    NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property dam ...

  • Bryant 598B - page 2

    INSTALLATION I. CHECK EQUIPMENT AND JOB SITE A. UNPACK UNIT Move to final location. Remove carton, taking care not to damage unit. B. INSPECT EQUIPMENT File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit corner panel. It contains information needed to properly install unit. C ...

  • Bryant 598B - page 3

    INSTALLING TXV IN PLACE OF PISTON 1. Remove any existing refrigerant and ensure coil has not been exposed to atmospheric pressure for more than 15 minutes. 2. Remove indoor coil inlet tube at piston body inlet. Use back-up wrench to prevent damage. 3. Remove piston retainer, begin careful not to damage scaling surface of O-ring. 4. Remove and disca ...

  • Bryant 598B - page 4

    CAUTION: If ANY refrigerant tubing is buried, provide 6 – in. vertical rise at service valve. Refrigerant tubing lengths up to 36 in. may be buried without further special consideration. Buried refrigerant tubing lengths greater than 36 in. are NOT recommended. CAUTION: To prevent damage to unit or service valves, observe the following: • Use a ...

  • Bryant 598B - page 5

    G. FINAL TUBING CHECK IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight. VII. MAKE ELECTRICAL CONNECTIONS WARNING: To avoid p ...

  • Bryant 598B - page 6

    VIII. INSTALL ELECTRICAL ACCESSORIES A. GENERAL Refer to the individual instructions packaged with kits or acces- sories when installing. Available electrical accessories include latent capacity control. See Fig. 11 for typical accessory wiring diagrams. B. LATENT CAPACITY CONTROL (LCC) The purpose of an LCC is to provide a dehumidification mode to ...

  • Bryant 598B - page 7

    O/ W2 W/W1 Y1 / W 2 G R THERMIDIST A T CONTROL MODEL RH V ARIABLE-SPEED CONDENSING FURNACE TW O-SPEED AIR CONDITIONER W/W1 G Y/ Y2 C Y2 R Y1 C DHUM HUM B S1 S2 W2 R C HEA T ST AGE 1 COOL ST AGE 1 COOL ST AGE 2 HEA T ST AGE 2 FA N 24 V A C HOT 24 V A C COMM DEHUMIDIFY HUMIDIFY N/A OUTDOOR SENSOR CONNECTION Y/ Y2 HUMIDIFIER (24 V A C) OUTDOOR SENSOR ...

  • Bryant 598B - page 8

    COOL ST AGE 1 FA N HEA T ST AGE 1 COOL ST AGE 2 N/A 24 V A C HOT R W/W1 Y/Y2 O/W2 Y1/W2 G 24 V A C COMM N/A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C PROGRAMMABLE THERMOST A T MODEL 2S SINGLE-ST AGE FURNACE TW O-SPEED AIR CONDITIONER W R Y1 R G Y See notes 1, 2, 3, and 5 A01501 24 V A C HOT 24 V A C COMM HEA T ST AGE 1 COOL ST AGE 2 FA N R C G W/W ...

  • Bryant 598B - page 9

    24 V A C HO T FA N COOL ST AGE 1 COOL ST AGE 2 HEA T ST AGE 1 HEA T ST AGE 2 R G R G 24 V A C COMM N/A OUTDOOR SENSOR CONNECTION C B S1 S2 C C R PROGRAMMABLE THERMOST A T MODEL 2S FK4C, FV4A OR 40FK F AN COIL J1 JUMPER REMO VE J2 JUMPER FOR HEA T ST AGING TWO-SPEED AIR CONDITIONER DH Y1 Y1 W/W1 O/W2 Y1/W2 W1 Y/Y2 Y2 Y/Y2 O W2 See notes 1, 2, 3, 5, ...

  • Bryant 598B - page 10

    WIRING DIAGRAM NOTES: 1. WIRING MUST CONFORM TO NEC OR LOCAL CODES. 2. UNDERLINED LETTER ON THERMOSTAT TERMINAL INDICATES USAGE. FOR EXAMPLE: O/W2 MEANS O IS ENERGIZED IN COOLING MODE. 3. REFER TO INDOOR UNIT INSTALLATION INSTRUCTIONS FOR ANY ADDITIONAL FEATURES AND WIRING INFORMA- TION. 4. NON-PROGRAMMABLE MODEL 2S01 – B, WHEN USED IN AIR CONDIT ...

  • Bryant 598B - page 11

    X. START-UP CAUTION: To prevent compressor damage or personal injury, observe the following: • Do not overcharge system with refrigerant. • Do not operate unit in a vacuum or at negative pressure. • Do not disable low-pressure switch. CAUTION: To prevent personal injury wear safety glasses, protective clothing, and gloves when handling refrig ...

  • Bryant 598B - page 12

    NOTE: If subcooling charging conditions are not favorable, charge must be weighed in accordance with unit rating plate ± 0.6 oz/ft of 3/8-in. liquid line above or below 15 ft respectively. EXAMPLE: To calculate additional charge required for a 25 ft line set: 25 ft - 15 ft = 10 ft x 0.6 oz/f t=6o zo f additional charge. XII. SYSTEM FUNCTIONS AND S ...

  • Bryant 598B - page 13

    I. PRESSURE SWITCH PROTECTION The outdoor unit is equipped with high- and low-pressure switches. If the control senses the opening of a high or low pressure switch, it will respond as follows: 1. De-energize the compressor low or high speed contactor, 2. Keep the outdoor fan operating for 15 minutes, 3. Display the appropriate error code on the sta ...

  • Bryant 598B - page 14

    XIII. FINAL CHECKS IMPORTANT: Before leaving job, be sure to do the following: 1. Ensure that all wiring and tubing is secure in unit before adding panels and covers. Securely fasten all panels and covers. 2. Tighten service valve stem caps to 1/12 turn past finger tight. 3. Leave Owner ’ s Manual with owner. Explain system opera- tion and period ...

  • Bryant 598B - page 15

    Fig. 15 — Wiring Diagram — 024, 036, 048 A01513 CONNECTION DIAGRAM OCT -t ° LPS HPS OAT -t ° LO HI TO INDO O R UN IT RED CCH FA N C A P YEL RED BRN OFM BL K BL U/ PNK BLU/ PNK YEL / PN K YEL / PNK BRN BRN BLK BLK RED BL U CH 11 21 23 23 YEL BLK BLK BLK C L 11 21 H C STAR T COMP RELAY BRN CAP L2 L1 EQUI P GND DUA L CAP ACI T Y ABC D BLU BRN BR ...

  • Bryant 598B - page 16

    Fig. 16 — Wiring Diagram — 060 A02212 CONNECTION DIAGRA M OCT -t ∞ LPS HPS OAT -t ∞ LO HI T O IN DO O R U NIT RED CCH FA N CA P RED BRN OFM BL K BL U/ PNK BLU / PNK YEL / P NK YEL / PN K BRN BR N BLK RE D BLU CH 11 21 23 13 YEL BLK BLK H C ST ART COMP RELA Y BRN CAP L2 L1 EQUI P GND DUAL CAP A C I TY AB CD BLU BRN BLK YEL BRN BLK C O W Y 2 ...

メーカー Bryant カテゴリー Air Conditioner

Bryant 598Bのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 598Bの取扱説明書
- Bryantの製品カード
- パンフレット
- またはBryant 598Bの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Bryant 598Bの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Bryant 598Bの取り付け説明書、サービスマニュアル、簡易説明書、またはBryant 598Bのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Bryant 598Bの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Bryant 598Bデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがBryant 598Bを使用するのを助ける技術的文書のことです。説明書は通常、全てのBryant 598Bユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Bryantの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Bryant 598Bの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははBryant 598Bの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Bryant 598Bに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Bryant 598Bデバイスの基本機能を使うにあたってのヒント。 Bryant 598Bのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Bryant 598Bに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるBryant 598Bのメーカー/サービスへの連絡先に関する情報。

Bryant 598Bについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもBryant 598Bの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがBryant 598Bで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)