Manuale per l’uso National Instruments CFP-CTR-502

22 pagine 0.44 mb
Scarica

Vai alla pagina of 22

Summary
  • National Instruments CFP-CTR-502 - page 1

    323324B-01 June 2003 © 2002–2003 Nationa l Instruments Corp. A ll rights res erved. FieldPoint™, Nati onal Instruments™, NI™, and ni.com™ are trademarks of N ational Instruments Corpo ration. Product and company names ment ioned herein are trademark s or trade names of their respecti ve companies. For patents covering National Inst rumen ...

  • National Instruments CFP-CTR-502 - page 2

    FP-CTR-502 and cFP-CTR-502 2 ni.com Installing the FP-CTR-502 The FP-CTR-502 mounts on a FieldPoint terminal base (FP-TB- x ), which provides operating po wer to the module. Instal ling the FP-CTR-502 onto a po wered termin al base does not disrupt the operation of the FieldPoint bank. T o install the FP-CTR-502, refer to Figure 1 and complete the ...

  • National Instruments CFP-CTR-502 - page 3

    © National Instruments Corp. 3 FP-CTR-502 and cFP-CTR-502 2. Press firmly to seat the cFP-CTR-502 on the backplane. 3. Using a number 2 Phillips scre wdri ver with a shank of at least 64 mm (2.5 in.) length, tighten the capti v e scre ws to 1.1 N ⋅ m (10 lb ⋅ in.) of torque. The nylon coating on the screws pre v ents them from loosening. Figur ...

  • National Instruments CFP-CTR-502 - page 4

    FP-CTR-502 and cFP-CTR-502 4 ni.com Use a 5–30 VDC external po wer s upply for the input channels. The power supply must provid e e nough current to po wer all of the input channels and all of the f i eld de vices on the output channels. Connect the external po wer supply to multiple V and V SUP terminals and to multiple C and COM t erminals as n ...

  • National Instruments CFP-CTR-502 - page 5

    © National Instruments Corp. 5 FP-CTR-502 and cFP-CTR-502 Inputs Each input channel has one input terminal, V IN . Each channel also has V SUP and COM terminals that can supply power to f ield de vices or provide additional conne ctions to the external po wer supply . Y ou can connect the eigh t count-input channels and four gate-input channels to ...

  • National Instruments CFP-CTR-502 - page 6

    FP-CTR-502 and cFP-CTR-502 6 ni.com V IN is 21 V or lower , a nd an OF F state when V IN is 22 V or higher . The channel state is indeterminate when V IN is between 21 V a n d2 2V . Ensure that the sinking-output de vices ha v e OFF state leak age currents of less than 0.3 mA so they do not send false ON state readings to the [c]FP-CTR-502. Note Yo ...

  • National Instruments CFP-CTR-502 - page 7

    © National Instruments Corp. 7 FP-CTR-502 and cFP-CTR-502 Figure 4. Wiring an O utput Channel to a Sourcing-Input Device If you connect a [c]FP-CTR-502 output to an e xternally po wered sourcing-input device, be a ware th at the voltage applied to the V OUT terminal b y the exte rnal de vice must not exceed the volta ge lev el of the po wer supply ...

  • National Instruments CFP-CTR-502 - page 8

    FP-CTR-502 and cFP-CTR-502 8 ni.com Configuring Count-Input Channels Channels 0 –7 are count-input channels. In FieldPoint software, you can conf igure each count-i nput channel to operate with attributes and comman ds. In th e Channel Conf iguration dialog box, select attrib utes for ea ch channel from the Attributes menu and commands from the C ...

  • National Instruments CFP-CTR-502 - page 9

    © National Instruments Corp. 9 FP-CTR-502 and cFP-CTR-502 to Channel 0, Channel 0 to Chan nel 7, Channel 7 to Channel 6, and so on. If you select this op ti on for all of the channels, no counting occurs. Gate Source Select Gate Input 0 –3 from the V alue menu to associate a gate-input channel with a count-i nput channel. If the count-input chan ...

  • National Instruments CFP-CTR-502 - page 10

    FP-CTR-502 and cFP-CTR-502 10 ni.com Noise Rejection Each count-input channel has a so ftware-enabled lo wpass f ilter that you can set to reject freque ncies abov e 200 Hz or 50 kHz. Select 200 Hz or 50 kHz from the V alue menu to configure noise rejection. The default is 50 kHz. Control Y ou can set the Control command to increment or reset by se ...

  • National Instruments CFP-CTR-502 - page 11

    © National Instruments Corp. 1 1 FP-CTR-502 and cFP-CTR-502 Output Mode For each output channe l select one of the follo wing output modes from the V alue menu : Toggle, Reset Off ; Toggle, Reset On ; On Pulse ; or Off Pulse . The output modes work only if you select Counter Channel 0 –7 for the Output Source . The follo wing sections describe t ...

  • National Instruments CFP-CTR-502 - page 12

    FP-CTR-502 and cFP-CTR-502 12 ni.com On Pulse In On Pulse mode, the output ch annel starts low and goes high when the terminal count is e xce eded. The output channel returns to low after one count. In Figure 9, the terminal count is 4. Figure 9. Output of a Channel Set to On Puls e Mode Off Pulse In Of f Pulse mode, the output ch annel starts high ...

  • National Instruments CFP-CTR-502 - page 13

    © National Instruments Corp. 1 3 FP-CTR-502 and cFP-CTR-502 Application Note: Generating a Contin uous Pulse T rain Y ou can use two [c]FP-CTR-502 count-input cha nnels and one output channel to generate a co ntinuous pulse train with a controllable duty cycle and period . The f irst count-input channel serves as a clock prescaler and di vides the ...

  • National Instruments CFP-CTR-502 - page 14

    FP-CTR-502 and cFP-CTR-502 14 ni.com 4. Set the Count Source of the pr escaler cou nter to the clock on which you want to base your pul se train. This can be the external counter input or one of the [c]FP-CTR-502 internal references. 5. Subtract 1 from the value that you w ant to divide the input clock by , and set the terminal c ount of the presca ...

  • National Instruments CFP-CTR-502 - page 15

    © National Instruments Corp. 1 5 FP-CTR-502 and cFP-CTR-502 T o determine the frequenc y of the output from the pulse counter , use the follo wing formula: where f pulse is the pulse counter output frequency f pre is the prescaler c ounter output frequency term pulse is the terminal count value for the pulse counter Step 3. Configure the Pulse T r ...

  • National Instruments CFP-CTR-502 - page 16

    FP-CTR-502 and cFP-CTR-502 16 ni.com Status Indicators Figure 12 shows the status indica tor LEDs on the [c]FP-CTR-502 . Figure 12. Status Indicators The [c]FP-CTR-502 has two green status LEDs, POWER and READY . After you install the [c]FP-CTR-502 onto a terminal base or backplane and apply po wer to the connected network module, the green POWER i ...

  • National Instruments CFP-CTR-502 - page 17

    © National Instruments Corp. 1 7 FP-CTR-502 and cFP-CTR-502 Follo w these guideli nes to ensure a safe total system. • The [c]FP-CTR -50 2 has a safety isolation barrier between the I/O channels and the inter-modu le commu nication b us. Th ere is no isolation between channe ls unless otherwise noted. If any of the channels on a module are wired ...

  • National Instruments CFP-CTR-502 - page 18

    FP-CTR-502 and cFP-CTR-502 18 ni.com Specifications The follo wing specif ications are typical for a range of – 40 to 70 °C unless otherwise noted. 1 Input Characteristic s Number of channels ... ........... ............ 12 (8 count, 4 gate) Input type ............ ...................... ........ 5–30 VDC sourcing , compatible with TTL devices ...

  • National Instruments CFP-CTR-502 - page 19

    © National Instruments Corp. 1 9 FP-CTR-502 and cFP-CTR-502 Maximum output current Per channel .......... ........... ........... . 1 A Across all channe ls .................. ... 4 A Output impedance ... .............. ........... . 0.12 Ω Output bandwidth ................. ............ 16 kHz for a cu rrent flow ≥ 3.2 mA Maximum of f-state l ...

  • National Instruments CFP-CTR-502 - page 20

    FP-CTR-502 and cFP-CTR-502 20 ni.com Shock and Vibration These specifications apply only to the cFP-CTR-502. NI recommends Compact FieldPoi nt if your application is subject to shock and vibration. Operating vibration, random (IEC 60068-2-64)....... ........... ............ 1 0 –500 Hz, 5 g rms Operating vibration, sinusoidal (IEC 60068-2-6)..... ...

  • National Instruments CFP-CTR-502 - page 21

    © National Instruments Corp. 2 1 FP-CTR-502 and cFP-CTR-502 CE Compliance This product meets the essentia l requirements of applicable European Directi v es, as amended for CE Marking, as follo ws: Lo w-V oltage Directi v e (s afety). ..... ... 73/23/EEC Electromagnet ic Compatibility Directiv e (EMC) ... ........... ......... ........ 89/336/EEC ...

  • National Instruments CFP-CTR-502 - page 22

    FP-CTR-502 and cFP-CTR-502 22 ni.com Where to Go for Support For more information about settin g up the FieldPoint system, refer to these National Instruments documents: • FieldPoint network module user manual • Other FieldPo int I/O m odule operating instructions • FieldPoint terminal base and connector block operating instructions Go to ni. ...

Fabbricante National Instruments Categoria Network Card

I documenti che otteniamo dal fabbricante del dispositivoNational Instruments CFP-CTR-502 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici National Instruments
- manuali per l’uso CFP-CTR-502
- schede prodotto National Instruments
- opuscoli
- o etichette energetiche National Instruments CFP-CTR-502
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso National Instruments CFP-CTR-502.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione National Instruments CFP-CTR-502, manuali di manutenzione, brevi manuali o manuali utente National Instruments CFP-CTR-502. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto National Instruments CFP-CTR-502.

Manuale completo del dispositivo National Instruments CFP-CTR-502, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare National Instruments CFP-CTR-502 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti National Instruments CFP-CTR-502.

Il manuale per l’uso completo National Instruments, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale National Instruments CFP-CTR-502 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice National Instruments CFP-CTR-502, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per National Instruments CFP-CTR-502 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo National Instruments CFP-CTR-502 - che ci dovrebbe aiutare nei primi passi durante l'uso National Instruments CFP-CTR-502
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del National Instruments CFP-CTR-502
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio National Instruments CFP-CTR-502 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su National Instruments CFP-CTR-502?

Utilizza il modulo sottostante

Se non hai risolto il problema con National Instruments CFP-CTR-502 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con National Instruments CFP-CTR-502 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)