    Light Commer cial Heat Recovery V entilators VB0002 VB0003 VB0001 600 cfm 700 cfm 1200 cfm Installation, Operation and Service Instructions 06/00 04597 ...

  • Venmar 600 cfm - page 2

    Page 2 Contents 1 Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2 Installation 2.1 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.2 Mounting Location Requirements . . . . . . . . . . . . . . . . . . . . ...

  • Venmar 600 cfm - page 3

    Page 3 1 Safety Considerations Hazards may exist within this equipment because it contains electrical and powerful moving components. Only qualified service personnel should install or service this equipment. Untrained personnel can perform basic maintenance such as maintaining filters. Observe precautions marked in literature and on labels attache ...

  • Venmar 600 cfm - page 4

    Page 4 The supply and exhaust ducts connected to outside, as well as any ducts passing through an unconditioned space, must have a minimum insulation value of R5. In addition, a continuous integral vapor barrier over the duct insulation must be used. Air balancing dampers are recommended for both supply and exhaust ducts to allow for adjustment of ...

  • Venmar 600 cfm - page 5

    Page 5 2.8 Electrical Connections Power A terminal block and strain relief bushing or a junction box is provided for line voltage to make the necessary power connections. The electrical requirements are as follows: Control Box Access For Low Speed Setting (600 cfm/1200 cfm only) Disconnect power to the unit. Remove the four screws securing the cove ...

  • Venmar 600 cfm - page 6

    Page 6 Recirculation Defr ost Module (Optional - Factory Installed) The Recirculation Defrost Module is only available with the 600 cfm and 1200 cfm units. The defrost cycle is electronically controlled in response to the outside temperature 23°F to -22°F (-5°C to -30°C). On a call for defrost, the supply air damper in the recirculation module ...

  • Venmar 600 cfm - page 7

    Page 7 4.2 Balancing Procedur e Before proceeding with balancing, all windows, overhead doors and walk-in doors should be closed and exhaust systems should be turned off. The connections between the flow stations and the ducts must be sealed with tape. Mount the magnehelic gauge in a convenient location where it is level and will not vibrate or be ...

  • Venmar 600 cfm - page 8

    Page 8 Allow the heat recovery core to soak for three hours in warm water and mild soap. Rinse under a heavy stream of water . Fans Blower wheels and fan housing should be checked for dirt build-up. If they appear dirty , it may be necessary to remove the blower assembly and then vacuum the dust out through the fan mouth. See the following page for ...

  • Venmar 600 cfm - page 9

    Page 9 3/8" (10mm) Threaded Rod (Supplied by others) Rubber Vibration Isolater Cabinet Mounted U Channel Wooden Curb (Supplied by others) Bolt to Floor Space must be left to allow connection of drain lines with adequate slope for drainage Dry Contacts Dry Contacts VD0003A Space must be left to allow connection of drain lines with adequate slop ...

  • Venmar 600 cfm - page 10

    Page 10 8.000" [203] 4.000" [102] 8.000" [203] 3.535" [90] 4.000" [102] 28.005" [71 1] 14.000" [356] 5.859" [149] 13.375" [340] 23.500" [597] 2.750" [70] 14.000" [356] 6.500" [165] 8.000" [203] 8.000" [203] 14.103" [358] 7.705" [196] 4.000" [102] 24.500" ...

  • Venmar 600 cfm - page 11

    28.12" [714] 14.00" [356] 4.00" [102] 1.75" [44] 8.00" [203] 2.75" [70] 19.207" [488] 5.125" [130] Access Door Strap Mounting Location Drain Fitting NOTE: For units with the reversed door option, interior components will appear as a mirror image of the above diagram. 49.550" [1259] Line Power Control Box ...

  • Venmar 600 cfm - page 12

    Page 12 41.206" [1047] 40.326" [1024] 20.000" [508] 5.715" [145] 20.620" [524] 14.250" [362] 34.000" [864] 5.125" [130] 19.207" [488] 4.028" [102] 1 1.325" [288] 12.000" [305] 15.000" [381] 20.000" [508] 4.000" [102] 2.750" [70] 1 1.000" [279] 20.000" [508] 9. ...

  • Venmar 600 cfm - page 13

    Page 13 8.00" [203] 1.75" [44] 10.00" [254] 20.00" [508] 2.75" [70] Alimentation électrique Borniers 49.550" [1259] Localisation de la courroie de fixation Aspiration d’air frais Évacuation d’air vicié 5.125" [130] Noyau de récupération de chaleur Option de porte inversée Porte d’accès 15.00" [38 ...

  • Venmar 600 cfm - page 14

    Page 14 10.000" [254] Dimensions in [ ] are in millimeters Center of gravity Direction of airflow HRV700i LBS Kg 32.74 14.85 68.46 31.05 35.20 15.97 73.60 33.38 210.00 1.875" [48] EXHAUST AIR OPENING SUPPL Y AIR OPENING 20.750" [527] 8.000" [203] 10.750" [273] 7.500" [191] 10.605" [269] 12.104" [307] 2.157&qu ...

  • Venmar 600 cfm - page 15

    Page 15 Flow Measuring Station (FMS) Balancing Damper Canvas Vibration Isolator Min. 12" (305mm) Min. 30" (762mm) Reverse Door Option Exhaust Air From Building Fresh Air From Outside Min. 8" (203mm) (Optional) Canvas Vibration Isolator Min. 12" (305mm) VP0001A Min.12" (304mm) Flow Measuring Station (FMS) Balancing Damper (n ...

  • Venmar 600 cfm - page 16

    Page 16 T o Drain Copper or Plastic Pipe Plastic Drain Fittings Plastic Hose W ater T rap Coupler 3/4"NPT Note: All hose, pipe & couplers to be supplied by others TD i All hose, pipe, and couplers to be supplied by others. Plastic Hose W ater T rap 3/4" NPT T o Drain Copper or Plastic Pipe Plastic Drain Fitting Note: T o Drain Coupler ...

  • Venmar 600 cfm - page 17

    Page 17 WALL CONTROL CLASS 2 VOL T AGE Black OCCUPIED TIMER/ SENSOR F F LOW COMMON HIGH Red Green Y ellow NOTE: Connections are all dry contacts except wall control and 24V AC power supply . Use of 24V AC circuit requires isolating contacts (ex. thermostat) to prevent interconnection of Class 2 outputs. VE0002A W all Control JUMPER WALL CONTROL CLA ...

  • Venmar 600 cfm - page 18

    Page 18 JUMPER (factory installed) OCC. CONTROL (field installed) NSB Timer V enmar PN 1604128 1 M 234 5 JUMPER WALL CONTROL CLASS 2 VOL T AGE Black OCCUPIED TIMER/ SENSOR F F LOW COMMON HIGH Red Green Y ellow NOTE: Connections are all dry contacts except wall control and 24V AC power supply . Use of 24V AC circuit requires isolating contacts (ex. ...

  • Venmar 600 cfm - page 19

    Page 19 Control cover plate Control box Remote control access plate Remote wiring terminal block HRV Cabinet VE0001A R ed Low Speed (Red) Remove power before installing or removing JU1-F Extended Defrost Jumper 12 pin 2 pin Med Speed (Blue) Low T o Medium, move the fork connector: T o change the minimum speed setting from from here to here LOW SPEE ...

  • Venmar 600 cfm - page 20

    Page 20 Although the 600 cfm, 700 cfm and 1200 cfm models have good efficiencies, the supply air could be colder than the ambient room air . It is possible to eliminate the discomfort associated with this temperature difference by installing an electric duct heater . This will temper the air before it is distributed throughout the building. The tab ...

  • Venmar 600 cfm - page 21

    Page 21 Appendix H Wiring Diagram Wiring Diagram for 600 cfm unit INTERLOCK (FF) W ALL CONTROL BLACK VE0023A 48445 POWER CONTROL BOARD -t 8 9 10 11 12 13 14 T7 1 2 3 4 5 6 7 T7 BL BL G R Y BK J3 1 J3 2 J3 8 J3 7 J3 6 J3 9 W ALL CONTROL RED OCC./ UNOCC. REMOTE F AN COMMON AUTOTRANSFORMER AL TERNA TE WIRING FOR LOW SPEED AUTOTRANSFORMER OPTION INPUT ...

  • Venmar 600 cfm - page 22

    Page 22 Appendix H Continued Wiring Diagram Wiring Diagram for 700 cfm unit VE0024A J1 6 J1 9 J1 2 K7 J1 3 LO GND L1 NEUT 120VCA 60Hz COLOR CODE 110 VOL TS LOW VOL T AGE AND FIELD WIRE J1 8 1 2 3 4 5 6 7 T7 INTERLOCK (FF) W ALL CONTROL BLACK 8 9 10 11 12 13 14 T7 W ALL CONTROL RED OCC./ UNOCC. REMOTE F AN CONTROL BOX W ALL CONTROL GREEN W ALL CONTR ...

  • Venmar 600 cfm - page 23

    Page 23 Appendix H Continued Wiring Diagram Wiring Diagram for 1200 cfm unit INTERLOCK (FF) W ALL CONTROL BLACK VE0022A . . . . . . JU1 J4 2 1 A B C D E F G 1 2 3 4 5 6 7 8 9 J3 F F I OC OL Y R G B 4 7 6 9 48445 POWER CONTROL BOARD J1 3 2 1 8 1 2 3 J2 COMM. N/C N/O -t DEFROST TEMP . SENSOR 8 9 10 11 12 13 14 T7 1 2 3 4 5 6 7 T7 BL BL G R Y BK J3 1 ...

  • Venmar 600 cfm - page 24

    For technical assistance and warranty information, please call your local supplier . Appendix I T rouble Shooting SYMPTOMS POSSIBLE CAUSES SOLUTIONS Inside air is too dry Over ventilation - speed setting Adjust speed setting too high Dehumidistat setting is too low Set dehumidistat control in a higher position (if applicable) Persistent condensatio ...

Fabbricante Venmar Categoria Ventilation Hood

I documenti che otteniamo dal fabbricante del dispositivoVenmar 600 cfm possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Venmar
- manuali per l’uso 600 cfm
- schede prodotto Venmar
- opuscoli
- o etichette energetiche Venmar 600 cfm
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Venmar 600 cfm.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Venmar 600 cfm, manuali di manutenzione, brevi manuali o manuali utente Venmar 600 cfm. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Venmar 600 cfm.

Manuali per l’uso simili

Manuale completo del dispositivo Venmar 600 cfm, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Venmar 600 cfm dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Venmar 600 cfm.

Il manuale per l’uso completo Venmar, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Venmar 600 cfm - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Venmar 600 cfm, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Venmar 600 cfm che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Venmar 600 cfm - che ci dovrebbe aiutare nei primi passi durante l'uso Venmar 600 cfm
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Venmar 600 cfm
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Venmar 600 cfm in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Venmar 600 cfm?

Utilizza il modulo sottostante

Se non hai risolto il problema con Venmar 600 cfm con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Venmar 600 cfm è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)