Summary
  • York CHAMPION D2EB - page 1

    GENERAL Model D2EB units are factory assembled cooling only air condi- tioners designed for outdoor installation on a rooftop or a slab. Field-installed electric heater accessories are available to provide electric heat combined with electric cooling. All units and heaters are certified by CSA. The units are completely assembled on rigid, but easil ...

  • York CHAMPION D2EB - page 2

    LIMIT ATIONS These units must be installed in accordance with the following national and local safety codes. 1. National Electrical Code ANSI/NFPS No. 70 or Canadian Electrical Code Part 1, C22.1 (latest editions). 2. Local plumbing and waste water codes and other applica - ble local codes. Refer to T able 1 for unit application data and to T able ...

  • York CHAMPION D2EB - page 3

    CLEARANCES All units require certain clearances for proper operation and service. Refer to Figure 3 for the clearances required for com - bustion, construction, servicing and proper unit operation. WARNING: Do not permit overhanging structures or shrubs to obstruct the condenser air discharge outlet. DUCT WORK These units are adaptable to downflow ...

  • York CHAMPION D2EB - page 4

    POWER AND CONTROL WIRING Field wiring to the unit must conform to provisions of the current N.E.C. ANSI/NFP A No. 70 or C.E.C. and/or local ordinances. The unit must be electrically grounded in accordance with local codes or , in their absence, with the N.E.C./C.E.C. V oltage toler - ances which must be maintained at the compressor terminals during ...

  • York CHAMPION D2EB - page 5

    174065-YIM-A-0206 Unitary Products Group 5 MODEL DEB POWER SUP - PL Y VOL TAGE LIMIT ATIONS 1 COMPRESSOR COND. FA N MOTOR, FLA SUPPL Y AIR BLOWER MOTOR, FLA MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, AMPS 2 MAX. HACR BREAKER SIZE, AMPS UNIT POWER F ACTOR TRANSFORMER SIZE (V A) MIN. MAX. RLA LRA 018 208/230-1-60 187 253 9.0 48.0 1.1 2.6 14.9 20 20 .9 ...

  • York CHAMPION D2EB - page 6

    174065-YIM-A-0206 6 Unitary Products Group DEB POWER SUPPL Y COMPRESSOR COND. FA N MOTOR FLA SUPPL Y AIR BLOWER MOTOR, FLA ELECTRIC HEA T ACCESSORY MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, 1 AMPS MAX. HACR 2 BREAKER SIZE MODEL RLA LRA MODEL NO. ST AGE KW TOT AL AMPS 018 208/230-1-60 9.0 48.0 1.1 2.6 2NH04500506 2NH04500706 1 2 3.8/5.0 * 5.6/7.5 * ...

  • York CHAMPION D2EB - page 7

    Checking Supply Air CFM T o check the supply air CFM after the initial balancing has been completed: 1.Remove the two ¼ inch dot plugs in the duct panel. 2.Insert at least 8 inches of ¼ inch tubing into each of these holes for sufficient penetration into the airflow on both sides of the indoor coil. 3.Using an inclined manometer , determine the p ...

  • York CHAMPION D2EB - page 8

    8 Unitary Products Group 174065-YIM-A-0206 T ABLE 7 - SUPERHEA T CHARGING T ABLE FOR MODEL D2EB024 OUTDOOR TEMPERATURE (F) SUPERHEA T A T COMPRESSOR SUCTION (F), AIRFLOW = 800 CFM/TON INDOOR WB TEMPERATURE (F) 55 57 59 61 63 65 67 69 71 73 75 65 13.5 15.0 16.5 18.0 19.6 21.1 22.6 23.9 25.3 26.6 27.9 70 10.1 1 1.8 13.5 15.2 16.9 18.6 20.3 21.9 23.4 ...

  • York CHAMPION D2EB - page 9

    Unitary Products Group 9 174065-YIM-A-0206 T ABLE 10 - SUPERHEA T CHARGING T ABLE FOR MODEL D2EB042 OUTDOOR TEMPERATURE (F) SUPERHEA T A T COMPRESSOR SUCTION (F), AIRFLOW = 1,400 CFM/TON INDOOR WB TEMPERATURE (F) 55 57 59 61 63 65 67 69 71 73 75 65 20.3 21.9 23.5 25.0 26.6 28.1 29.7 30.6 31.6 32.6 33.6 70 16.7 18.5 20.3 22.1 23.9 25.7 27.5 28.6 29. ...

  • York CHAMPION D2EB - page 10

    10 Unitary Products Group 174065-YIM-A-0206 FIG . 3 - DIMENSIONS AND CLEARANCES CLEARANCES (Minimum) Front 12" Back 0" Left Side (Filter Access) 24" Right Side 24" Below Unit 1 0" Above Unit 2 36" (For Condenser Air Discharge) Units may be installed on combustible floors made from wood or class A, B or C roof covering ...

  • York CHAMPION D2EB - page 11

    Cooling The following sequences of operation are based on using a standard single-stage cooling thermost at. WITH POWER TO UNIT AND THERMOST A T IN COOLING MODE. 1. If the fan switch on the thermostat is in the “ON” position, the 24 volts at “G” will energize the “K1" relay on the fan control board, close the ”K1" relay contac ...

  • York CHAMPION D2EB - page 12

    12 Unitary Products Group 174065-YIM-A-0206 NORMAL MAINTENANCE WARNING: Prior to any of the following maintenance proce - dures, shut off all power to the unit, to avoid per - sonal injury . Periodic maintenance consists of changing or cleaning filters and general cleaning of the outdoor coil. FILTERS - Inspect once a month. Replace Disposable or c ...

  • York CHAMPION D2EB - page 13

    Unitary Products Group 13 174065-YIM-A-0206 FIG . 4 - TYPICAL WIRING DIAGRAM (208/230-1-60 POWER SUPPL Y) POWER SUPPLY 208/230-1-60 USE COPPER CONDUCTORS ONLY SECONDARY POWER SUPPLY FOR DUAL POINT ELEC HEAT 208/230-1-60 USE COPPER CONDUCTORS ONLY (HTR5) (HTR4) (HTR3) (HTR2) (M1) 705/PR 708/PR 716/PR 713/PR 710/PR F6 F4 F2 (K6) (K4) (K5) (K3) (M1) 7 ...

  • York CHAMPION D2EB - page 14

    14 Unitary Products Group 174065-YIM-A-0206 TYPICAL WIRING DIAGRAM NOTES TYPICAL WIRING DIAGRAM LEGEND CB CCH COMPR DS F1 F2 F3 F4 F5 F6 F7 F8 F9 F24 FS HP HTR 1 HTR 2 HTR 3 HTR 4 HTR 5 HTR 6 K1 K2 K3 K7 LP LS M1 M2 M3 PTCR RC1/RC2 RC1 RC2 RC3 RV S S2/P2 S3/P3 S4/P4 S3/P3 T1 TB2 CIRCUIT BREAKER 24V , 3 AMP CRANKCASE HEA TER (OPTIONAL) COMPRESSOR DE ...

  • York CHAMPION D2EB - page 15

    Unitary Products Group 15 174065-YIM-A-0206 NOTES ...

  • York CHAMPION D2EB - page 16

    NOTES Unitary Products Group 5005 York Drive, Norman Oklahoma 73069 Subject to change without notice. Printed in U.S.A. Copyright © by York International Corporation 2006. All Rights Reserved. Supersedes: Nothing 174065-YIM-A-0206 ...

メーカー York カテゴリー Air Conditioner

York CHAMPION D2EBのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- CHAMPION D2EBの取扱説明書
- Yorkの製品カード
- パンフレット
- またはYork CHAMPION D2EBの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、York CHAMPION D2EBの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、York CHAMPION D2EBの取り付け説明書、サービスマニュアル、簡易説明書、またはYork CHAMPION D2EBのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、York CHAMPION D2EBの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

York CHAMPION D2EBデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがYork CHAMPION D2EBを使用するのを助ける技術的文書のことです。説明書は通常、全てのYork CHAMPION D2EBユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Yorkの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. York CHAMPION D2EBの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははYork CHAMPION D2EBの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。York CHAMPION D2EBに関してこのドキュメントで見つけることができる全てのヒントの目次
3. York CHAMPION D2EBデバイスの基本機能を使うにあたってのヒント。 York CHAMPION D2EBのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。York CHAMPION D2EBに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるYork CHAMPION D2EBのメーカー/サービスへの連絡先に関する情報。

York CHAMPION D2EBについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもYork CHAMPION D2EBの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがYork CHAMPION D2EBで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)