    SSZ 14 SEER S plit System Heat Pumps • Refer to Service Manual RS6200005 for installation, op- eration, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. RT6213005 May 2006 TECHNICAL INFORMA TION MANUAL Copyright ? ...

  • Goodman Mfg SSZ140181A - page 2

    PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to d ...

  • Goodman Mfg SSZ140181A - page 3

    PRODUCT IDENTIFICA TION 3 WARNING WARNING WARNING WARNING To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance. Do not connect or use any device that is not design certified by Goodman for use with this unit. Serio ...

  • Goodman Mfg SSZ140181A - page 4

    PRODUCT DESIGN 4 SSZ14 models are available in 1 1/2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet. These units are designed for ...

  • Goodman Mfg SSZ140181A - page 5

    HEA T PUMP SPECIFICA TIONS 5 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...

  • Goodman Mfg SSZ140181A - page 6

    6 COOLING PERFORMANCE DA T A SSZ140181A* EXPA NDED PERFORMAN CE DA TA COOLING OPE RA TION MODEL: SSZ140181A * / CA *F3131*6 A* +TXV / M BR800**-1 D esign Subcooling 9 ± 3 °F @ the liqui d service valve, A RI 95 test conditio ns Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature I D B * A i r f l o w 5 96 36 77 1 ...

  • Goodman Mfg SSZ140181A - page 7

    7 COOLING PERFORMANCE DA T A SSZ140181A* EXPA NDED PERFORMAN CE DATA COOLING O PERATION MODEL: SSZ140 181A * / CA *F3131*6A * +TXV / M BR800**-1 D esign Subc ooling 9 ±3 °F @ t he liquid service v alve, A RI 95 test c onditio ns Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor W et Bulb Temperatur e I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg SSZ140181A - page 8

    8 COOLING PERFORMANCE DA T A SSZ140241A* EXPA ND ED PERFORM A NCE DATA COOLING OP ERA TION MODEL: SS Z140241A * / CA *F3636*6 A *+TXV / MBR80 0**-1 Design Subco oling 9 ±3 °F @ the liquid service val v e, A RI 95 tes t condition s Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperatur e I D B * A i r f l o w 5 96 3 6 ...

  • Goodman Mfg SSZ140181A - page 9

    9 COOLING PERFORMANCE DA T A SSZ140241A* EXPA NDED PERFO RMA NCE DA T A COOLING OPERA TION MO DEL: SSZ140241A* / CA *F3636* 6A *+TXV / MB R800**-1 Design Subcoo ling 9 ±3 °F @ the liqui d service valv e, ARI 95 test condit ion s Out door A mbient Temp eratur e 65 75 85 95 105 115 Enteri ng I ndoor W et Bulb Temperatur e I D B * A i r f l o w 5 96 ...

  • Goodman Mfg SSZ140181A - page 10

    10 COOLING PERFORMANCE DA T A SSZ140301A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION M ODEL: SSZ140301A* / CA *F3642*6A*+TXV / MBR1600**-1 Design Subcooling 9 ±3 °F @ the liquid service valv e, AR I 95 test conditio ns Outdoor A mbient Temperature 65 75 85 95 105 1 15 Enterin g Indo or W et Bul b Temperatur e I D B * A i r f l o w 5 96 36 77 ...

  • Goodman Mfg SSZ140181A - page 11

    11 COOLING PERFORMANCE DA T A SSZ140301A* EXPA NDED PERFORMA NC E DA TA COOLING OPERA TION M ODEL: SSZ 140301A * / CA*F3642*6A *+T XV / MB R1600**-1 Design Subcooling 9 ±3 °F @ th e liquid serv ice valve, ARI 95 test conditio ns Outdoor A mbi ent Temper atu re 65 75 85 95 105 115 Enterin g Indo or W et Bulb Temperature I D B * A i r f l o w 5 96 ...

  • Goodman Mfg SSZ140181A - page 12

    12 COOLING PERFORMANCE DA T A SSZ140361A* EXPA NDED PER FOR M A NCE DA T A MODEL: SSZ140 361A * / CA*F4860*6A*+TXV / M BR1600 **- 1 Desig n Subco oli ng 9 ±3 ° F @ th e li qu id serv i ce va lv e, A RI 95 t est co ndi ti o ns Outdo or A mbient T emperature 65 75 85 9 5 105 115 Entering I ndoor Wet Bulb Te mperature IDB Airfl ow 59 63 67 71 59 63 ...

  • Goodman Mfg SSZ140181A - page 13

    13 COOLING PERFORMANCE DA T A SSZ140361A* EXPA ND ED PERFO RM A NCE D A TA COOLING OP ERATION MODEL: SSZ140361A* / CA *F4860*6A*+TXV / M BR1600 **- 1 Desig n Subco oli ng 9 ±3 ° F @ th e li qu id serv i ce va lv e, A RI 95 te st cond it i o ns Outdo or A mbient T emper ature 65 75 85 9 5 105 115 Entering I ndoor Wet Bulb Te mperature I D B * A i ...

  • Goodman Mfg SSZ140181A - page 14

    14 COOLING PERFORMANCE DA T A SSZ140421A* EXPA NDED PERFORMA NCE DA T A MODEL: S SZ1404 21A * / CA *F4860*6 A*+TXV / M BR2000 **-1 Design Sub cooling 9 ±3 °F @ the li quid service valve, A RI 95 test conditio ns Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB A irf lo w 59 63 67 71 59 63 6 7 71 59 63 67 7 ...

  • Goodman Mfg SSZ140181A - page 15

    15 COOLING PERFORMANCE DA T A SSZ140421A* EXPANDED PERFORMANCE DA T A COOLING OP ERA TION MODEL: SSZ14 0421A * / CA *F4860*6A *+TXV / MBR2000 **-1 Design Sub cooli ng 9 ±3 °F @ the liquid s ervice valve, A RI 95 test condi t io ns Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg SSZ140181A - page 16

    16 COOLING PERFORMANCE DA T A SSZ140481A* EXPA NDED PERFORMANCE DA TA COOLING O PERA TION MODEL: SS Z140 481A * / CA *F48 60*6A *+TXV / MBR20 00**-1 Design Sub cooling 9 ±3 °F @ the liq uid service va lve, A RI 95 test con ditio ns Outdoor A mbient Temperatur e 65 75 85 95 1 05 115 Entering Indoor Wet Bulb Te mperature I D B * A i r f l o w 5 96 ...

  • Goodman Mfg SSZ140181A - page 17

    17 COOLING PERFORMANCE DA T A SSZ140481A* EXPA NDED PERFORMA NCE DATA COOLING O PERA TI ON MODEL: S S Z140481 A* / C A*F4 860*6A *+TXV / MBR2000**-1 Design S ubcool ing 9 ±3 °F @ the liquid s ervice valve, A RI 95 tes t conditio ns Outdoor A mbient Temperature 65 75 85 95 1 05 115 Entering Indoor Wet Bulb Temperatur e I D B * A i r f l o w 5 96 3 ...

  • Goodman Mfg SSZ140181A - page 18

    18 COOLING PERFORMANCE DA T A SSZ140601A* EXPA NDED PERFORMA N CE DA TA COOLING O PERATION MODEL: SSZ140 601A * / CA *F4860*6A *+TXV / MBE200 0**-1 Design S ubcooling 9 ±3 ° F @ the liquid s ervice valve, A RI 95 test conditio ns Outdoor A mbie nt Temperat ure 65 75 85 9 5 105 115 Entering Indoor W et Bulb Temperature IDB A irf lo w 59 63 67 71 5 ...

  • Goodman Mfg SSZ140181A - page 19

    19 COOLING PERFORMANCE DA T A SSZ140601A* EXPA NDED PERFORMA NCE DAT A COOLING O PE RA TI ON MODEL: SSZ140 601A * / CA *F4860*6 A *+TXV / MBE2000** -1 Design Subcooling 9 ±3 ° F @ the liquid service valve , A RI 95 test conditio ns Outdoor A mbie nt Temperat ure 65 75 85 9 5 105 115 Entering Indoor W et Bulb Temperature I D B * A i r f l o w 5 96 ...

  • Goodman Mfg SSZ140181A - page 20

    20 PERFORMANCE DA T A Out door Temp. ° F . Tota l Btuh Sen sibl e Btu h La te nt Btuh Total Wat ts 75° 36,330 24,713 11,617 2,662 80° 35,898 24,729 11,169 2,742 85° 35,465 24,738 10,727 2,822 90° 35,033 24,830 10,203 2,892 95° 34,600 24,912 9,688 2,963 100° 33,735 24,749 8,986 3,023 105° 32,870 24,563 8,307 3,083 110° 31,659 23,757 7,902 3 ...

  • Goodman Mfg SSZ140181A - page 21

    21 EXPA NDED PERFORM ANCE DA TA M ODEL: SSZ140361A * / CA*F4860C6A *+T XV / M BR1600**-1 HEATING O PERATION Outdoo r Ambient Tem p era ture 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 MBh 43.5 41.2 38.8 36.2 34.6 33.5 31. 1 28.7 28.8 26.6 24.5 23. 1 22. 3 20.0 17.7 1 5.5 13.2 10.8 Delta T 38.4 36.3 34.2 31.9 30.5 29.6 27.5 2 5.3 2 5.4 23.5 ...

  • Goodman Mfg SSZ140181A - page 22

    22 EXPANDED PERFORM ANCE DA TA MO DEL: SSZ140481A* / CA*F4860*6A *+TX V / MBR 2000**-1 HEA T ING OP ERATION Outdoor A mbient Te mperat ure 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -1 0 MBh 57.8 5 4.7 5 1.5 48. 2 46. 0 44.6 41 .4 38.2 36 .6 33 . 8 31.1 29. 4 28.3 25 .4 22 .5 19.6 16. 8 13.7 D e l t a T 3 4 . 53 2 . 73 0 . 8 2 8 . 8 2 7 . 5 2 ...

  • Goodman Mfg SSZ140181A - page 23

    23 HEA TING SPECIFICA TIONS capacit y btuh c.o.p. 4.8 9.6 1 4.4 19.2 65 22.63 4.23 39.01 55.39 71.77 88.16 60 21.42 4.09 37.80 54.18 70.57 86.95 55 20.16 3.93 36.54 52.92 69.31 85.69 50 18.85 3.75 35.23 51.61 67.99 84.38 45 17.44 3.54 33.82 50.21 66.59 82.97 40 16.20 3.36 32.58 48.96 65.35 81.73 35 14.94 3.16 31.32 47.70 64.09 80.47 30 12.80 2.70 2 ...

  • Goodman Mfg SSZ140181A - page 24

    24 HEA TING SPECIFICA TIONS capaci t y btuh c. o.p . 4. 8 9. 6 14.4 19 . 2 65 51.5 4 4. 44 67. 92 84. 30 1 00. 68 117. 07 60 48.7 9 4. 28 65. 17 81. 55 9 7.9 4 114 .32 55 45.9 2 4. 11 62. 30 78. 68 9 5.0 7 111 .45 50 42.9 3 3. 92 59. 31 75. 69 9 2.0 7 108 .46 45 39.7 3 3. 70 56. 11 72. 49 8 8.8 8 105 .26 40 36.9 0 3. 50 53. 28 69. 66 8 6.0 5 102 .4 ...

  • Goodman Mfg SSZ140181A - page 25

    25 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a ...

  • Goodman Mfg SSZ140181A - page 26

    WIRING DIAGRAMS 26 TO AVOID POSSI BLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DI SCONNECT THE POWER BEFORE SERVI CING. WARNING ! Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. SSZ140[18-60]1A* COM P IO T1 C M A I N R A U X 5 S SR SA 2 1 RCCF SC T2 C L1 L2 C H C F M A I N A U X IO CM ...

Fabbricante Goodman Mfg Categoria Heat Pump

I documenti che otteniamo dal fabbricante del dispositivoGoodman Mfg SSZ140181A possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Goodman Mfg
- manuali per l’uso SSZ140181A
- schede prodotto Goodman Mfg
- opuscoli
- o etichette energetiche Goodman Mfg SSZ140181A
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Goodman Mfg SSZ140181A.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Goodman Mfg SSZ140181A, manuali di manutenzione, brevi manuali o manuali utente Goodman Mfg SSZ140181A. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Goodman Mfg SSZ140181A.

Manuali per l’uso simili

Manuale completo del dispositivo Goodman Mfg SSZ140181A, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Goodman Mfg SSZ140181A dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Goodman Mfg SSZ140181A.

Il manuale per l’uso completo Goodman Mfg, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Goodman Mfg SSZ140181A - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Goodman Mfg SSZ140181A, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Goodman Mfg SSZ140181A che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Goodman Mfg SSZ140181A - che ci dovrebbe aiutare nei primi passi durante l'uso Goodman Mfg SSZ140181A
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Goodman Mfg SSZ140181A
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Goodman Mfg SSZ140181A in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Goodman Mfg SSZ140181A?

Utilizza il modulo sottostante

Se non hai risolto il problema con Goodman Mfg SSZ140181A con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Goodman Mfg SSZ140181A è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)