Summary
  • Friedrich SH20J30B-A - page 1

    AMERICA’S BEST AIR CONDITIONER 2002 HAZARDGARD ® ROOM AIR CONDITIONER Service & Parts Manual Models SH14J30B-A SH20J30B-A HG2002 (02/02) ...

  • Friedrich SH20J30B-A - page 2

    2 T ABLE OF CONTENTS Specifications ................................................................................................................. ... 3 Performance Data ............................................................................................................. 3 Component Operation & T esting .............................. ...

  • Friedrich SH20J30B-A - page 3

    3 * Rating Conditions: 80 ° F . Room Air T emperature and 59% Relative Humidity with 95 ° F . Outside Air T emperature at 40% Relative Humidity . PERFORMANCE EV APORA T OR AIR OPERA TING ELECTRICAL R-22 COMP . DA T A * TEMP° F PRESSURES RATINGS REFRIG. OIL DISCHARGE TEMP SUCTION DISCHARGE AMPS LOCKED CHARGE IN CHARGE IN AIR DROP °F ROTOR AMPS O ...

  • Friedrich SH20J30B-A - page 4

    4 COMPRESSOR WINDING TEST (See Figure 2.) Remove the compressor terminal box cover and disconnect the wires from the terminals. Using an ohmmeter , check continuity across the following: DISCONNECT ELECTRICAL POWER T O THE UNIT BEFORE SER VICING OR TESTING COMPONENT OPERA TION AND TESTING W ARNING COMPRESSORS Compressors are single phase, 208/230 v ...

  • Friedrich SH20J30B-A - page 5

    5 F AN MOTOR (Figure 4) A 230 volt single phase permanent split capacitor motor is used to drive the evaporator blower and condenser fan. A running capacitor is wired across the start and run terminals of the motor . The motor is totally enclosed and is protected with a line voltage overload located internally of the motor . The motor shaft is stai ...

  • Friedrich SH20J30B-A - page 6

    6 RED DOT RUN CAP ACIT OR FA N MOT OR COMPRESSOR FIGURE 6 RUN CAP ACITOR HOOK–UP CAP ACIT OR, RUN A run capacitor is wired across the auxiliary and main winding of a single phase permanent split capacitor motor such as the compressor and fan motors. A single capacitor can be used for each motor or a dual rated capacitor can be used for both. The ...

  • Friedrich SH20J30B-A - page 7

    7 Note: The temperature must be within the range listed to check the thermostat. Refer to the troubleshooting section in this manual for additional information on thermostat testing. TEST Remove the wires from the thermostat. T urn the thermostat to its coldest position. Check to see if there is continuity between the two terminals. T urn the therm ...

  • Friedrich SH20J30B-A - page 8

    8 LOW AMBIENT BY–P ASS V AL VE The HazardGard unit is designed to operate at low outside ambient temperatures. This is accomplished by the use of a bypass valve installed in the refrigeration circuit. The valve is connected between the discharge line at the compressor and the suction process tube. The valve responds to suction pressure which, whe ...

  • Friedrich SH20J30B-A - page 9

    9 10 . Evacuate the system to an absolute holding pressure of 200 microns or less. NOTE: This procedure can be speeded up by the use of heat lamps, or by breaking the vacuum with refrigerant or dry nitrogen at 5,000 microns. Pressure system to 5 PSIG and leave in the system a minimum of 10 minutes. Recover refrigerant, and proceed with evacuation t ...

  • Friedrich SH20J30B-A - page 10

    10 NOTE: All inoperative compressors returned to Friedrich must have all lines properly plugged with the plugs from the replacement compressor . REFRIGERANT CHARGE 1. The refrigerant charge is extremely critical. Measure the charge carefully and as exactly as possible to the nameplate charge. 2. The correct method for charging the rotary is to intr ...

  • Friedrich SH20J30B-A - page 11

    11 PROBLEM POSSIBLE CAUSE TO CORRECT Unit does not run. PROBLEM POSSIBLE CAUSE TO CORRECT Dirty Filter . Restricted air flow . Inoperative thermostat. Short of refrigerant. Partially restricted capillary . Inoperative fan motor . Evaporator coil freezes up. PROBLEM POSSIBLE CAUSE TO CORRECT T est cooling performance of unit. Unit undersized. Check ...

  • Friedrich SH20J30B-A - page 12

    12 PROBLEM POSSIBLE CAUSE T O CORRECT Compressor attempts to start, or runs for short periods only . Cycles on overload. Allow a minimum of two (2) minutes to allow pressures to equalize before attempting to start. Check voltage with unit operating. Check for other appliances on the circuit. Unit should be on separate circuit for proper voltage, an ...

  • Friedrich SH20J30B-A - page 13

    13 PROBLEM POSSIBLE CAUSE T O CORRECT Replace selector switch. Replace relay . Selector Switch Relay PROBLEM POSSIBLE CAUSE T O CORRECT Refer to Installation Instructions for proper installation. Adjust motor mount to attain proper fan blade and blower wheel clearance. Check for deteriorated compressor grommets, or missing mounting parts. Adjust an ...

  • Friedrich SH20J30B-A - page 14

    14 WIRING DIAGRAM FOR SH14J30B-A & SH20J30B-A ...

  • Friedrich SH20J30B-A - page 15

    15 HazardGard Cabinet Parts ...

  • Friedrich SH20J30B-A - page 16

    16 HazardGard Chassis Parts ...

  • Friedrich SH20J30B-A - page 17

    17 HAZARDGARD P ARTS LIST REF . P ART NO. DESCRIPTION APPLICA TION SS HH 12 40 JJ 33 00 BB -- AA 1 61 1-935-49 Compressor , T ecumseh, 230/208V; 60 Hz 1 Ph, Model A WG5515EXN ...................... 1 1 1 61 1-935-50 Compressor , T ecumseh, 230/208 V ; 60 Hz 1 Ph, Model AWG5519EXN ..................... 1 1 2 618-714-26 Motor , Fan 1/8 HP ........... ...

  • Friedrich SH20J30B-A - page 18

    18 HAZARDGARD P ARTS LIST REF . P ART NO. DESCRIPTION SS HH 12 40 JJ 33 00 BB -- AA APPLICA TION 14 618-028-02 Partition, Control Box ............................................................................................. ............ 1 1 4 618-043-02 Partition, Control Box ..................................................................... ...

  • Friedrich SH20J30B-A - page 19

    19 * 618-092-00 Lever , Fresh Air & Exhaust .................................................................................................. 1 1 * 618-062-00 Connector , Louver .............................................................................................................. .2 2 * 618-063-00 Louver , Grille ...................... ...

  • Friedrich SH20J30B-A - page 20

    20 Friedrich Air Conditioning Co. 4200 North Pan Am Expressway P .O. Box 1540, San Antonio, T exas 78295-1540, USA T el. (210) 357/4400 Fax: (210) 357/4480 Printed in the U.S.A HG2002 (02/02) Certified Parts... Use Factory ...

メーカー Friedrich カテゴリー Air Conditioner

Friedrich SH20J30B-Aのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- SH20J30B-Aの取扱説明書
- Friedrichの製品カード
- パンフレット
- またはFriedrich SH20J30B-Aの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Friedrich SH20J30B-Aの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Friedrich SH20J30B-Aの取り付け説明書、サービスマニュアル、簡易説明書、またはFriedrich SH20J30B-Aのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Friedrich SH20J30B-Aの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Friedrich SH20J30B-Aデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがFriedrich SH20J30B-Aを使用するのを助ける技術的文書のことです。説明書は通常、全てのFriedrich SH20J30B-Aユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Friedrichの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Friedrich SH20J30B-Aの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははFriedrich SH20J30B-Aの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Friedrich SH20J30B-Aに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Friedrich SH20J30B-Aデバイスの基本機能を使うにあたってのヒント。 Friedrich SH20J30B-Aのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Friedrich SH20J30B-Aに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるFriedrich SH20J30B-Aのメーカー/サービスへの連絡先に関する情報。

Friedrich SH20J30B-Aについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもFriedrich SH20J30B-Aの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがFriedrich SH20J30B-Aで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)