Emerson MAS 2600の取扱説明書

28ページ 1.02 mb
ダウンロード

ページに移動 of 28

Summary
  • Emerson MAS 2600 - page 1

    Installa tion & User Ma nual Ed 19 UK June 2013 MAS 2600 Tank Con tents Tra nsmi tte r ...

  • Emerson MAS 2600 - page 2

    Installa tion & User Manual Ed 19 UK June 2013 Page 2 of 28 Table of con ten ts Description and Operation ............................................................................................. 3 MAS2600 Tan k Conte nts Tr ansm itte r .............................................................................................. 3 Applica ...

  • Emerson MAS 2600 - page 3

    Installa tion & User Ma nual June 2013 Ed 19 UK Page 3 of 28 C ERTI FI C ATE RE F. : 4- 20 m A L i n t = 2 0 uH x MARI NE AUT OMATI ON DE NMARK S/N: Um ax = 33 V T Ci nt = 1 0 n F C i EE X a 90- C.95948 T5 am b . : -40 to +85 ° C I 4 5 mA K = < 2600 T WO WI RE T RA NS MI T T E R 2600 SERI ES S/N 46374 1. 5 bar g PDCR- 941-1 MAS 2600 DMS Des ...

  • Emerson MAS 2600 - page 4

    Installa tion & User Manual Ed 19 UK June 2013 Page 4 of 28 0 100 200 300 400 500 600 700 17 20 23 26 29 32 Load resistance (ohm) Power supply (V) Max. load resistanc e at v arious power supply T echnic al Spe cifi cati ons Trans ducer Ra nges: Gauge: 0-3.5 / 0-7 / 0-16 / 0-35 m H 2 O. Absolute: 0-20.394 / 0-35.690 m H 2 O. Progra mmable Mea su ...

  • Emerson MAS 2600 - page 5

    Installa tion & User Ma nual June 2013 Ed 19 UK Page 5 of 28 MAS2600 Or deri ng Infor mati on Typ e A absolute transducer G gaug e transducer H high temperature gaug e transducer Transduce r Ranges 1 3,5 mH 2 O gauge or high tem p. 2 7,0 mH 2 O gauge or high tem p. 3 16,0 mH 2 O gaug e or high temp. 4 35,0 mH 2 O gaug e or 0,8 – 3,5 bar absol ...

  • Emerson MAS 2600 - page 6

    Installa tion & User Manual Ed 19 UK June 2013 Page 6 of 28 Type MAS2600-X XX - XX - X/XX A: Absolute Transducer. The absolute transducer has no breather pipe, because it refers to absolute vacuum. An atmospheric pressure sensor is used to compensate for the atmospheric pressure. The abs olute t rans ducer is es pecial l y suitabl e for open d ...

  • Emerson MAS 2600 - page 7

    Installa tion & User Ma nual June 2013 Ed 19 UK Page 7 of 28 M AS 2600 Am pli f i er box Fl ange mounted G022P 013 Sensor pos . above l owest poi nt T ankhei ght V ent pi pe hei ght TWO WIRE TRANSM ITTER 2600 SERIES 90-C.95948 T5 Cint = 10 nF C CERTIFICATE REF.: 4-20 mA Lint = 20 uH x i EE X a MARINE AUTOMATION DENMARK S/N: Umax = 33 V T amb.: ...

  • Emerson MAS 2600 - page 8

    Installa tion & User Manual Ed 19 UK June 2013 Page 8 of 28 Absol ute Tr ans duce rs : The Absolute Transmitter is typically used if the amplifier is exposed to water, e.g. on open deck. The Absolu te Transmitter is av ailable i n 2 rang es: 0 -20 and 0-35 mH 2 O. In practice this means 10 mH 2 O less than the nominal range beca use of the atmo ...

  • Emerson MAS 2600 - page 9

    Installa tion & User Ma nual June 2013 Ed 19 UK Page 9 of 28 Class approved Sea valv e TWO WIRE TRAN SMITTER 2600 SERIES 90-C.95948 T5 Cint = 10 nF C CERTIFICATE REF.: 4-20 mA Lint = 20 uH x i EE X a MARINE AUTOMATION DENMARK S/N: Umax = 33 V T amb.: -40 to +85 °C I 45 mA K= < 2600 W eathe r d eck MAS2600 am plifier box Sens or p os. ab ove ...

  • Emerson MAS 2600 - page 10

    Installa tion & User Manual Ed 19 UK June 2013 Page 10 of 28 Brac kets f or In terna l M ounti ng - drawi ng no. G022P010 : Bulkhead T ank bott om TWO WIRE TRAN SMITTER 2600 SERIES 90-C.95948 T5 Cint = 10 nF C CERTIFICATE REF.: 4-20 mA Lint = 20 uH x i EE X a MARINE AUTOMATION DENMARK S/N: Umax = 33 V T amb.: -40 to +85 °C I 45 mA K = < 260 ...

  • Emerson MAS 2600 - page 11

    Installa tion & User Ma nual June 2013 Ed 19 UK Page 11 of 28 19,5 D k d b TWO WI RE TR ANSMI TTE R 2600 SERIES 90-C.95948 T5 Cint = 10 nF C CERTIFICATE REF.: 4-20 mA Lint = 20 uH x i EE X a MARINE AUTOMATI ON DENMARK S/N: Umax = 33 V T amb.: -40 to +85 °C I 45 mA K= < 2600 Tank t op Tank bot t om Bul khe ad 25,0 55, 0 80, 0 34.0 26,0 24.0 ...

  • Emerson MAS 2600 - page 12

    Installa tion & User Manual Ed 19 UK June 2013 Page 12 of 28 Tank bot t om H Bul khe ad Lint = 20 uH CERTIFICATE REF. : 4-20 m A Tank t op x S/N: MARINE AUTOMATI ON DENMARK Umax = 33 V 90-C.95948 TWO WIRE TRAN SMITTER Cint = 10 nF X EE i a T5 C 2600 SERIES I 4 5 mA amb.: -40 to +85 °C < = K T 2600 Bul khe ad Tank bot t om Tank t op TWO WI R ...

  • Emerson MAS 2600 - page 13

    Installa tion & User Ma nual June 2013 Ed 19 UK Page 13 of 28 Tank bot t om Bul khe ad Tank t op 4-20 mA CERTIFICATE REF.: Lint = 20 uH x EE X 2600 amb.: -40 to +85 °C I 45 mA MARINE AUTOMATION DENMARK TWO WIRE TRANSM I TTER 90-C.95948 Umax = 33 V Cint = 10 nF C a i T5 T S/N: < = K 2600 SERIES DN25 f lange wi th 1” ball va lve – dra win ...

  • Emerson MAS 2600 - page 14

    Installa tion & User Manual Ed 19 UK June 2013 Page 14 of 28 Amplifier Box MAS2600- XXX - XX - X/ XX The MAS2600 amplifier box is manufactured in poly ester, which has the strength and stability of aluminium, insulation and resistance properties of plastics. Colour code RAL 7000. The amplifier box is protected to the level of IP 56 and must be ...

  • Emerson MAS 2600 - page 15

    Installa tion & User Ma nual June 2013 Ed 19 UK Page 15 of 28 Amplifier P CB MAS2600- XXX - XX - X/XX The PC B is avail able in different t ypes for the d ifferen t tran s ducers, with or without terminals for Pt100 temperature sensor. 0: Without amplifie r PCB. P or S : Program mable ou tput ran ge. Th e ampli fier can b e cal ibrated t o 4 -2 ...

  • Emerson MAS 2600 - page 16

    Installa tion & User Manual Ed 19 UK June 2013 Page 16 of 28 Handling The MAS2600 transducer is a highly sensitive electronic piece of equipment and proper handling is most importan t. To avoid damaging the transducers : • NEVER lift by the ca ble if transduc er is mounted with fittings. • NEVER remove the protection cap in front of the dia ...

  • Emerson MAS 2600 - page 17

    Installa tion & User Ma nual June 2013 Ed 19 UK Page 17 of 28 Installati on Prior to insta llation pleas e check tha t: • the serial numbers on the transducer, amplifier and lid of amplifier box agree. The serial numbers are to be found on the inside of the lid of the amplifier box on the bottom line - ampli fier S/N and transd ucer S /N on t ...

  • Emerson MAS 2600 - page 18

    Installa tion & User Manual Ed 19 UK June 2013 Page 18 of 28 If the a mplifier bo x is installed in an a rea with over pressure or negative pressure in relation to the atmospheric pressure in the tank, the breather tube must be directed to an area with atmospheric pressure equalling the pressure inside the tank. This applies to ga uge transmitt ...

  • Emerson MAS 2600 - page 19

    Installa tion & User Ma nual June 2013 Ed 19 UK Page 19 of 28 Intrinsi call y S afe Installation The MAS2600 is designed for use in an approved intrinsically safe installation. The amplifier is fitted with a label de scribing the IS category : S/N: XXXXXX- YYY Y DEMKO 11 ATEX 146506X IECEx ULD 10.0013X Ui: 29V Ii: 93 mA Li: 20µH C i: 60 nF Pi: ...

  • Emerson MAS 2600 - page 20

    Installa tion & User Manual Ed 19 UK June 2013 Page 20 of 28 Before in st alling intrins ically safe un its within an ap proved insta llation, it is essential to e nsure that there are no deviations from the conditions of the order or the requirements of the approved block schematic diagram and the following related instructions: 1. No circuits ...

  • Emerson MAS 2600 - page 21

    Installa tion & User Ma nual June 2013 Ed 19 UK Page 21 of 28 4- 20 m A Hazar dous ar ea Saf e ar ea Any 28V / 300R Shunt zener di ode s af t y bar r i er or Ex r epeat er cer t i fi ed to Ex I a I IC. T r ans ducer Am pl i f i er box MARI NE AUT OMATI ON DENMARK Cint = 10 nF 2600 SERIES 4-20 mA CERTIFICATE REF.: Lint = 20 uH x EE X i a C amb.: ...

  • Emerson MAS 2600 - page 22

    Installa tion & User Manual Ed 19 UK June 2013 Page 22 of 28 T esting and R ec alibr ating Please observe that testing and recalibration of sensors mounted in hazardous arias shall be carried out of Ex qualified pe rsonnel. Testin g Before di spatch, the MA S2600 transm itter i s calib rated in ac cord ance wit h the requ irem ents specifi ed i ...

  • Emerson MAS 2600 - page 23

    Installa tion & User Ma nual June 2013 Ed 19 UK Page 23 of 28 Recalibrating Gauge Trans mitter using Vacuu m (for gauge trans mitters only) An internally mounted transducer can also be recalibrated by using vacuum. 1. Check that the tank is empty. 2. Check t hat the ran ge sel ect swi tch on t he ampli fier i s correctl y set. 3. Set the calibr ...

  • Emerson MAS 2600 - page 24

    Installa tion & User Manual Ed 19 UK June 2013 Page 24 of 28 Recalibr ati ng t he Abso lute T ransm itter using Test Cup type G0 22 S100 When recal ibr ating the MAS2600 Absol ute Tran smit ter a press ure cal i brator w ith a range o f -1 to 3.5 bar should be used. It should have an accuracy of 0.05% FS or better, as well as a 4½ digit millia ...

  • Emerson MAS 2600 - page 25

    Installa tion & User Ma nual June 2013 Ed 19 UK Page 25 of 28 EXAMPLE: If the range of the transducer is 3.5 bar abs and the atmospheric pressure is 1005 mbar. Calculated output at atmospheric pressure: mA @ Atm .p ress = 4 16 1005 800 3500 800 + − − * ( ) = 5.215 mA Calculated applied pressure for maximum output: mbarg @ 20 mA = 3500 1005 ...

  • Emerson MAS 2600 - page 26

    Installa tion & User Manual Ed 19 UK June 2013 Page 26 of 28 Maint enance and T r o uble Shooting Mainten an ce Damcos recommends that the following to be checked annually: 1. Visual inspection of the cable, transducer and amplifier. 2. Compare signal with e.g. hand sounding, and if necessary perform a zero and full- scale calibra tion. Trouble ...

  • Emerson MAS 2600 - page 27

    Installa tion & User Ma nual June 2013 Ed 19 UK Page 27 of 28 MAS260 0 Tes t sh eet ATT.: Emerson Process Management Marine Solutions Damcos A /S, Service Departm ent F AX . : +45 5578 7272 Nam e: Ship name: Yard: NB No: MAS2600: Transduce r serial n o.: Amp lifier seri al no.: Tank nam e: Liquid in tank HFO: DO: Ballast: Othe r: Th e tan k is ...

  • Emerson MAS 2600 - page 28

    Installa tion & User Manual Ed 19 UK June 2013 Page 28 of 28 Emerson P rocess Manag ement Damcos A/S Aaderupve j 41 DK - 4700 Naestved T +45 5578 7200 F +45 5578 7272 www. EmersonProcesss. com/mtm ©2013 Emerso n Process Management. All rights res erved. The Emerson logo is a trademark and service mark of Emerson Electric Co. Damcos and the Dam ...

メーカー Emerson カテゴリー Marine Instruments

Emerson MAS 2600のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- MAS 2600の取扱説明書
- Emersonの製品カード
- パンフレット
- またはEmerson MAS 2600の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Emerson MAS 2600の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Emerson MAS 2600の取り付け説明書、サービスマニュアル、簡易説明書、またはEmerson MAS 2600のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Emerson MAS 2600の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Emerson MAS 2600デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがEmerson MAS 2600を使用するのを助ける技術的文書のことです。説明書は通常、全てのEmerson MAS 2600ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Emersonの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Emerson MAS 2600の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははEmerson MAS 2600の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Emerson MAS 2600に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Emerson MAS 2600デバイスの基本機能を使うにあたってのヒント。 Emerson MAS 2600のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Emerson MAS 2600に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるEmerson MAS 2600のメーカー/サービスへの連絡先に関する情報。

Emerson MAS 2600についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもEmerson MAS 2600の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがEmerson MAS 2600で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)