    FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE TECHNICAL GUIDE SPLIT -SYSTEM A IR CONDITIONERS 13 SEER A Y012MA321 THRU 036 (1 THRU 3 NOMINAL T ONS, 1 PH) Due to conti nu ou s prod uc t improvement, speci fic a t io ns are subject to change with out notice. V isit us on the web at www .york.com for the most up-to-date techni cal ...

  • York AY012MA321 - page 2

    246814-YTG-D-0606 2 Unitary Products Group 1. Dual element fuses or HACR circuit breaker . 2. The Unit Charge is correct for the out door unit, matched indoor coil and 15 feet of re frig erant tubing. For tubing lengt hs o t her than 15 feet, add or subtract the amo unt of refrigerant, using the dif ference in length multiplied by the per foot valu ...

  • York AY012MA321 - page 3

    246814-YTG-D-0606 Unitary Products Group 3 Additional R-22 Charge / TXV for V arious Matched Systems Outdoor Unit A Y012MA321 A Y018MA321 A Y024MA321 A Y030MA321 A Y036MA321 Required TXV 1 TVM2A1 1 TVM2A1 1 TVM2A1 1 TVM2A1 1 TVM2A1 Factory R-22 Charge, lbs-oz 2 - 14 2 - 14 3 - 6 3 - 14 3 - 8 Indoor Coil1 Coil Orifice2 TXV Kit3 - Additional Charge, ...

  • York AY012MA321 - page 4

    246814-YTG-D-0606 4 Unitary Products Group FOOTNOTES: * This system does not achieve 13 SE ER 1. Systems matched with furnace or air hand lers not equipped with blower-off delays may re quire blower T ime Delay Kit #6918A501 1 2. These orifices are factory mounted in the flow device of each indoor coil 3. A TXV kit must be used with these coi l s t ...

  • York AY012MA321 - page 5

    246814-YTG-D-0606 Unitary Products Group 5 1. G4FD coils available with a factory inst alled horizont a l drain pan. See price p ages for specific model number . 2. Single phase unit s require single phase 2HK heaters. COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL ELECTRIC 2 HEAT KW W RATED CFM NET MB ...

  • York AY012MA321 - page 6

    246814-YTG-D-0606 6 Unitary Products Group 1. Requires a 2FD Blower T ime Delay unless a standard furnace is equipped with one. 2. TXV = Use 1 TVM2* kit on non-fact ory installed TXV coils. ** Refer to Quick Selection Chart for specific fu rnace mat ch-up. COOLING CAP ACI TY - Upflow , Downflow , & Horizontal Furnaces and Coils UNIT MODEL FURNA ...

  • York AY012MA321 - page 7

    246814-YTG-D-0606 Unitary Products Group 7 COOLING CAP ACI TY - V ariable S peed Furnaces UNIT MODEL V ARIABLE S PEED COIL MODEL W COOLING FURNACE MODEL RATED CFM NET MBH SEER EER T OTAL SENS. A Y018MA321 PV8*A12 FC/MC/PC18A 14 600 18.4 12.8 14.50 12.00 PV8*B16 FC/MC/PC18B 17 600 18.4 12.8 14.50 12.00 PV9*A12 FC/MC/PC18A 14 600 18.3 12.7 14.00 1 1. ...

  • York AY012MA321 - page 8

    246814-YTG-D-0606 8 Unitary Products Group 1. G4FD coils available with a factory inst alled horizont a l drain pan. See price p ages for specific model number . 2. V ariable speed furnaces have B.O.D. (Blower on Delay) standard. COOLING CAPACITY - V ARIABLE SPEED FURNACES (CONTINUED) UNIT MODEL V ARIABLE S PEED COIL MODEL W COOLING FURNACE MODEL R ...

  • York AY012MA321 - page 9

    246814-YTG-D-0606 Unitary Products Group 9 ACCESSORIES* Refer to Price Manual for specific mo del numbers. OFF CYCL E TIMER DELA Y - Provides a 5-minute off cycle to pre- vent rapid recycling of the compressor . ROOM THERMOST A T S - A wide selection of compatible thermoset s are available to provide optimum performance and features f or any instal ...

  • York AY012MA321 - page 10

    246814-YTG-D-0606 10 Unitary Products Group TYPICAL INST ALLA TION THERMOSTA T SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT TO INDOOR COIL TO FURNACE OR AIR HANDLER TERMINAL BLOCK NEC CLASS 2 WIRING NEC CLASS 1 WIRING NOTE :ALL OUTDOOR WIRING MUST BE WEATHERPROOF . CONTROL ACCESS P ANEL WEATHERPROOF DISCONNECT SWITCH MINIMUM 24” SERVICE ACCESS CLE ...

  • York AY012MA321 - page 11

    246814-YTG-D-0606 Unitary Products Group 11 Multipliers for determining the perfo rmance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increase s by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree belo ...

  • York AY012MA321 - page 12

    246814-YTG-D-0606 12 Unitary Products Group Multipliers for determining the perfo rmance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM per degree belo ...

  • York AY012MA321 - page 13

    246814-YTG-D-0606 Unitary Products Group 13 Multipliers for determining the perfo rmance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increase s by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree belo ...

  • York AY012MA321 - page 14

    246814-YTG-D-0606 14 Unitary Products Group Multipliers for determining the perfo rmance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM per degree belo ...

  • York AY012MA321 - page 15

    246814-YTG-D-0606 Unitary Products Group 15 Multipliers for determining the perfo rmance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increase s by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree belo ...

  • York AY012MA321 - page 16

    Subject to change without notice. Printed in U. S.A. 246814-YTG-D-0606 Copyright © by Y ork International Corp. 20 06. All rights reserved. Supersedes: 246814-YTG-C-0506 Unitary 5005 Norman Product Y ork OK Group Drive 73069 NOTES ...

Fabbricante York Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoYork AY012MA321 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici York
- manuali per l’uso AY012MA321
- schede prodotto York
- opuscoli
- o etichette energetiche York AY012MA321
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso York AY012MA321.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione York AY012MA321, manuali di manutenzione, brevi manuali o manuali utente York AY012MA321. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto York AY012MA321.

Manuali per l’uso simili

Manuale completo del dispositivo York AY012MA321, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare York AY012MA321 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti York AY012MA321.

Il manuale per l’uso completo York, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale York AY012MA321 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice York AY012MA321, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per York AY012MA321 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo York AY012MA321 - che ci dovrebbe aiutare nei primi passi durante l'uso York AY012MA321
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del York AY012MA321
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio York AY012MA321 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su York AY012MA321?

Utilizza il modulo sottostante

Se non hai risolto il problema con York AY012MA321 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con York AY012MA321 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)