reducing the condenser water temperatur e is an effective method of lowering the chiller power input. However , the effect of lowering the condenser water temperatur e may cause an increase in s ...

  • Trane CVGF - page 12

    Application Considerations Contact your local T rane Sales Offi ce for information regar ding optimum condenser water temperatures and fl ow rates for a specifi c application. W ater T reatment The use of untreated or impr operly treated water in a chiller may r esult in scaling, erosion, corrosion, algae, or slime. It is recommended that the se ...

  • Trane CVGF - page 13

    General Data 13 T able GD-1 – Model CVGF Description Model CVGF Nominal Cooling Capacity NTON 400 500 500 650 800 1000 Heat Exchanger Size Evaporator EVSZ 500 500 700 700 1000 1000 Condenser CDSZ 500 500 700 700 1000 1000 Heat Exchanger Bundles Evaporator EVBS A = Small A = Small A = Small A = Small A = Small A = Small B = Medium B = Medium B = M ...

  • Trane CVGF - page 14

    14 General Data 50 and 60 Hz SI Units and (English Units) High Effi ciency Shells - 0.75 inch (19 mm) Internally Enhanced Cu T ube: Condenser: Nominal Shell 500 500 500 700 700 700 1000 1000 1000 1000 Bundle Size Small Medium Large Small Medium Large Small Medium Large Extra Large Number of Passes 2 2 2 2 22222 2 Min Flow L/s (gpm) 31 (487) 34 (54 ...

  • Trane CVGF - page 15

    Supply and Motor Lead Wiring and Connections Only copper conductors should be connected to the compressor motor due to the possibility of galvanic corrosion as a r esult of moisture if aluminum conductors ar e used. Copper conductors are recommended for supply leads in the starter panel. Suggested starter panel line- and load-side lug sizes (when l ...

  • Trane CVGF - page 16

    16 Standard Featur es Field Connection The fi eld-connected elements are involved in physically turning the chiller on or off. This involves ensuring that the chiller is not in an emergency or external stop condition, starting the pumps, and verifying that fl ow has been established. The optional, factory-supplied fl ow switch or a customer - su ...

  • Trane CVGF - page 17

    Extended Operation Package Select the extended-operation package for chillers that requir e external, hot water control, and/or base-loading capabilities. This package also includes a 4-20 mA or 0-10 Vdc analog input for a refrigerant monitor . • External base-loading control • External base-loading relay • External hot-water control relay ? ...

  • Trane CVGF - page 18

    18 Controls Standard Protections Standard Pr otections The chiller controller uses pr oportional-integral-derivative (PID) control for all limits—ther e is no dead band. This removes oscillation above and below setpoints and extends the capabilities of the chiller . Some of the standard pr otection features of the chiller contr oller are describe ...

  • Trane CVGF - page 19

    Standard Protections 19 Oil-T emperature Pr otection Low oil temperature when the oil pump and/or compr essor are running may be an indication of refrigerant diluting the oil. If the oil temperatur e is at or below the low oil-temperature setpoint, the compressor is shut down on a latching diagnostic and cannot be started. The diagnostic is reporte ...

  • Trane CVGF - page 20

    20 Controls levels at which this may occur . It is diffi cult to defi ne an exact voltage sag or voltage level at which a particular motor will no longer consume power , but we are able to make some general statements concerning MPL protection: The chiller will remain running under the following conditions: • Line-voltage sag of 1.5 line cycles ...

  • Trane CVGF - page 21

    Standard Protections Short-Cycling Protection This function mimics heat dissipation from a motor start using two setpoints: Restart Inhibit Free Starts and Restart Inhibit Start-to-Start Timer . This allows the CVGF to inhibit too many starts in a defi ned amount of time while still allowing for fast restarts. The default for CVGF is 3 Free Starts ...

  • Trane CVGF - page 22

    22 Figure PD-1 –Model CVGF Cooling Only With Unit-Mounted Starter Figure PD-2 –Model CVGF Cooling Only Without Unit-Mounted Starter (for Remote-Mounted Starter) CL1 at either end of machine and is requir ed for tube pull clearance. CL2 is always at the opposite end of machine from CL1 and is for water box plus clearance. – Recommended clearan ...

  • Trane CVGF - page 23

    Model CVGF Water Connection Pipe Size Shell Size 500 700 1000 W ater Passes Metric Pipe Size (mm) DN Evaporator 2 Pass DN 200 (8”) DN 250 (10”) DN 300 (12”) 3 Pass DN 200 (8”) DN 200 (8”) DN 250 (10”) Condenser Condenser DN 250 (10”) DN 300 (12”) DN 350 (14”) 23 Evaporator Water Box Length — SI (I-P) Length No. mm (in) Shell Pre ...

  • Trane CVGF - page 24

    T rane CVGF packaged centrifugal water chillers using HFC-134a refrigerant consist of a hermetic two-stage, gear -drive centrifugal compressor , evaporator , condenser , interstage economizer , unit- mounted micropr ocessor based control panel , and compr essor motor starter . The chiller is entire factory assembled. Compressor T wo-stage centrifug ...

  • Trane CVGF - page 25

    25 Condenser The condenser is designed, tested and stamped in accordance with the ASME Boiler and Pr essure V essel Code or PED (European Code) for a refrigerant side working pr essure of 15.2 bars (220 psig). It consists of a carbon steel shell with steel tube sheets welded to each end. Individually- replaceable, externally-fi nned and internally ...

  • Trane CVGF - page 26

    Compressor -Motor Starter Unit-mounted starters can either be a star -delta or solid-state in NEMA 1 type enclosure rated up to 952 RLA at 380-480 V olts (star -delta), 900 RLA at 481-600 V olts (star -delta), and 1472 RLA at 380-600 V olts (solid-state). Remote-mounted starters can either be star -delta or solid-state for low voltage. Across-the-l ...

  • Trane CVGF - page 27

    27 T o Convert From: T o : Multiply By: Length Feet (ft) meters(mm) 0.30481 Inches (In) millimeters (mm) 25.4 Area Square Feet (ft 2 ) square meters (m 2 ) 0.093 Square Inches (In 2 ) square millimeters (mm 2 ) 645.2 V olume Cubic Feet (ft 2 ) Cubic meters (m 3 ) 0.0283 Cubic Inches (In 3 ) Cubic mm (mm 3 ) 16387 Gallons (gal) Iitres (L) 3.875 Gall ...

  • Trane CVGF - page 28

    www .trane.com For more information, contact your local T rane offi ce or e-mail us at comfort@trane.com T rane has a policy of continuous product and data improvement and reserves the right to change design specifi cations without notice. Literature Or der Number Date Supersedes CTV -PRC001-E4 October 2008 September 2004 ...

Fabbricante Trane Categoria Water Pump

I documenti che otteniamo dal fabbricante del dispositivoTrane CVGF possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Trane
- manuali per l’uso CVGF
- schede prodotto Trane
- opuscoli
- o etichette energetiche Trane CVGF
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Trane CVGF.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Trane CVGF, manuali di manutenzione, brevi manuali o manuali utente Trane CVGF. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Trane CVGF.

Manuali per l’uso simili

Manuale completo del dispositivo Trane CVGF, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Trane CVGF dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Trane CVGF.

Il manuale per l’uso completo Trane, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Trane CVGF - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Trane CVGF, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Trane CVGF che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Trane CVGF - che ci dovrebbe aiutare nei primi passi durante l'uso Trane CVGF
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Trane CVGF
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Trane CVGF in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Trane CVGF?

Utilizza il modulo sottostante

Se non hai risolto il problema con Trane CVGF con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Trane CVGF è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)