    Model 109SS Temperature Probe Revision: 12/10 Copyright © 1983-2010 Campbell Scientific, Inc. ...

  • Campbell TEMPERATURE PROBE 109SS - page 2

    Warranty and Assistance The MODEL 109SS TEMPERATURE PROBE FOR HARSH ENVIRONMENTS is warranted by Campbell Scientific, Inc. to be free from defects in mat erials and workma nship under normal use and servi ce for twelve (12) months from date of shipm ent unless specified otherwi se. Batteri es have no warranty. Cam pbell Scienti fic, Inc. 's ob ...

  • Campbell TEMPERATURE PROBE 109SS - page 3

    109SS Table of Contents PDF viewers note: These page numbers refer to the printed version of this document. Use the Adobe Acrobat® bookmarks tab for links to specific sections. 1. General ......................................................................... 1 1.1 Specifications................................................................... ...

  • Campbell TEMPERATURE PROBE 109SS - page 4

    ...

  • Campbell TEMPERATURE PROBE 109SS - page 5

    Model 109SS Temperature Probe 1. General The –L portion of this probe’s m odel number i ndicates the probe has a user- specified lead length. For readab ility purposes, the pro b e will be referred to as the 109SS throughout this docum ent. The 109SS consists of a thermistor encas ed in a stainless-steel sheath. The rugged stainless-steel sheat ...

  • Campbell TEMPERATURE PROBE 109SS - page 6

    Model 109SS Temperature Probe 1.1 Specifications Temperature Range: -40° to +70°C Survival Range: -50° to +100°C (thermist or); -50°C to +70°C (overm olded joint and cable) Thermistor Interchangeability Tolerance: Temperature Tolerance -40°C ± 0.6°C 0°C ± 0.38°C 25°C ± 0.1°C 50°C ± 0.3°C 70°C ± 0.45°C Time Constant: Fluid τ St ...

  • Campbell TEMPERATURE PROBE 109SS - page 7

    Model 109SS Temperature Probe 2. Accuracy The overall probe accuracy is a combinati on of the thermi stor's interchangeability specification and the accuracy of the bri dge resistor. The Steinhart and Hart equation used to calculate temperature has a negl igible error (Figure 2-1). In a "worst case" the errors add to an accuracy of ? ...

  • Campbell TEMPERATURE PROBE 109SS - page 8

    Model 109SS Temperature Probe 3. Installation and Wiring 3.1 Burial The 109SS is suitable for shallow burial onl y. It should be placed horizontally at the desired depth to avoid thermal conduction from the surface to the thermistor. Placem ent of the cable in side a rugged conduit may be advisable for long cable runs, especially in locations subje ...

  • Campbell TEMPERATURE PROBE 109SS - page 9

    Model 109SS Temperature Probe The datalogger is programme d using eith er CRBasic or Edlog. Dataloggers that use CRBasic include our CR200( X)-series, CR800, CR850, CR1000, CR3000, CR5000, and CR9000(X); see Section 5.1. Dataloggers t hat use Edlog include our CR10, CR 10(X), CR23X, and CR7; refer t o Section 5.2. CRBasic and Edlog are included in ...

  • Campbell TEMPERATURE PROBE 109SS - page 10

    Model 109SS Temperature Probe 5.1.1.1 Sample Program for CR200(X) Series Datalogger 'CR200(X) Seri es Datalogger ‘This example program measures a single 109SS Thermist or Probe ‘once a second and stores the aver age temperature every 10 minutes. ‘Declare the variable for th e temperature measurement Public Air_Temp ‘Define a data table ...

  • Campbell TEMPERATURE PROBE 109SS - page 11

    Model 109SS Temperature Probe 5.1.1.3 Sample Program for CR5000 'CR5000 'This example program measures a single 109 Thermist or probe 'once a second and stores the aver age temperature every 10 minutes. 'Declare the variable for the temperature. Public Air_Temp 'Declare variables for the raw measurement, t hermistor resista ...

  • Campbell TEMPERATURE PROBE 109SS - page 12

    Model 109SS Temperature Probe Example Program for CR10X ;{CR10X} ; *Table 1 Program 01: 1 Execution Interval (seconds) 1: AC Half Bridge (P5) 1: 1 Reps 2: 25 2500 mV 60 Hz Reject ion Range 3: 1 SE Channel 4: 1 Excite all reps w/Exchan 1 5: 2500 mV Excitati on 6: 1 Loc [ V_Vx ] 7: 1.0 Mult 8: 0.0 Offset 2: Z=1/X (P42) 1: 1 X Loc [ V_Vx ] 2: 2 Z Loc ...

  • Campbell TEMPERATURE PROBE 109SS - page 13

    Model 109SS Temperature Probe 9: Z=X+F (P34) 1: 8 X Loc [ Tk ] 2: -273.15 F 3: 9 Z Loc [ Air_Temp ] 10: If tim e is (P92) 1: 0 Minutes (Seconds --) into a 2: 10 Interval (same uni ts as above) 3: 10 Set Output Flag Hi gh (Flag 0) 11: Real Tim e (P77) 1: 110 Day,Hour/Minut e (midni ght = 0000) 12: Average (P71) 1: 1 Reps 2: 9 Loc [ Air_Temp ] *Table ...

  • Campbell TEMPERATURE PROBE 109SS - page 14

    Model 109SS Temperature Probe 1: Excite-Delay (SE) (P4) 1: 1 Reps 2: 25 2500 mV 60 Hz Rejecti on Range (Delay m ust be zero) 3: 1 SE Channel 4: 1 Excite all reps w/Exchan 1 5: 2 Delay (0.01 sec units) 6: 2500 mV Excitati on 7: 3 Loc [V_Vx ] 8: .0004 Multiplier 9: 0.0 Offset 6. Measurement Details Understanding the detail s in this section are not n ...

  • Campbell TEMPERATURE PROBE 109SS - page 15

    Model 109SS Temperature Probe The resistance of the thermistor is: ⎟ ⎠ ⎞ ⎜ ⎝ ⎛ − = 1 900 , 24 V V R EX t The Steinhart and Hart equation i s used to calculate temperature from Resistance: 3 )) (ln( ) ln( 1 T T K R C R B A T + + = Where T K is the temperature in Kelvin . Th e Steinhart and Ha rt coefficients used in the Therm109 instru ...

  • Campbell TEMPERATURE PROBE 109SS - page 16

    Model 109SS Temperature Probe 12 Symptom: Unstable Tem perature Try using the 60 Hz o r 50 Hz integratio n options, and /o r increasing the settling time as descri bed in Sections 8 and 9. Make sure the clear shi eld wire is connected to datalogger ground, and the dat alogger is properly grounded. ...

  • Campbell TEMPERATURE PROBE 109SS - page 17

    ...

  • Campbell TEMPERATURE PROBE 109SS - page 18

    Campbell Scientific Companies Campbell Scientific, Inc. (CSI) 815 West 1800 Nort h Logan, Utah 84 321 UNITED STATES www.campbellsci.com • info@cam pbellsci.com Campbell Scientific Afri ca Pty. Lt d. (CSAf) PO Box 2450 Somerset West 7129 SOUTH AFRICA www.csafrica.co .za • cleroux@csafrica.co.za Campbell Scientific Aust ralia Pty. Ltd. (CSA) PO B ...

Fabbricante Campbell Categoria Power Supply

I documenti che otteniamo dal fabbricante del dispositivoCampbell TEMPERATURE PROBE 109SS possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Campbell
- manuali per l’uso TEMPERATURE PROBE 109SS
- schede prodotto Campbell
- opuscoli
- o etichette energetiche Campbell TEMPERATURE PROBE 109SS
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Campbell TEMPERATURE PROBE 109SS.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Campbell TEMPERATURE PROBE 109SS, manuali di manutenzione, brevi manuali o manuali utente Campbell TEMPERATURE PROBE 109SS. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Campbell TEMPERATURE PROBE 109SS.

Manuale completo del dispositivo Campbell TEMPERATURE PROBE 109SS, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Campbell TEMPERATURE PROBE 109SS dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Campbell TEMPERATURE PROBE 109SS.

Il manuale per l’uso completo Campbell, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Campbell TEMPERATURE PROBE 109SS - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Campbell TEMPERATURE PROBE 109SS, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Campbell TEMPERATURE PROBE 109SS che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Campbell TEMPERATURE PROBE 109SS - che ci dovrebbe aiutare nei primi passi durante l'uso Campbell TEMPERATURE PROBE 109SS
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Campbell TEMPERATURE PROBE 109SS
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Campbell TEMPERATURE PROBE 109SS in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Campbell TEMPERATURE PROBE 109SS?

Utilizza il modulo sottostante

Se non hai risolto il problema con Campbell TEMPERATURE PROBE 109SS con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Campbell TEMPERATURE PROBE 109SS è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)