Trane RTHDの取扱説明書

32ページ 2.31 mb
ダウンロード

ページに移動 of 32

Summary
  • Trane RTHD - page 1

    Ser ies R ™ Helical Rotary Liquid Chillers Model RTHD 1 75-450 T ons (60 Hz) 125-450 T ons (50 Hz) Built f or Industr ial and Commer cial Applications RLC-PRC020-EN June 2006 ...

  • Trane RTHD - page 2

    RLC-PRC020-EN © 2004 American Standard Inc. All rights reserved. Intr oduction T o meet a wide range of applications in the medium-tonnage, water -cooled market, T rane is proud to introduce the model R THD helical rotary liquid c hiller . The introduction of this next-generation c hiller an exciting step forward in application versatility, ease o ...

  • Trane RTHD - page 3

    3 RLC-PRC020-EN Contents Intr oduction F eatur es and Benefits Options Contr ols Application Considerations Selection Pr ocedur e Model Nomenclat ur e Gener al Data Electr ical D ata and Connections Dimensions and W eights Mechanical Specifications Con version T able 2 4 6 8 10 12 14 16 19 22 29 30 ...

  • Trane RTHD - page 4

    RLC-PRC020-EN 4 F eatures and Benef its Applications in this catalog specifically excluded from the ARI certification program are: • Low temperature applications, including ice storage • Glycol • 50Hz units below 200 nominal tons Application V ersatility and High Performance • Screw compressor tec hnology and the electronic expansion valve ...

  • Trane RTHD - page 5

    5 RLC-PRC020-EN F eatures and Benef its State-of-the-Art, Precision Control • Microprocessor -based CH530 controls monitor and maintain optimal operation of the c hiller and its associated sensor s, actuator s, relays, and switc hes, all of whic h are factory-assembled and extensively tested. • Easy interface with computers hosting T racer Summ ...

  • Trane RTHD - page 6

    RLC-PRC020-EN 6 Options Insulation All low temperature surfaces are covered with factory installed 3/4 inc h (1 9.05 mm) Armaflex II or equal (k=0.28) insulation, including the evaporator and water boxes, suction line, and motor housing. 3/8" foam insulation is used on the liquid level sensor and gas pump assembly , including piping. Low -T em ...

  • Trane RTHD - page 7

    7 RLC-PRC020-EN Control Options: T racer Summit Communications Link to factory-installed, tested communication board, via single twisted- pair wiring, adds T racer Summit communications to the system. LonT alk LCI-C Interf ace LonT alk (LCI-C) communications capabilities are available, with communication link via single twisted-pair wiring to facto ...

  • Trane RTHD - page 8

    RLC-PRC020-EN 8 LCD T ouc h-Screen Displa y with Multi-Language Support The standard DynaView display provided with the CH530 control panel features an LCD touc h-screen, allowing access to all operational inputs and outputs. This display supports eleven languages: English, Chinese, Dutc h, Frenc h, German, Italian, Japanese, Korean, Portugese, Spa ...

  • Trane RTHD - page 9

    9 RLC-PRC020-EN Contr ols T rane Chiller Plant A utomation T rane’ s depth of experience in c hillers and controls makes us a well-qualified choice for automation of c hiller plants using air - cooled S eries R ® c hiller s ® . The chiller plant control capabilities of the T rane T racer Summit ® building automation system are unequaled in the ...

  • Trane RTHD - page 10

    RLC-PRC020-EN 10 Condenser W ater T emperatur es Reduced sensitivity to condenser water startup temperatures is one major enhancement in the newest-generation water -cooled Series R c hiller . With the model RTHD c hiller , a condenser water control method is necessary only if the unit starts with entering water temperatures below 55°F (12.8°C), ...

  • Trane RTHD - page 11

    11 RLC-PRC020-EN Ser ies Chiller Ar rangements Another energy-saving strategy is to design the system around c hillers ar ranged in series, on the evaporator , condenser , or both. The actual savings possible with suc h strategies depends on the application dynamics and should be researc hed by consulting your T rane Systems Solutions Representativ ...

  • Trane RTHD - page 12

    RLC-PRC020-EN 12 S election P r ocedure T rane Series R c hiller performance is rated in accordance with the ARI Standard 550/590-2003 Certification Program. Chiller selection assistance and performance information can be obtained by using the Series R c hiller selection program, available through local T rane sales offices. Performance The compute ...

  • Trane RTHD - page 13

    13 RLC-PRC020-EN Electr ical Data T ables Compressor motor electrical data is provided in the data section for eac h compressor size. Rated load amperes (RLA), loc k ed rotor wye amperes (LRA) and expected inrush for the Wye-delta and Solid State Starter configurations are shown. Although the terms “LRA ” and “ expected inrush” are of ten u ...

  • Trane RTHD - page 14

    RLC-PRC020-EN 14 Model Nomenclature RTH D U D 2 F 0 A0 U A G 3 A 4 L A L G 3 F 2 L A L 1 , 2 , 3 4 5 6 7 8 9 1 0 , 1 1 1 21 3 1 41 5 1 6 1 7 1 81 9 2 02 1 2 22 32 4 2 52 6 2 7 Digits 0 1, 02, 03 – Ser ies R ™ RTH = Series R Digit 04 – Dev Sequence D = 4th Major Development Digit 05 – Design Control U = WCBU Digit 06 – Compressor Frame B = ...

  • Trane RTHD - page 15

    15 RLC-PRC020-EN Model Nomenclature A V X Q X E X A A B D Y 444 D A X A 4 X X X R X V X 2 8 2 9 3 0 3 1 3 2 33 3 4 3 5 3 6 37 3 8 3 9 40,41,42 4 3 4 4 4 5 4 6 4 7 4 8 4 9 5 0 51 5 2 5 3 5 4 Digit 28 – Condenser Leaving Water T emperature A = Standard Digit 29 – Refrigerant Specialties X = No Refrigerant Isolation V alves V = With Refrigerant Is ...

  • Trane RTHD - page 16

    RLC-PRC020-EN 16 Nominal Data Nominal Compressor B1 B2 C1 C2 D 1 D 2 D 3 E 3 T onnage (60 Hz) 175-200 200-225 225-275 275-325 325-400 375-450 N/ A N/A T onnage (50 Hz) 125-150 150-175 175-225 225-275 275-325 300-350 325-375 375-450 Notes: 1 . Chiller selections can be optimized through the use of the ARI-Certified Series R selection program and by ...

  • Trane RTHD - page 17

    17 RLC-PRC020-EN General Data Minimum/Maximum Evaporator Flow Rates (Gallons/Minute ) T wo P a s s Three Pass Four Pass Evaporator Nominal Nominal Nominal Code Min Ma x Conn Size (In.) M i n M a x Conn Size (In.) M i n M a x Conn Size (In.) B 1 253 1 10 4 8 168 736 6 —- — - — - B2 28 8 1266 8 1 92 84 4 6 —- —- —- C1 32 0 1412 8 21 3 94 ...

  • Trane RTHD - page 18

    RLC-PRC020-EN 18 Minimum/Maximum Evaporator Flow Rates (GPM) T wo P a s s Three Pass Four Pass Evaporator Nominal Nominal Nominal Code Min Max Conn Size (In.) M i n M a x Conn Size (In.) M i n M a x Conn Size (In.) B 1 303 1 10 4 8 200 736 6 —- — - — - B2 34 6 1266 8 2 33 84 4 6 —- —- —- C1 34 6 1412 8 2 54 94 1 6 —- —- —- C2 37 5 ...

  • Trane RTHD - page 19

    19 RLC-PRC020-EN Electrical Data and Connections Compressor Motor Electrical Data (60 Hertz) Nominal V oltage 20 0 2 30 3 80 4 60 57 5 Compressor V oltage 18 0/ 208/ 342/ 414/ 516/ Code Utilization Range 2 20 2 54 4 1 8 50 6 63 3 Max kW 1 74 1 74 1 7 4 1 7 4 17 4 B1, B2 RLA @ Max kW 5 57 4 84 2 91 2 41 1 93 LRA Y 970 818 488 400 329 LRAD 3103 2617 ...

  • Trane RTHD - page 20

    RLC-PRC020-EN 20 Electrical Data and Connections ...

  • Trane RTHD - page 21

    21 RLC-PRC020-EN Electrical Data and Connections ...

  • Trane RTHD - page 22

    RLC-PRC020-EN 22 Shipping and Operating W eights Compressor Evaporato r Condenser Operating W eight Shipping W eight Code Code Code ( l b s ) (kg) (lbs) (kg) B1 B1 B1 9,867 4,476 9,292 4,215 B1 C1 D 1 10,554 4,787 9,837 4,462 B2 B2 B2 1 0 ,0 19 4,545 9,402 4,265 B2 C2 D 2 10,653 4,832 9,953 4,515 C1 D 6 E 5 13,397 6,077 12,780 5,797 C1 D 5 E 4 13,6 ...

  • Trane RTHD - page 23

    23 RLC-PRC020-EN Dimensions and W eights BBB Configuration Recommended Clearances Front 36" (914 mm) Back 36" (914 mm) Either End 36" (914 mm) Other End* 108" (2743 mm) T o p 36" (914 mm) * Clearance for tube removal Note: 1 . Dimensions are based on 3 Pass Evap / 2 P ass Cond and LH/LH water connections. Refer to submittal ...

  • Trane RTHD - page 24

    RLC-PRC020-EN 24 Dimensions and W eights BCD Configuration Recommended Clearances Front 36" (914 mm) Back 36" (914 mm) Either End 36" (914 mm) Other End* 126" (3200 mm) T o p 36" (914 mm) * Clearance for tube removal Note: 1 . Dimensions are based on 3 Pass Evap / 2 Pass Cond and LH/LH water connections. Refer to submittals ...

  • Trane RTHD - page 25

    25 RLC-PRC020-EN Dimensions and W eights CDE, DDE, EDE Configuration Recommended Clearances Front 36" (914 mm) Back 36" (914 mm) Either End 36" (914 mm) Other End* 108" (2743 mm) T o p 36" (914 mm) * Clearance for tube removal Note: 1 . Dimensions are based on 3 Pass Evap / 2 P ass Cond and LH/LH water connections. Refer to ...

  • Trane RTHD - page 26

    RLC-PRC020-EN 26 Dimensions and W eights CEF Configuration Recommended Clearances Front 36" (914 mm) Back 36" (914 mm) Either End 36" (914 mm) Other End* 126" (3200 mm) T o p 36" (914 mm) * Clearance for tube removal Note: 1 . Dimensions are based on 3 Pass Evap / 2 Pass Cond and LH/LH water connections. Refer to submittals ...

  • Trane RTHD - page 27

    27 RLC-PRC020-EN Dimensions and W eights CFF , DFF , EFF Configur ation Recommended Clearances Front 36" (914 mm) Back 36" (914 mm) Either End 36" (914 mm) Other End* 126" (3200 mm) T o p 36" (914 mm) * Clearance for tube removal Note: 1 . Dimensions are based on 3 Pass Evap / 2 P ass Cond and LH/LH water connections. Refer ...

  • Trane RTHD - page 28

    RLC-PRC020-EN 28 Dimensions and W eights DGG, EGG Configuration Recommended Clearances Front 36" (914 mm) Back 36" (914 mm) Either End 36" (914 mm) Other End* 126" (3200 mm) T o p 36" (914 mm) * Clearance for tube removal Note: 1 . Dimensions are based on 3 Pass Evap / 2 Pass Cond and LH/LH water connections. Refer to submi ...

  • Trane RTHD - page 29

    29 RLC-PRC020-EN Mec hanical Specif ications General Exposed metal surfaces are painted with air -dry beige, direct-to-metal, single- component paint. Eac h unit ships with full operating c harges of refrigerant and oil. Molded neoprene isolation pads are supplied for placement under all support points. Startup and operator instruction by factory-t ...

  • Trane RTHD - page 30

    RLC-PRC020-EN 30 Con v er sion T able ...

  • Trane RTHD - page 31

    31 RLC-PRC020-EN ...

  • Trane RTHD - page 32

    T rane has a policy of continuous product and product data impro vement and reserves the right to change design and specifications without notice. Literature Order Number File Number Supersedes Stocking Location T rane A business of American Standar d Companies www .tr ane.com For more information, contact your local sales office or e-mail us at co ...

メーカー Trane カテゴリー Beverage Dispenser

Trane RTHDのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- RTHDの取扱説明書
- Traneの製品カード
- パンフレット
- またはTrane RTHDの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Trane RTHDの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Trane RTHDの取り付け説明書、サービスマニュアル、簡易説明書、またはTrane RTHDのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Trane RTHDの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Trane RTHDデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがTrane RTHDを使用するのを助ける技術的文書のことです。説明書は通常、全てのTrane RTHDユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Traneの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Trane RTHDの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははTrane RTHDの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Trane RTHDに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Trane RTHDデバイスの基本機能を使うにあたってのヒント。 Trane RTHDのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Trane RTHDに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるTrane RTHDのメーカー/サービスへの連絡先に関する情報。

Trane RTHDについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもTrane RTHDの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがTrane RTHDで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)