  • York TCGF24 THRU 60 - page 1

    TECHNICAL GUIDE SPLIT -SYSTEM AIR CONDITIONERS 14.5 SEER – R-410A MODE LS: TCGF24 THRU 60 (2 THRU 5 NOMINAL TONS, 1 PHASE) Due to continuou s product improvem ent, specifications are subject to change without notice. Visit us on the web at www .york.com Additional rating information can be found at www .ahridirectory.org W ARRANTY S tandard 5-yea ...

  • York TCGF24 THRU 60 - page 2

    413434-LTG-E-0909 2 Johnson Controls Unitary Products All dimensions are in inche s. They are subject to change with- out notice. Certified dimensions will be provi ded upon request. Physical and Electrica l Data MODEL TCGF24S41S1 TCGF30S41S1 TCGF36S41S1 TCG F42S41S1 TCGF48S41S1 TCGF60S41S1 Unit Supply V oltage 208-230V , 1  60Hz Normal V olt ...

  • York TCGF24 THRU 60 - page 3

    413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 3 PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refrigerant for the co ndenser , the smallest evaporator and 15 feet of interconnecting line tub ing. 2. V erify the TXV or orifice and additional charge required for specific evaporator co il in the system u sing the abo ...

  • York TCGF24 THRU 60 - page 4

    413434-LTG-E-0909 4 Johnson Controls Unitary Products COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 14.5 SEER AC WITH MA TCGF24S41S1 MA08B 17 FC/MC24B 800 24.8 17.3 14.35 12.15 MA08B 17 FC/MC30B 800 24.8 17.3 14.35 12.15 MA08B 17 FC/MC35B 800 25.0 17.6 14.50 1 ...

  • York TCGF24 THRU 60 - page 5

    413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 5 14.5 SEER AC WITH MV - V ARIABLE SPEED (Continued) TCGF36S41S1 MV12B 17 FC/MC35B 1200 35.0 25.8 15.00 12.50 MV16C 21 FC/MC35C 1200 35.2 26.0 15.75 13.00 MV12B 17 FC/MC36B 1200 34.8 25.4 15.00 12.75 MV16C 21 FC/MC36C 1200 35.0 25.6 15.50 13.00 MV12B 17 FC/MC43B 1200 35.8 26.4 15.50 13.00 MV16C ...

  • York TCGF24 THRU 60 - page 6

    413434-LTG-E-0909 6 Johnson Controls Unitary Products — = Not applicable. TCGF30S41S1 AHP36 21 – 1000 29.6 21.4 14.30 12.20 AHX30 17 – 1025 29.6 22 .0 15.25 13.00 AHX36 21 – 1005 30.2 22 .6 16.25 13.00 AHX42 21 – 990 30.6 22.8 16.50 13.25 AHX48 24 – 1090 31.0 23 .6 16.50 13.25 F6FP030 17 – 1035 29.2 21.8 15.00 12.75 F6FP036 21 – 980 ...

  • York TCGF24 THRU 60 - page 7

    413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 7 COOLING CAP ACITY - Upflow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TE D CFM NET MBH SEER 1 EER TOT AL SE NS . TCGF24S41S1 600 - 1000 14,17 FC/MC/PC24 800 24.8 17.3 14.00 12.00 600 - 1000 14,17 FC/MC/PC30 800 24.8 17.3 1 ...

  • York TCGF24 THRU 60 - page 8

    413434-LTG-E-0909 8 Johnson Controls Unitary Products COOLING CAP ACITY - With High Efficiency Motor Fu rnaces UNIT MODEL FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT AL SENS. 14.5 SEER AC WITH V ARIABLE SPEED FURNACES 2 TCGF24S41S1 T*(8,L)X*A12 FC/MC/PC24A 14 775 25.4 18.6 15.50 13.20 T*(8,L)X*B12 FC/MC/PC24B 17 835 25.6 19 ...

  • York TCGF24 THRU 60 - page 9

    413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 9 TCGF24S41S1 (L*9C/T*9V)*B12 FC/MC/PC35B 17 815 24.0 17.0 15.75 13.25 L*(8,L)C*A12 FC/MC/PC36A 14 805 24.0 17.0 16.00 13.50 L*(8,L)C*B12 FC/MC/PC36B 17 765 24.0 16.7 15.75 13.50 (L*9C/T*9V)*B12 FC/MC/PC36B 17 815 24.0 17.1 15.75 13.50 L*(8,L)C*A12 FC/MC/PC37A 14 805 24.0 16.9 16.00 13.50 L*(8,L ...

  • York TCGF24 THRU 60 - page 10

    413434-LTG-E-0909 10 Johnson Controls Unitary Products TCGF30S41S1 T*9X*C16 FC/MC/PC48C 21 1075 30.8 23.4 16.00 13.25 T*9X*C20 FC/MC/PC48C 21 745 29.0 20.2 16.00 13.25 T*9X*D20 FC/MC/PC48D 24 780 29.2 20.6 16.00 13.25 T*(8,L)X*A12 UC30A 14 1035 29.4 21.8 15.25 13.00 T*(8,L)X*B12 UC30B 17 1 1 10 29 .8 22.6 15.50 13.25 T*9X*B12 UC30B 17 1080 29.8 22. ...

  • York TCGF24 THRU 60 - page 11

    413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 11 TCGF36S41S1 T*(8,L)X*B12 FC/MC/PC35B 17 1290 34.6 25.8 15.25 12.75 T*(8,L)X*C16 FC/MC/PC35C 21 1 105 34.0 24.4 15.50 12.75 T*(8,L)X*C20 FC/MC/PC35C 21 1225 34.4 25.4 15.50 12.75 T*9X*B12 FC/MC/PC35B 17 1265 34.2 25.2 14.75 12.25 T*9X*C16 FC/MC/PC35C 21 1270 34.4 25.2 15.25 12.75 T*9X*C20 FC/M ...

  • York TCGF24 THRU 60 - page 12

    413434-LTG-E-0909 12 Johnson Controls Unitary Products TCGF36S41S1 L*(8,L)C*C20 FC/MC/PC43C 21 1 190 35.0 25.6 15.75 13.00 (L*9C/T*9V)*C16 FC/MC/PC43C 21 1240 34.8 25.6 15.25 12.75 (L*9C/T*9V)*C20 FC/MC/PC43C 21 1200 35.0 25.6 15.50 13.00 L*(8,L)C*C16 FC/MC/PC48C 21 1210 35.6 26.2 16.00 13.25 L*(8,L)C*C20 FC/MC/PC48C 21 1 155 35.6 26.4 16.25 13.50 ...

  • York TCGF24 THRU 60 - page 13

    413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 13 TCGF42S41S1 T*9X*D20 HD4 8 24 1460 47.5 27.4 14.75 12.50 T*(8,L)X*C16 UC48C 21 1400 40.0 29.8 14.90 12.65 T*(8,L)X*C20 UC48C 21 1515 40.5 30.8 14.90 12.65 T*9X*C16 UC48C 21 1425 39.5 29.6 14.50 12.25 T*9X*C20 UC48C 21 1420 40.0 29.6 14.50 12.25 T*9X*D20 UC48D 24 1435 40.0 29.8 14.50 12.25 L*( ...

  • York TCGF24 THRU 60 - page 14

    413434-LTG-E-0909 14 Johnson Controls Unitary Products TCGF48S41S1 T*(8,L)X*C16 FC/MC/PC48C 21 1600 47.0 33.8 14.50 12.25 T*(8,L)X*C20 FC/MC/PC48C 21 1660 47.5 33.8 14.75 12.50 T*9X*C16 FC/MC/PC48C 21 1565 47.0 33 .8 14.50 12.25 T*9X*C20 FC/MC/PC48C 21 1615 47.5 33 .8 14.75 12.50 T*9X*D20 FC/MC/PC48D 24 1635 47.0 33 .8 14.50 12.25 T*(8,L)X*C16 FC/P ...

  • York TCGF24 THRU 60 - page 15

    413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 15 TCGF48S41S1 (L*9C/T*9V)*C16 HD60 21 1590 47.0 33.4 14.75 12.50 (L*9C/T*9V)*C20 HD60 21 1655 47.0 33.4 14.75 12.50 (L*9C/T*9V)*D20 HD60 24 1615 47.0 33.4 14.75 12.50 TCGF60S41S1 T*(8,L)X*C 20 FC/PC60C 21 1605 55.0 37.2 13.75 11 . 8 0 T*(8,L)X*C 20 FC/MC62D 21 1665 56.0 37.8 14.50 12.50 T*9X*C2 ...

  • York TCGF24 THRU 60 - page 16

    413434-LTG-E-0909 16 Johnson Controls Unitary Products ACCESSORIES Refer to Price Manual for specific model numbers. Off Cycle Timer Delay - Provides a 5-minute off cycle to pre- vent rapid recycling of the compressor . Hard St a rt Kit - Required when using TXV indoor coil. Also, provides increased starting torque for areas with low voltage. Therm ...

  • York TCGF24 THRU 60 - page 17

    413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 17 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree a bove the listed temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • York TCGF24 THRU 60 - page 18

    413434-LTG-E-0909 18 Johnson Controls Unitary Products Furnaces Coils T .C. S.C. KW T*(8,L)X*A12 FC/MC/PC24A 1.04 1.07 0.92 T*(8,L)X*B12 FC/MC/PC24B 1.05 1.10 0.92 T*9X*B12 FC/MC/PC24B 1.04 1.07 0.92 T*(8,L)X*A12 FC/MC/PC30A 1.04 1.07 0.92 T*(8,L)X*B12 FC/MC/PC30B 1.05 1.10 0.92 T*9X*B12 FC/MC/PC30B 1.04 1.07 0.92 T*(8,L)X*A12 FC/MC/PC32A 1.05 1.10 ...

  • York TCGF24 THRU 60 - page 19

    413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 19 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree a bove the listed temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • York TCGF24 THRU 60 - page 20

    413434-LTG-E-0909 20 Johnson Controls Unitary Products Furnaces Coils T .C. S.C. KW T*(8,L)X*A12 FC/MC/PC30A 1.00 1.01 0.94 T*(8,L)X*B12 FC/MC/PC30B 0.99 0.98 0.91 T*9X*B12 FC/MC/PC30B 1.00 1.02 0.94 T*(8,L)X*A12 FC/MC/PC32A 0.99 0.98 0.95 T*(8,L)X*B12 FC/MC/PC35B 1.02 1.04 0.94 T*(8,L)X*C16 FC/MC/PC35C 1.02 1.05 0.92 T*(8,L)X*C20 FC/MC/PC35C 0.98 ...

  • York TCGF24 THRU 60 - page 21

    413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 21 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree a bove the listed temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • York TCGF24 THRU 60 - page 22

    413434-LTG-E-0909 22 Johnson Controls Unitary Products Furnaces Coils T .C. S.C. KW T*(8,L)X*B12 FC/MC/PC35B 1.01 1.03 0.95 T*(8,L)X*C16 FC/MC/PC35C 0.99 0.97 0.91 T*(8,L)X*C20 FC/MC/PC35C 1.00 1.01 0.92 T*9X*B12 FC/MC/PC35B 0.99 1.00 0.95 T*9X*C16 FC/ MC/PC35C 1.00 1.00 0.94 T*9X*C20 FC/ MC/PC35C 1.00 1.01 0.93 T*(8,L)X*A12 FC/MC/PC36A 0.99 0.97 0 ...

  • York TCGF24 THRU 60 - page 23

    413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 23 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree a bove the listed temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • York TCGF24 THRU 60 - page 24

    413434-LTG-E-0909 24 Johnson Controls Unitary Products Furnaces Coils T .C. S.C. KW T*(8,L)X*B12 FC/MC/PC43B 0.99 0.98 0.94 T*(8,L)X*C16 FC/MC/PC43C 1.02 1.03 0.95 T*(8,L)X*C20 FC/MC/PC43C 1.01 1.02 0.94 T*9X*B12 FC/MC/PC43B 0.97 0.94 0.94 T*9X*C16 FC/ MC/PC43C 1.01 1.01 0.95 T*9X*C20 FC/ MC/PC43C 1.01 1.01 0.94 T*(8,L)X*C16 FC/MC/PC48C 1.02 1.02 0 ...

  • York TCGF24 THRU 60 - page 25

    413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 25 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree a bove the listed temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • York TCGF24 THRU 60 - page 26

    413434-LTG-E-0909 26 Johnson Controls Unitary Products Furnaces Coils T .C. S.C. KW T*(8,L)X*C16 FC/MC/PC48C 1.01 1.02 0.96 T*(8,L)X*C20 FC/MC/PC48C 1.01 1.02 0.95 T*9X*C16 FC/ MC/PC48C 1.01 1.02 0.96 T*9X*C20 FC/ MC/PC48C 1.01 1.02 0.95 T*9X*D20 FC/ MC/PC48D 1.01 1.02 0.96 T*(8,L)X*C16 FC/PC60C 1.00 1.00 0.96 T*(8,L)X*C20 FC/MC/PC60D 1.01 1.01 0.9 ...

  • York TCGF24 THRU 60 - page 27

    413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 27 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree a bove the listed temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • York TCGF24 THRU 60 - page 28

    Subject to change without notice. Publishe d in U.S.A. 413434-LTG-E-0909 Copyright © 2009 by Johnson Controls, Inc. All rights reserved. Supersedes: 413434-LTG-D-0509 Johnson Controls Unit ary Products 5005 Y ork Drive Norman, OK 73069 NOTES ...

Fabbricante York Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoYork TCGF24 THRU 60 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici York
- manuali per l’uso TCGF24 THRU 60
- schede prodotto York
- opuscoli
- o etichette energetiche York TCGF24 THRU 60
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso York TCGF24 THRU 60.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione York TCGF24 THRU 60, manuali di manutenzione, brevi manuali o manuali utente York TCGF24 THRU 60. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto York TCGF24 THRU 60.

Manuali per l’uso simili

Manuale completo del dispositivo York TCGF24 THRU 60, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare York TCGF24 THRU 60 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti York TCGF24 THRU 60.

Il manuale per l’uso completo York, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale York TCGF24 THRU 60 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice York TCGF24 THRU 60, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per York TCGF24 THRU 60 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo York TCGF24 THRU 60 - che ci dovrebbe aiutare nei primi passi durante l'uso York TCGF24 THRU 60
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del York TCGF24 THRU 60
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio York TCGF24 THRU 60 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su York TCGF24 THRU 60?

Utilizza il modulo sottostante

Se non hai risolto il problema con York TCGF24 THRU 60 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con York TCGF24 THRU 60 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)