    1 PLACE THESE INSTRUCTIONS ADJACENT TO HEA TER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE. PRINTED IN U.S.A. 0303 P ART NO.195092-000 COMMERCIAL OIL FIRED W A TER HEA TER FOR HOT W A TER SUPPL Y • Installation • Operation • Service • Maintenance MODELS GPO 86-199 THRU GPO 69-700(A) CAUTION TEXT PRINTED OR OUTLINED IN RED CONT AINS INFORM ...

  • State Industries GPO 86-199 - page 2

    2 TEXT PRINTED OR OUTLINED IN RED CONT AINS INFORMA TION RELA TIVE TO YOUR SAFETY . PLEASE READ THOROUGHL Y BEFORE USING APPLIANCE. This is a typical oil-fired heater for commercial water heating applications. The principal components of the heater are shown and identified here. The identification plate illustrations on page 4 interpret certain mar ...

  • State Industries GPO 86-199 - page 3

    3 FEA TURES AND SPECIFICA TIONS ................................................... 2 APPROV ALS ....................................................................................... 3 IDENTIFICA TION Oil and Burner Nameplate Decal ............................................... 3 Oil Burner Specifications ........................................ ...

  • State Industries GPO 86-199 - page 4

    4 OIL BURNER SPECIFICA TIONS The oil burner nameplate decal includes a series code which identifies the major features of the oil burner . The series number is the last three digits of the burner code number . T able 3 below describes the oil burner characteristics for each series number . The burners are to be used with fuel oil not heavier than N ...

  • State Industries GPO 86-199 - page 5

    5 • The discharge opening of the relief valve should always be piped to an open drain. • Choose the point of major hot water usage, fuel supply and chimney . • Try to make hot water and oil piping as short as possible. • Insulate hot and cold water piping where heat loss and condensatio n may be a problem. CLEARANCES The heater has minimum ...

  • State Industries GPO 86-199 - page 6

    6 • When communicating with outdoors by means of vertical ducts, each opening shall have a free area of not less than one square inch per 4,000 Btu per hour (551 mm 2 /kW) (35 square inches per gallon of oil consumed per hour) of total input rating of all appliances in the enclosure. • If horizontal ducts are used, each opening shall have a fre ...

  • State Industries GPO 86-199 - page 7

    7 MUL TIPLE HEA TER FLUES When two or more oil-fired water heaters are connected to a single chimney or vent there shall be sufficient draft available for safe combustion and removal of combustion products to the outdoors from each heater . Refer to local codes for connection details. Only one oil-fired water heater should be connected to any one t ...

  • State Industries GPO 86-199 - page 8

    8 A TYPICAL HEA TER INST ALLA TION - FIGURE 9 Refer to pages 2, 3, and 4 in this manual for more information about burner series numbers and characteristics for adaptability to the following systems. SYSTEM TYPES Single Stage, Supply Line Only: The bottom of the oil storage tank must be above the level of the fuel unit, fig. 10. The fuel oil will f ...

  • State Industries GPO 86-199 - page 9

    9 BURNER The burner assembly is mounted on the flange of the combustion chamber , fig. 13. NOTE: Be certain combustion chamber opening is aligned with opening in heater flange, fig. 13, before placing burner into heater . 1. Place the flange gasket and combustion chamber seal over the burner tube. 2. Place the burner flange on the studs and into th ...

  • State Industries GPO 86-199 - page 10

    10 OPERA TION GENERAL Never operate the heater unless the tank is filled with water and a temperature and pressure relief valve is installed. FILLING 1. Oil burner electrical disconnect switch should be in the "OFF position 2. Close the heater drain valve. 3. Open a nearby hot water faucet to allow the air in the system to escape. 4. Fully ope ...

  • State Industries GPO 86-199 - page 11

    11 DUAL-BULB THERMOST A T (COVER REMOVED) FIGURE 17 BURNER CERTIFICA TE (COMBUSTION TEST) The Commercial Standard CS75 Oil Burner Certificate form must be filled in and posted in the vicinity of the water heater . Instructions for filling in certificate are on the back of the certificate. This must be done by the installer at the time the heater is ...

  • State Industries GPO 86-199 - page 12

    12 SEDIMENT REMOV AL W ater borne impurities consist of fine particles of soil and sand which settle out and form a layer of sediment on the bottom of the tank. For convenience, sediment removal and lime scale removal should be performed at the same time. LIME SCALE REMOV AL The amount of calcium carbonate (Lime) released from water is in direct pr ...

  • State Industries GPO 86-199 - page 13

    13 • Observe interior through opening - a small flashlight may be used ef fectively . • If the interior still shows water scale, the deliming process should be continued. • T o check UN•LIME® for continued use or reuse, place some lime scale or white chalk into a glass with a small amount of the solution. If the material is vigorously diss ...

  • State Industries GPO 86-199 - page 14

    14 ONE TEMPERA TURE - ONE HEA TER VERTICAL STORAGE T ANK FORCED CIRCULA TION WITH OR WITHOUT BUILDING RECIRCULA TION SCALD PREVENTION HOT WA TER CAN SCALD IF USED CARELESSL Y OR IN UNANTICIPA T ED MANNER. CAUTION IF BUILDING COLD WA TER SUPPL Y HAS A BACK FLOW PREVENTER, CHECK V AL VE OR W A TER METER WITH CHECK V AL VE, PROVISIONS FOR THERMAL EXP ...

  • State Industries GPO 86-199 - page 15

    15 SINGLE TEMPERA TURE OR BOOSTER TWO TEMPERA TURE - ONE HEA TER HIGH TEMPERA TURE STORAGE WITH OR WITH OUT RECIRCULA TION RETURN LINE FROM 180°F (82.2°C) CIRCULA TING LOOP (IF USED) NOTE: IF TEMPERED WA TER IS RECIRCULA TED RETURN LINE SHOULD BE CONNECTED A T POINT "A" * PIPE TO OPEN DRAIN DANGER: TEMPERA TURE SETTING SHOULD NOT EXCEED ...

  • State Industries GPO 86-199 - page 16

    16 TWO TEMPERA TURE - TWO HEA TERS HIGH TEMPERA TURE STORAGE WITH OR WITHOUT RECIRCULA TION * PIPE RELIEF V AL VE TO OPEN DRAIN NOTE: IF TEMPERED WA TER IS RECIRCULA TED, RETURN LINE SHOULD BE CONNECTED A T POINT "A" FOR MUL TIPLE HEA TER INST ALLA TION SEE MANIFOLD KIT SPECIFICA TIONS, P AGES 19. DANGER: TEMPERA TURE SETTING SHOULD NOT E ...

  • State Industries GPO 86-199 - page 17

    17 TWO TEMPERA TURE - THREE HEA TERS (TWO PRE-HEA TERS/ONE BOOSTER) WITH OR WITHOUT CIRCULA TION TWO TEMPERA TURE - TWO HEA TERS (ONE PRE-HEA TER/ONE BOOSTER HEA TER) WITH OR WITHOUT RECIRCULA TION * PIPE RELIEF V A L VE TO OPEN DRAIN ** 140°F (60°C) TO 150°F (65.5°C) SHOULD BE MAXIMUM W A TER TEMPERA TURE MAINT AINED IN THE PRE-HEA TERS. 120° ...

  • State Industries GPO 86-199 - page 18

    18 TWO TEMPERA TURE-ONE HEA TER HIGH TEMPERA TURE ST ORAGE WITH RECIRCULA TION OF SANITIZING LOOP NOTE 1: T OGGLE SWITCH CONTROLS 180°F WA TER CIRCULA TION. INST ALL ON OR CLOSE T O DISHWASHING MACHINE . TOGGLE SWITCH MUST BE CLOSED (ON) DURING THE RINSE OPERA TION AND OPEN (OFF) WHEN DISHW ASHER IS NOT OPERA TING. NOTE 2: INST ALL LINE TEMPERA TU ...

  • State Industries GPO 86-199 - page 19

    19 THREE UNIT MANIFOLD KIT (P ART NO. 78693) FOUR UNIT MANIFOLD KIT (P ART NO. 78694) CHECK LIST AND SERVICE INFORMA TION IMPORT ANT The installer may be able to observe and correct certain problems which might arise when the unit is put into operation or when it is refired after a prolonged shut-down. HOWEVER, it is recommended that only qualified ...

  • State Industries GPO 86-199 - page 20

    20 8. Burner may not be firing at proper rate. • Check nozzle size. • Check fuel pump pressure setting. • GPO-199 . . . . . . . . . . . 1 10 psig (758 kPa) • All others . . . . . . . . . . . 100 psig (689.5 lPa) 9. Burner may be short cycling. Short cycling (too frequent off and on) of burner will cause sooting. If unit or burner become dir ...

  • State Industries GPO 86-199 - page 21

    21 If the problem is not getting a spark to ignite the oil, check for the following: 1. Loose wiring. 2. Red ignition transformer . 3. Low voltage. 4. Crack in electrode porcelain insulators. 5. Electrodes carboned or out of adjustment. 6. Weak or no contact between bus bars and terminals of transformer . NORMAL ST ART , BUT LOCKS OUT ON SAFETY Whe ...

  • State Industries GPO 86-199 - page 22

    22 TROUBLESHOOTING TROUBLE CAUSE REMEDY Oil level below intake line in supply tank. Fill tank with oil. Clogged strainer or filter . Remove and clean strainer . Replace filter element. Clogged nozzle. Replace nozzle. Air leak in intake line. T ighten all fittings in intake line. T ighten unused intake port plug. Check filter cover and gasket. Restr ...

  • State Industries GPO 86-199 - page 23

    23 COMMERCIAL OIL FIRED W A TER HEA TER MODEL GPO XX - 199, 245, 315, 385, 455 & 700 AND GPO XX - 315A, 385A, 455A & 700A ITEM NO. 13 ITEM NO. 25 REPLACEMENT P ARTS LIST CLEANOUT ASSEMBLY OIL STATE WATER HEATERS 500 Lindahl Parkway, Ashland City, TN 37015 Phone: 800-821-2017 • Fax: 800-644-9306 www.stateind.com ...

  • State Industries GPO 86-199 - page 24

    24 GPO 86 GPO 86 GPO 84 GPO 75 GPO 75 GPO 69 ITEM DESCRIPTION 199 245 315 385(A) 455(A) 700(A) 1 .... *Anode ................................... 183523-42(2) .. . 183523-42(2) ...... 183523-42(2) ....... 183523-39(3) ....... 183523-39(3) ..... 183523-39(4) 2 .... Baffle, Flue ............................. 39616-13(6) ..... 39616-13(6) ........ 3961 ...

メーカー State Industries カテゴリー Water Heater

State Industries GPO 86-199のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- GPO 86-199の取扱説明書
- State Industriesの製品カード
- パンフレット
- またはState Industries GPO 86-199の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、State Industries GPO 86-199の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、State Industries GPO 86-199の取り付け説明書、サービスマニュアル、簡易説明書、またはState Industries GPO 86-199のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、State Industries GPO 86-199の製品を使用するにあたって最も人気のある説明書を閲覧できます。

State Industries GPO 86-199デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがState Industries GPO 86-199を使用するのを助ける技術的文書のことです。説明書は通常、全てのState Industries GPO 86-199ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

State Industriesの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. State Industries GPO 86-199の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははState Industries GPO 86-199の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。State Industries GPO 86-199に関してこのドキュメントで見つけることができる全てのヒントの目次
3. State Industries GPO 86-199デバイスの基本機能を使うにあたってのヒント。 State Industries GPO 86-199のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。State Industries GPO 86-199に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるState Industries GPO 86-199のメーカー/サービスへの連絡先に関する情報。

State Industries GPO 86-199についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもState Industries GPO 86-199の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがState Industries GPO 86-199で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)