  • Emerson CW - page 1

    Precision Cooling For Business -Critic al C ontinuity™ Li eber t ® CW ™ Syst em Desi gn Manu al - 26-181kW , 50 & 60Hz ...

  • Emerson CW - page 2

    ...

  • Emerson CW - page 3

    i T ABLE OF CONTENTS L IEBERT CW M ODEL N UMBER N OMENCL ATURE . . . . . . . . . . . . . . . . . . . . . . I NSIDE F RONT C OVER 1.0 L IEBERT CW P ERFORMANCE D AT A —50 & 60 H Z S YSTEMS . . . . . . . . . . . . . . . . . . . . . . . . 2 2.0 L IEBERT CW P ERFORMANCE D AT A —M ODELS WITH EC F ANS , 50 & 60 H Z . . . . . . . . . . . . 4 3. ...

  • Emerson CW - page 4

    ii ...

  • Emerson CW - page 5

    1 L IEBERT CW M ODEL N UMBER N OMENCLATURE CW CW = Liebert CW Floor Mount Chilled W ater Unit 1 14 D C S 2 1234 A Nominal Capa city , kW D = Downflow U = Up flow C = Chilled W ater S = Forward-Curved Centrifuga l Fan with S t andard Motor V = Forward-Curved Centrifuga l fan with V ariable Speed Drive 1 = EC Motorized Impeller 2 = 2-W ay V alve, Sta ...

  • Emerson CW - page 6

    Liebert CW Performance Data—50 & 60 Hz Syste ms 2 1.0 L IEBERT CW P ERFORMANCE D AT A —50 & 60 H Z S YSTEMS CW026 CW038 CW041 CW051 CW060 CW076 CW084 CW106 CW114 Capacity Data BTU/Hr (kW) {Based on 45°F (7 .2°C) Entering Water. 10°F (5.6°C) Water Rise} 80°F DB, 66.8°F WB (26.6°C D B, 19.3°C WB) 50% RH Total - kBTUH (kW) 142 (41. ...

  • Emerson CW - page 7

    Liebert CW Performance Data—50 & 60 Hz Syste ms 3 CW026 CW038 CW041 CW051 CW060 CW076 CW084 CW106 CW114 Fan Section - Variable Pitch, Two-Belt Dri ve Package* (*Some options or combination of options may result in reduced air flow. Consult factory for recommendation.) Air Volume CFM (CMH) 5250 (8920) 6050 (10,280 ) 5900 (10,020) 9300 (15,800) ...

  • Emerson CW - page 8

    Liebert CW Performance Data—Mo dels with EC Fans, 50 & 60 Hz 4 2.0 L IEBERT CW P ERFORMANCE D AT A —M ODELS WITH EC F ANS , 50 & 60 H Z CW106D CW114D CW181D Capacity Data BTU/Hr (kW) {Based on 45°F (7.2°C) Entering Water. 10°F Water Rise} 75°F DB, 62.5°F WB (23.9°C DB, 16.9°C WB ) 50% RH * Total -kBTUH (kw) 435 (127.5) 552 (161.7 ...

  • Emerson CW - page 9

    Electrical Data—Units with EC Fans 5 3.0 E LECTRICAL D AT A —U NIT S WITH EC F ANS 3.1 CW106 and CW1 14 Electri cal Dat a with EC Fans 3.2 CW181 Electrical Da t a with EC Fans T able 1 Electrical dat a—60Hz-3 phase Reheat Humidifier Volts FLA WSA OPD Electric Infrared 460 65.4 81.8 90 Electric Infrared 575 53.4 66.8 70 Electric Infrared 460 5 ...

  • Emerson CW - page 10

    Dimensional Data 6 4.0 D IMENSIONAL D AT A Figure 1 Dimensions, CW026 - CW084 Model Dimensional Data. inches (mm) Net Weight lb (kg) AB C D E F G H J K CW026 50 (1270) 46 (1168) 35 (889) 32 (813) 48 (1219) 33 (883) 8 (203) 37 (940) 35-5/8 (905) 31 (787) 760 (345) CW038 50 (1270) 46 (1168) 35 (889) 32 (813) 48 (1219) 33 (883) 8 (203) 37 (940) 35 5/8 ...

  • Emerson CW - page 11

    Dimensional Data 7 Figure 2 Dimensional Dat a—50 & 60 Hz Systems CW106—CW1 14, downflow models Model Dimensional Data, inches (mm) Net Weight lb (kg) AB C D E F G H I CW106 122 (3099) 118 (2997) 35 (889) 31 (787) 120 (3048) 33 (838) 35-5/8 (905) 30 (762) 34 (864) 1785 (810) CW114 1925 (873) UNIT DI MEN SI ONAL DA T A Projection of Display B ...

  • Emerson CW - page 12

    Dimensional Data 8 Figure 3 Cabinet and Floor Pla nning Dimensiona l Dat a, Downflow Model CW181 with EC Fans Note: D imensions do not include fil ter plenum shipped s eparate and field-A instal led. DPN 001694 REV 0 Note: E lectri cal connecti ons can be made from the bottom of the unit. FRON T VI EW TOP V IE W Shaded a rea indicates the required ...

  • Emerson CW - page 13

    Dimensional Data 9 Figure 4 Cabinet and floor planning dimension s, up flow models—CW026 -CW084 Model No. of Blowers Dimensional Data, inches (mm) Net Weight, lb (kg) ABCD E F G H J K LM CW026 1 50 (1270) 48 (1219) 46 (1168) 44 (1118) 3 (76) 5 (127) 18 (457) 15-7/8 (403) 18-5/8 (473) 2-3/16 (55) 17-3/8 (454) — 760 (345) CW038 1 50 (1270) 48 (12 ...

  • Emerson CW - page 14

    Dimensional Data 10 Figure 5 Cabinet and floor plannin g dimensions, CW 106 and CW1 14 upf low models Unit Dime nsional Data Air grille suppli ed on units with front return air only Shaded are as indicate a recommended c learance of 36" (914mm) f or component access and filte r remova l. Duct Co nn ection Data Models With R ear Return Projec t ...

  • Emerson CW - page 15

    Upflow Duct Conne cti on Data CW026—CW084 11 5.0 U P FLOW D UCT C ONNECTION D AT A CW026—CW084 No. of Blowers Model No. Chilled Water Dimensional Data—in. (mm) A BCD E F G H J 1 CW026 15-7/8 (403) 18-5/8 (473) 2-3/ 16 (55) 17-7 /8 (454) - 50 (1270) 35 (889) 44 (111 8) 18 (457) 1 CW038 15-7/8 (403) 18-5/8 (473) 2-3/16 (55) 17-7 /8 (454) - 50 ( ...

  • Emerson CW - page 16

    Blower Duct & Deck Dimensions, CW106 and CW1 14, Upflow Models 12 6.0 B LOWER D UCT & D ECK D IMENSIONS , CW106 AND CW1 14, U P FLOW M ODELS Model Blower Supply Motor, hp Dimensional Data, inches (mm) Net Weight lb. (Kg) AB C D E F CW106 15 x 15 Top Front 10-15 27-1/2 (699) 3 1/2 (89) 18-11/16 (475) 16-3/16 (411) 10 (254) 4 1/2 (114) 1785 ( ...

  • Emerson CW - page 17

    Electrical Specifications 13 7.0 E LECTRICAL S PECIFICATIONS T able 5 Electrical dat a—50 Hz systems Reheat Options Electric None Electric None Humidifier Options IR/SGH IR/SGH Steam or None Steam or None Models Motor HP Volts 200 230 380-415 200 23 0 380-415 200 230 380-415 200 230 380-415 CW026 2.0 FLA 46.7 43.4 24.3 19.8 17.2 9 .9 33.9 32.3 17 ...

  • Emerson CW - page 18

    Electrical Specifications 14 T able 7 Electrical dat a—60 Hz Systems Chilled Water Model s - 60Hz Reheat Options Electric None Electric El ectric Humidifier Options Infrared or St eam Generating Infrared or Steam Generating Steam or None Steam or None Models / Motor HP Volts 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575 CW026 2. ...

  • Emerson CW - page 19

    Electrical Specifications 15 CW106 20.0 HP (Upflow only) FLA 165.1 154.8 77.7 63.7 86.0 76.2 3 8.6 33.6 138.5 132.6 66. 1 52.1 59.4 54.0 27.0 22.0 WSA 206.4 19 3.5 97.1 79.6 107.5 95.3 48.3 4 2.0 173.1 165.8 82.6 65.1 7 4.3 67.5 33.8 27.5 MFCB 225 2 00 110 90 150 125 70 60 200 200 90 70 125 110 60 45 CW114 10.0 HP FLA 136.5 128.8 64.7 52.7 57.4 50. ...

  • Emerson CW - page 20

    Guide Specifications 16 G UIDE S PECIFICATIONS 1.0 G ENERAL 1.1 Summary These specifications describe requirements for a precision environmental control system. The system shall be design ed to main tain temperature conditio ns in the r ooms containing electronic equipment. The manufacturer shall design and furnish all equip men t to be fully compa ...

  • Emerson CW - page 21

    Guide Specifications 17 System Auto Restart - The auto restart feature will automa tically restart the system after a power failure. Time dela y is programmable. Sequential Load Activation - On in itial startup or restart after po wer failure, each operational load is sequenced with a minimum of one seco nd delay to minimize total inrush current. H ...

  • Emerson CW - page 22

    Guide Specifications 18 The Service Menus Shall be Defined as Follows Setpoints : Menu shall allow setpoin ts within the following ranges: • Temperature Setpoint 65-85ºF (18-29ºC)* • Temperature Sensitivity +1-10ºF (0.6-5.6ºC) • Humidity Setpoint 20-80% RH* • H umidity Sensitivity 1 -30% RH • High Temperature Alarm 35-90ºF (2-32ºC) ...

  • Emerson CW - page 23

    Guide Specifications 19 Advanced Menus Factory Settings : Configuration settings shall be fa ctor y-set based on the pre-defi ned component operation. Change Passw ords : Menu shall allow new passwords to be set or changed. 2.4.1 Liebert iCOM Microprocessor Control With L arge Graphic Display (Optional) The Liebert iCOM unit control with large grap ...

  • Emerson CW - page 24

    Guide Specifications 20 2.5.1.4 Alarms The Liebert iCOM control shall activate an audibl e and visual alarm in event of any of the foll owing conditions: • H igh Temperature • Low Temperature • H igh Humidity • Low Humidity • Main Fan Overload (opt) • Change Filters • Loss of Air Flow • Loss of Power • Custom Alarm (#1 to #4) Cust ...

  • Emerson CW - page 25

    Guide Specifications 21 2.7 High Pressure Chilled W ater Control V alve—Optional The chilled wa ter circuit shall inclu de a 3-way (2-way ) high pressure modu lating valve. The valve shall be designed for up to 400 PSI (2758 kPa) water pressure. 2.8 A-Frame Chilled W ater Coil The cooling coil shall be of A-frame design with a minimum of __ __ sq ...

  • Emerson CW - page 26

    Guide Specifications 22 2.1 1.6 Floor St and The floor stand shall be constructed of a heliarc- welded, tubular steel frame. The floor stand shall have adjustable legs wit h vibration isolation pa ds. The floor stand shall be ____ inches high. 2.1 1.6.1 Floor St and T urning V ane A factory-supplied , field-mounted turning vane shall be provided. 2 ...

  • Emerson CW - page 27

    ...

  • Emerson CW - page 28

    Ensuring The Hi gh A vai lab ilit y Of Mission-Critic al Data An d Appli c ations. Emerson Net work P ow er , the global leader in enabling business-critical continuity , ensures network re siliency and adaptabilit y through a family of technologies—inc luding Liebert power and cooling technologies—that prot ect and suppor t business-critical s ...

Fabbricante Emerson Categoria Network Card

I documenti che otteniamo dal fabbricante del dispositivoEmerson CW possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Emerson
- manuali per l’uso CW
- schede prodotto Emerson
- opuscoli
- o etichette energetiche Emerson CW
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Emerson CW.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Emerson CW, manuali di manutenzione, brevi manuali o manuali utente Emerson CW. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Emerson CW.

Manuali per l’uso simili

Manuale completo del dispositivo Emerson CW, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Emerson CW dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Emerson CW.

Il manuale per l’uso completo Emerson, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Emerson CW - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Emerson CW, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Emerson CW che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Emerson CW - che ci dovrebbe aiutare nei primi passi durante l'uso Emerson CW
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Emerson CW
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Emerson CW in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Emerson CW?

Utilizza il modulo sottostante

Se non hai risolto il problema con Emerson CW con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Emerson CW è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)