  • Mitsubishi MSZ-GF60VE-E1 - page 1

    SER VICE MANUAL CONTENTS 1. TECHNICAL CHANGES ··································· 3 2. P ART NAMES AND FUNCTIONS ····················· 4 3. SPECIFICA TION ················································ 5 4. NOISE CRITERIA CURVES ·······? ...

  • Mitsubishi MSZ-GF60VE-E1 - page 2

    2 Use the speci fi ed refrigerant only Never use any refrigerant other than that specified. Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failur ...

  • Mitsubishi MSZ-GF60VE-E1 - page 3

    3 MUZ-GF60VE - E1 MUZ-GF71VE - E1 1. New model TECHNICAL CHANGES 1 OBH635 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 4

    4 P ART NAMES AND FUNCTIONS 2 ACCESSORIES Model MUZ-GF60/71VE Drain socket 1 MUZ-GF60VE MUZ-GF71VE Piping Air outlet Drain outlet Air inlet (back and side) Drain hose OBH635 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 5

    5 SPECIFICA TION 3 Outdoor model MUZ-GF60VE MUZ-GF71VE Power supply Single phase, 230 V , 50 Hz Capacity Rated frequency (Min. - Max.) Cooling kW 6.1 (1.4 - 7.5) 7.1 (2.0 - 8.7) Heating 6.8 (2.0 - 9.3) 8.1 (2.2 - 9.9) Breaker Capacity A 20 Electrical data Power input 1 (T otal) Cooling W 1,790 2,130 Heating 1,810 2,230 Running current 1 (T otal) Co ...

  • Mitsubishi MSZ-GF60VE-E1 - page 6

    6 Speci fi cations and rated conditions of main electric parts Model Item MUZ-GF60VE MUZ-GF71VE Smoothing capacitor (CB1, CB2, CB3) 560 μ F 450 V Fuse (F601, F880, F901) T3.15AL250 V IGBT module (IC932) 5 A 600 V (IC700) 20 A 600 V Expansion valve coil (LEV) 12 V DC Reactor (L) 340 μ H Diode module (IC820) 20 A 600 V Circuit protection (PTC64, P ...

  • Mitsubishi MSZ-GF60VE-E1 - page 7

    7 NOISE CRITERIA CUR VES 4 MUZ-GF60VE MUZ-GF71VE T est conditions Cooling: Dry-bulb temperature 35°C Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C OUTDOOR UNIT MICROPHONE 1 m 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 NC-60 NC-50 NC-40 NC-30 NC-20 NC-70 OCT A VE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR B ...

  • Mitsubishi MSZ-GF60VE-E1 - page 8

    8 Unit: mm OUTLINES AND DIMENSIONS 5 MUZ-GF60VE MUZ-GF71VE 417.5 40 42 Drain hole 175 500 330 50 Air in Air out 2-holes 10 21 360 840 109 81 880 452 Service panel 99.5 164.5 195 35 44 Liquid refrigerant pipe joint Refrigerant pipe (flared) Ø 6.35 ( MUZ-GF60VE ) Ø 9.52 ( MUZ-GF71VE ) Gas refrigerant pipe joint Refrigerant pipe (flared) Ø 15.88 35 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 9

    9 WIRING DIAGRAM 6 MUZ-GF60VE MUZ-GF71VE OBH635 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 10

    10 REFRIGERANT SYSTEM DIAGRAM 7 MUZ-GF60VE Unit: mm Outdoor heat exchanger Flared connection Defrost thermistor RT6 1 Discharge temperature thermistor RT6 2 Flared connection Stop valve Stop valve (with service port) Capillary tube ø 4.0 × ø 2.4 × 100 Refrigerant flow in cooling Compressor 4-way valve Refrigerant flow in heating Refrigerant pip ...

  • Mitsubishi MSZ-GF60VE-E1 - page 11

    11 Max. Length A Max. Height difference B Indoor unit Outdoor unit MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE Refrigerant piping: m Piping size O.D: mm Max. Length A Max. Height difference B Gas Liquid MUZ-GF60 30 15 15.88 6.35 MUZ-GF71 9.52 ADDITIONAL REFRIGERANT CHARGE (R410A: g) Model Outdoor unit precharged Refrigerant piping len ...

  • Mitsubishi MSZ-GF60VE-E1 - page 12

    12 The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi- tions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the perform ...

  • Mitsubishi MSZ-GF60VE-E1 - page 13

    13 NOTE: The above broken lines are for the heating operation without any frost and defrost operation. 0.8 0.9 1.0 1.1 1.2 1.3 - 1 0 - 5 0 5 1 01 52 02 53 03 54 04 5 Outdoor intake air Dry-bulb temperature (°C) Input correction factors 26 24 22 20 18 Indoor intake air Wet-bulb temperature( ) Indoor air Wet-bulb temperature difference (°C) 7.9 7.2 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 14

    14 8-2. CAP ACITY AND INPUT CORRECTION BY OPERA TIONAL FREQUENCY OF COMPRESSOR Correction of Cooling capacity Capacity correction factors Correction of Cooling input Input correction factors Correction of Heating capacity Capacity correction factors MUZ-GF60VE Correction of Heating input Capacity correction factors Correction of Cooling capacity Ca ...

  • Mitsubishi MSZ-GF60VE-E1 - page 15

    15 15 20 50 25 60 30 70 35 4.0 5.0 6.0 7.0 8.0 9.0 15 20 50 25 60 30 70 35 4.0 5.0 6.0 7.0 8.0 9.0 MUZ-GF60VE MUZ-GF71VE Ambient temperature(°C) Ambient humidity(%) Am bient temperature ( °C) Amb ien t h umid it y(% ) O ut door current ( A) O ut door current ( A) Outdoor unit current 0 5 10 15 20 25 3.0 3.5 4.0 4.5 5.0 5.5 0 5 10 15 20 25 6 8 10 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 16

    16 PERFORMANCE DA T A COOL operation a t Rated frequency MUZ-GF60VE CAP ACITY : 6.1 kW SHF: 0.79 INPUT : 1790 W INDOOR DB (°C) INDOOR WB (°C) OUTDOOR DB (°C) 21 25 27 30 Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 7.17 4.37 0.61 1432 6.86 4.19 0.61 1504 6.59 4.02 0.61 1575 6.34 3.87 0.61 1647 21 20 7.47 3.66 0.49 1504 7 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 17

    17 PERFORMANCE DA T A COOL operation a t Rated frequency MUZ-GF60VE CAP ACITY : 6.1 kW SHF: 0.79 INPUT : 1790 W INDOOR DB (°C) INDOOR WB (°C) OUTDOOR DB (°C) 35 40 46 Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 5.98 3.65 0.61 1754 5.49 3.35 0.61 1862 5.06 3.09 0.61 1933 21 20 6.28 3.08 0.49 1826 5.86 2.87 0.49 1915 5.43 2.66 0.49 2023 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 18

    18 PERFORMANCE DA T A COOL operation a t Rated frequency MUZ-GF71VE CAP ACITY : 7.1 kW SHF: 0.78 INPUT : 2130 W INDOOR DB (°C) INDOOR WB (°C) OUTDOOR DB (°C) 21 25 27 30 Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 8.34 5.01 0.60 1704 7.99 4.79 0.60 1789 7.67 4.60 0.60 1874 7.38 4.43 0.60 1960 21 20 8.70 4.17 0.48 1789 8 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 19

    19 PERFORMANCE DA T A COOL operation a t Rated frequency MUZ-GF71VE CAP ACITY : 7.1 kW SHF: 0.78 INPUT : 2130 W INDOOR DB (°C) INDOOR WB (°C) OUTDOOR DB (°C) 35 40 46 Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 6.96 4.17 0.60 2087 6.39 3.83 0.60 2215 5.89 3.54 0.60 2300 21 20 7.31 3.51 0.48 2173 6.82 3.27 0.48 2279 6.32 3.03 0.48 2407 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 20

    20 PERFORMANCE DA T A HEA T operation at Rated frequency MUZ-GF60VE CAP ACITY : 6.8 kW INPUT : 1810 W INDOOR DB (°C) OUTDOOR WB (°C) -10 -5 0 5 10 15 20 Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 4.28 1 177 5.17 1412 6.05 1593 6.94 1720 7.82 1828 8.64 1882 9.52 1919 21 4.08 1267 4.90 1502 5.78 1665 6.60 1792 7.48 1882 8.30 1937 9. ...

  • Mitsubishi MSZ-GF60VE-E1 - page 21

    21 MUZ-GF60VE MUZ-GF71VE 9-2. R.V . COIL CONTROL Heating . . . . . . . . . . . . . . . . . ON Cooling . . . . . . . . . . . . . . . . . OFF Dry . . . . . . . . . . . . . . . . . . . . OFF NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor . ON OFF ON OFF Outdoor fan motor Compressor 5 seconds 15 seconds ON OFF Comp ...

  • Mitsubishi MSZ-GF60VE-E1 - page 22

    22 10-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature <JS> T o change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P .C. board. (Refer to 1 1-6-1.) Jumper wire Defrost fi nish temperature ( °C ) MUZ-GF 60VE 71VE JS Soldered (Initial setting) 10 10 None (Cut) 18 18 10-2. PRE-HEA T CONTROL SE ...

  • Mitsubishi MSZ-GF60VE-E1 - page 23

    23 Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (1 1-3.) disappears, the memorized failure details can be r ecalled. 1 1-2. F AILURE MODE RECALL FUNCTION 1. Flow chart of failure mode recall function for the indoor/outdo ...

  • Mitsubishi MSZ-GF60VE-E1 - page 24

    24 2. Flow chart of the detailed outdoor unit failure mode recall function 2.Blinking pattern when outdoor unit is abnormal: ON OFF No beep Beeps Repeated cycle 2.5-second OFF 3-second ON Blinking at 0.5- second interval No beep Beeps Repeated cycle 2.5-second OFF 3-second ON Blinking at 0.5- second interval Repeated cycle Does the upper lamp of OP ...

  • Mitsubishi MSZ-GF60VE-E1 - page 25

    25 3. Outdoor unit failure mode table The upper lamp of OPERA TION INDICA TOR lamp (Indoor unit) Abnormal point (Failure mode / protection) LED indication (Outdoor P .C. board) Condition Remedy Indoor/outdoor unit failure mode recall function Outdoor unit failure mode recall function OFF None (Normal) —— — — — 1-time fl ash 2.5 seconds O ...

  • Mitsubishi MSZ-GF60VE-E1 - page 26

    1 1-3. TROUBLESHOOTING CHECK T ABLE No. Symptom LED indication Abnormal point/ Condition Condition Remedy 1 Outdoor unit does not op- erate. 1-time fl ash every 2.5 seconds Outdoor power sys- tem Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started. Reconnect connector of compres- sor . Refe ...

  • Mitsubishi MSZ-GF60VE-E1 - page 27

    No. Symptom LED indication Abnormal point/ Condition Condition Remedy 19 Outdoor unit operates. 8-time fl ash 2.5 seconds OFF Zero cross detecting circuit Zero cross signal cannot be detected. It occurs with following cases. 1 Instantaneous power voltage drop. (Short time power failure) 2 Distortion of primary voltage Refer to 1 1-5. "Check o ...

  • Mitsubishi MSZ-GF60VE-E1 - page 28

    28 1 1-5. TROUBLESHOOTING FLOW Are the voltages balanced? Disconnect the connector between compressor and the IGBT module (IC700). Replace the inverter P .C. board. Check the voltage between terminals. Check the compressor . See 1 1-5. “Check of compressor”. No Ye s See 1 1-5. “Check of open phase”. A How to check inverter/compressor Refer ...

  • Mitsubishi MSZ-GF60VE-E1 - page 29

    29 F Check of compressor start failure D Check of compressor winding E Check of compressor operation time ● Disconnect the connector between the compressor and the IGBT module (IC700), and measure the resistance between the compressor terminals. <<Measurement point>> At 3 points BLK-WHT BLK-RED WHT -RED <<Judgement>> Refer ...

  • Mitsubishi MSZ-GF60VE-E1 - page 30

    30 G Check of outdoor thermistors H Check of R.V . coil Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P .C. board. Replace the inverter P .C. board. No No Is the resistance of thermistor normal? (Refer to 1 1-6.1.) Reconnect the connector of thermistor . T urn ON the power supply and press EMERGENCY OPERA TION swit ...

  • Mitsubishi MSZ-GF60VE-E1 - page 31

    31 I Check of outdoor fan motor Is the resistance between each ter- minal of outdoor fan motor normal? (Refer to 1 1-4.) Disconnect CN932 from the inverter P .C. board, and turn on the power supply . Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-) Does the vol ...

  • Mitsubishi MSZ-GF60VE-E1 - page 32

    32 J Check of power supply Is there voltage 230 V AC between the indoor terminal block S1 and S2? No Ye s Replace the indoor electronic control P .C. board. Rectify indoor/outdoor connecting wire. Ye s If light up, OK. If fl ash, refer to 1 1-3. Does the upper lamp of OPERA TION INDICA TOR on the indoor unit light up? Does LED on the inverter P .C ...

  • Mitsubishi MSZ-GF60VE-E1 - page 33

    33 Press OPERA TE/ST OP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1 Expansion valve operates in full-opening direction. OK NOTE : After check of LEV , do the undermentioned operations. 1. T urn OFF the power supply and turn it ON again. 2. Press RESET butto ...

  • Mitsubishi MSZ-GF60VE-E1 - page 34

    34 Check the outdoor fan motor . (Refer to 1 1-5. .) Is the fuse (F901) blown on the in- verter P .C. board? Check the connection of the connectors (CN931, CN932) of the outdoor fan motor . If the connection is poor , make it correct. Operate the outdoor unit by starting EMERGENCY OPERA TION. Check the LED indication on the inverter P .C. board. Do ...

  • Mitsubishi MSZ-GF60VE-E1 - page 35

    35 M How to check miswiring and serial signal error T urn the power supply OFF . Is there rated voltage in the power supply? Ye s No Check for incorrect indoor-outdoor connecting wiring. Check the power supply . A Is there rated voltage between outdoor terminal block S1 and S2? Check for miswiring, broken wires, and loose wire connection between th ...

  • Mitsubishi MSZ-GF60VE-E1 - page 36

    36 N Electromagnetic noise enters into TV sets or radios Ye s Is the unit earthed? No Earth the unit. Ye s Is the distance between the antennas and the indoor unit within 3 m, or is the distance between the antennas and the outdoor unit within 3 m? No Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor ...

  • Mitsubishi MSZ-GF60VE-E1 - page 37

    37 1. Inverter P .C. board 1 1-6. TEST POINT DIAGRAM AND VOL T AGE MUZ-GF60VE MUZ-GF71VE -20 -10 0 10 20 30 40 0 10 20 30 40 50 60 70 80 90 100 T emperature( ) Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68) T emperature( ) Discharge temperature thermistor(RT62) 0 1 02 03 04 05 06 07 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 38

    38 2. Relay P .C. board MUZ-GF60VE MUZ-GF71VE T o inverter P .C. board CN681 (CN680) CN60 L68B(-) L68A(+) 10 VDC OBH635 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 39

    39 12-1. MUZ-GF60VE MUZ-GF71VE NOTE: T urn OFF power supply before disassembly . OPERA TING PROCEDURE PHOTOS 1. Removing the cabinet (1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover . (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover . (7) Di ...

  • Mitsubishi MSZ-GF60VE-E1 - page 40

    OPERA TING PROCEDURE PHOTOS 2. Removing the inverter assembly , inverter P .C. board and relay P .C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con- nectors: <Inverter P .C. board> CN602 (R.V . coil) CN931, CN932 (Fan motor) CN671 (Defrost thermistor , discharge tempera ...

  • Mitsubishi MSZ-GF60VE-E1 - page 41

    OPERA TING PROCEDURE PHOTOS 4. Removing the discharge temperature thermistor , defrost thermistor , outdoor heat exchanger tempera- ture thermistor and ambient temperature thermistor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P .C. board> CN671 (Defrost ...

  • Mitsubishi MSZ-GF60VE-E1 - page 42

    © Copyright 2013 MITSUBISHI ELECTRIC CORPORA TION Distributed in Mar . 2013. No. OBH635 Made in Japan New publication, effective Mar . 2013 Specifications are subject to change without notice. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAP AN ...

メーカー Mitsubishi カテゴリー Air-conditioning

Mitsubishi MSZ-GF60VE-E1のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- MSZ-GF60VE-E1の取扱説明書
- Mitsubishiの製品カード
- パンフレット
- またはMitsubishi MSZ-GF60VE-E1の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Mitsubishi MSZ-GF60VE-E1の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Mitsubishi MSZ-GF60VE-E1の取り付け説明書、サービスマニュアル、簡易説明書、またはMitsubishi MSZ-GF60VE-E1のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Mitsubishi MSZ-GF60VE-E1の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Mitsubishi MSZ-GF60VE-E1デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがMitsubishi MSZ-GF60VE-E1を使用するのを助ける技術的文書のことです。説明書は通常、全てのMitsubishi MSZ-GF60VE-E1ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Mitsubishiの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Mitsubishi MSZ-GF60VE-E1の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははMitsubishi MSZ-GF60VE-E1の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Mitsubishi MSZ-GF60VE-E1に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Mitsubishi MSZ-GF60VE-E1デバイスの基本機能を使うにあたってのヒント。 Mitsubishi MSZ-GF60VE-E1のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Mitsubishi MSZ-GF60VE-E1に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるMitsubishi MSZ-GF60VE-E1のメーカー/サービスへの連絡先に関する情報。

Mitsubishi MSZ-GF60VE-E1についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもMitsubishi MSZ-GF60VE-E1の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがMitsubishi MSZ-GF60VE-E1で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)