    SAFETY CONSIDERA TIONS Due t o sys tem pr essu re, moving par ts and electrical com ponent s, inst allati on an d ser vicing of air conditioning equipm ent can be haza rdous . Only quali fied, trai ned, s ervice personnel should install, repair , maintain or service this equipm ent. Obser ve all pr ecau tion s in the lite ratu re, on la bels and t ...

  • York B1CH240 - page 2

    Gene ral ... ...... ...... .... ...... ...... ...... .... ...... ...... .... ...... ...... .... ...... . 1 Inspe ction ...... .... ...... ...... .... ...... ...... .... ...... ...... ...... .... ...... ...... . 1 Referen ce ... ...... .... .... .... ...... .... .... .... ...... .... .... .... ...... .... .... .... .. 1 App rovals ..... .... .... .. ...

  • York B1CH240 - page 3

    LIMIT A TIONS These unit s must be inst alle d in ac corda nce w ith the followin g natio nal and lo cal sa f ety co de s: In U .S.A. : 1. National Electrica l Code ANSI/ NFP A No . 70. 2. Lo cal elec tr ic ut ility r equi rem en ts. In Ca nada: 1. C ur re nt Cana dian Elec tri cal C ode C S A C22. 1. 2. Lo cal elec tr ica l code s. Refer to the Un ...

  • York B1CH240 - page 4

    FIXED OUTDOOR AIR INT AKE D AMPER This d ampe r is ship ped ins ide t he r etur n air co mpar tm ent. It is completely assembled and ready for installation. A damper baffle ins ide t he hood is adju stab le t o pro vide v ariable amounts of outdoor air intake on units that are not provided with an economizer or a motorized damper option. Gask etin ...

  • York B1CH240 - page 5

    The i nter n al w ir ing h ar n ess fur nishe d wi th this unit is an inte gral par t of a ET L a nd CG A de si gn ce rtified u ni t. Field a lt er atio n to com ply wit h elec tri cal co des sh ould not be req uired . A fus ed di scon nect switch sh ould be fi eld p rovided for the unit . The switch must b e se parat e fro m all ot her c irc uits. ...

  • York B1CH240 - page 6

    Ref er to the T ypical Field Wiring Fi gure and to the a ppropriate unit wiring diagr am f or control circui t and p ow er w iring inf or matio n. OPTIONAL ELECTRIC HE A TERS The f actory install ed heat ers are w ired f or s ingle point pow er supply . P ow er suppl y need only be brough t into th e singl e point terminal b loc k and thermostat wi ...

  • York B1CH240 - page 7

    FIG. 6 - ENTHAL PY SET POI NT ADJU STME NT 511.06-N3Y Unitar y Products Group 7 ...

  • York B1CH240 - page 8

    T ABLE 4 - PHYSIC AL D A T A MODELS UNIT SIZE 15 T ON 20 TO N SUPPL Y AIR BLOWER CENT RIFUGAL B LO WER (Dia. x Wd. in.) 15 x 15 18 x 15 F AN MOT OR HP 5 7.5 INDOOR COIL RO WS DEEP 4 4 FINS PER INCH 13 13 F ACE ARE A (Sq. Ft.) 15.5 20.5 OUTD OOR FA N S (T wo P er Unit) PR OP ELLE R DIA. (in.) (Each) 30 30 F AN MO T OR HP ( Eac h) 1 1 NOM. CFM T O T ...

  • York B1CH240 - page 9

    DUCT CO VERS - Units are shi pped with the bottom duct openings covered. An accessory flange kit is a v ail- able f or connecti ng side ducts. For bottom duct appl ications: 1. Remov e the side panels from the supply and return ai r compar tm ents to gain access to the bot tom suppl y and retur n air duct covers . 2. Remove and discard the bottom d ...

  • York B1CH240 - page 10

    A B C D FRONT 4 POINT LO ADS FIG. 8 - FOUR AND SIX POINT LO A DS A E D B F C FRONT 6 POINT LO ADS UNIT 4 - POINT LOADS (LBS) TOT A L A B C D 180 2,190 513 535 583 559 240 2,390 514 538 684 654 NO TE: These we ig ht s a r e wi th econom iz er and 36kW el ec tric h ea t. UNIT 6 - PO INT LOADS (LBS) TOT A L A B C D E F 180 2,190 342 358 373 388 372 35 ...

  • York B1CH240 - page 11

    T ABLE 6 - SUPPL Y AI R BL O WER PER FO R MAN CE (1 5 T ON) 180 MBH - BO TT OM DUCT CONNECTIONS BLOWER SPEED , (RPM) MO T OR PULLEY (TURNS OPEN)* CFM 4500 5250 6000 6750 7200 ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW 208 V OL T AND ST AND ARD DRIVE 850 6.0** 0.9 2.4 2.2 0.7 3.0 2. 7 0.5 3.2 2.9 - - - - - - 870 5.5 1.0 2.5 2.3 0.8 3.1 2 ...

  • York B1CH240 - page 12

    T ABLE 7 - SUPP L Y AIR BLOWER PERFORMANCE (20 T ON) BLOWER SPEED , (RPM) MO TO R PULLEY (TURNS OPEN)* CFM 6000 7000 8000 9000 9400 ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW 208 V OL T AND ST AND ARD DRIVE 8 7 0 6 . 0 * * 0 . 4 2 . 1 1 . 8 0 . 1 2 . 3 2 . 0 --------- 9 0 0 5 . 0 0 . 8 3 . 2 2 . 7 0 . 5 3 . 5 2 . 9 0 . 2 3 . 8 3 . 2 --- ...

  • York B1CH240 - page 13

    T ABLE 8 - ST A TIC RESIST ANCES 1 T ABLE 9 - PO WER EXHA US T PERFORMANCE MO TO R SPEED ST A TIC RESI ST ANCE OF RETURN DUCTWORK, IWG 0.2 0.3 0.4 0.5 0.6 CFM KW CFM KW CFM KW CF M KW CFM KW HIGH* 5250 0.83 4500 0.85 4200 0. 88 3750 0.93 3000 0.99 MEDIUM 4900 0.77 3900 0.79 3500 0.82 2900 0.85 - - LOW 4400 0. 72 3700 0.74 3000 0.78 - - - - * F a ct ...

  • York B1CH240 - page 14

    MODEL POWER SUPPL Y COMPRESSORS OUTDOOR F AN MO TO RS (#1 & #2) SUPPL Y AIR BLOWER MO TO R MINIM UM CIRCUIT AMP A CITY (AMPS) MAXIMUM TIME DEL A Y FUSE SI ZE (AMPS) #1 #2 RLA LRA RLA LRA HP EA CH FLA EA CH HP FLA B1CH180 208/230-3-60 28.2 260 28. 2 260 1 4.1/4.2 5 14.4/15.4 86.1/87.3 110 460-3-60 14. 1 128 14.1 128 1 2.1 5 7.2 43.1 50 575-3-60 ...

  • York B1CH240 - page 15

    COOL ING SY STEM The un it ha s an air -c ooled cooling section and is f act or y- c har ged wit h Refr ig er ant- 2 2. The co mpres sor s are h er met ical ly se aled , inter n ally spr ung and b as e-mou nted with r ubbe r-in sula ted hold -down bolts. Compress ors ha v e inhere nt (inte rnal) protecti on. If t here is an abnormal tem pera ture r ...

  • York B1CH240 - page 16

    HEA T ANTICIP A T OR SETPOINTS It is im po rtant tha t t he an ti ci pa tor se tp oi nt be co rrect. T oo high of a set ting wi ll result in longe r heat cycles and a greate r temper ature sw ing in th e cond itione d space . Reducing t he value be low the corr ect setpoi nt will gi v e shor te r “ON ” cyc les and ma y result in the l oweri ng ...

  • York B1CH240 - page 17

    DEFROST SEQUENCE OF OPERA TION These heat pumps hav e a unique “ambient modified” time-temperature d ef r os t c on t ro l t ha t a u t om at i c al l y ad j us t s t o change s in t he outd oor temp erat ure. The def rost control will shorten the de frost in itia tion ti me perio ds abo v e 35 ° F and will extend the defrost init iation time ...

  • York B1CH240 - page 18

    NORMAL MAINTENANCE CA UTION: P rior to any of th e f o llowing ma intenanc e proce- dures , shut off all el ectric po wer t o the un it to pre v ent pe rso na l in ju r y . FIL T ERS - In spec t on ce a mo nth. Repla ce di spos able or cl ean permanent ty pe as n ecessary . DO NO T replace permanent type wi th di spos able. The dim ensi onal size o ...

  • York B1CH240 - page 19

    511.06-N3Y Unitar y Products Group 19 ...

  • York B1CH240 - page 20

    Code: SBY 51 1.06 -N3Y 5005 Y or k Dr ive, Nor man , OK 7306 9 Subje ct to ch ange wit hout n otice. Prin ted in U.S .A Cop yright  by Y ork International Corporation 200 0. All Rights Reserved. ...

メーカー York カテゴリー Heat Pump

York B1CH240のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- B1CH240の取扱説明書
- Yorkの製品カード
- パンフレット
- またはYork B1CH240の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、York B1CH240の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、York B1CH240の取り付け説明書、サービスマニュアル、簡易説明書、またはYork B1CH240のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、York B1CH240の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

York B1CH240デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがYork B1CH240を使用するのを助ける技術的文書のことです。説明書は通常、全てのYork B1CH240ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Yorkの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. York B1CH240の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははYork B1CH240の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。York B1CH240に関してこのドキュメントで見つけることができる全てのヒントの目次
3. York B1CH240デバイスの基本機能を使うにあたってのヒント。 York B1CH240のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。York B1CH240に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるYork B1CH240のメーカー/サービスへの連絡先に関する情報。

York B1CH240についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもYork B1CH240の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがYork B1CH240で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)