    E6581343 ③ TOSVERT VF-AS1/PS1 PROFIBUS-DP Option Function Manual PDP002Z * The data given in this manual are subject to change without notice. © Toshiba Schneider Inverter Corporation 2006 All rights reserved. ...

  • Toshiba PDP002Z - page 2

    E6581343 ③ - 1 - Contents 1. Intr oducti on ................................................................................................................ ...............................2 2. Connection In format ion ...................................................................................................... ...................... 3 2. ...

  • Toshiba PDP002Z - page 3

    E6581343 ③ - 2 - 1. Introduction Thank you for purchasing the PROFIBUS-D P option “PDP002Z” for the VF-AS1/PS1. Before using the PROFIBUS-DP option, pleas e familiarize yourself with the product and be sure to thoroughly read the instructions and precautions contained in this manual. In addition, please make sure that this m anual and “Inst ...

  • Toshiba PDP002Z - page 4

    E6581343 ③ - 3 - 2. Connection Information This option allows the VF-AS1/PS1 inverter to be communicated with the cyclic command transmission and monitoring of the original pr ofile ("USER DEFIND", refer to page 19) of our company other than application profile "Pro file for Variable Speed Drives PROFIdrive (3.072), refer to page 8 ...

  • Toshiba PDP002Z - page 5

    E6581343 ③ - 4 - 2.2. PDP002Z Device Data Parameter Value Note Vendor_Name "TSIJ" - Model_Name "PDP002Z" - Revision "V1.1" - Ident_Number 0x093C ID number Protocol_Ident 0 PROFIBUS-DP Station_Type 0 DP slave FMS_supp 0 PROFIBUS-FMS: not supported Hardware_Release "V1.0" - Software_Release "V1.0" - ...

  • Toshiba PDP002Z - page 6

    E6581343 ③ - 5 - 2.3. Setting a station address The DIP switch on the circuit board of the opt ion is used to set a station address. Each DIP switch is ON when it is flipped to the lower position. By default, it is factory-configured to 2. The station address must be unique and not match any other device on the network. SW ID 1 2 3 4 5 6 7 8 SW I ...

  • Toshiba PDP002Z - page 7

    E6581343 ③ - 6 - SW ID 1 2 3 4 5 6 7 8 SW ID 1 2 3 4 5 6 7 8 64 OFF ON OFF OFF OFF OFF OFF OFF 96 OFF ON ON OFF OFF OFF OFF OFF 65 OFF ON OFF OFF OFF OFF OFF ON 97 OFF ON ON OFF OFF OFF OFF ON 66 OFF ON OFF OFF OFF OFF ON OFF 98 OFF ON ON OFF OFF OFF ON OFF 67 OFF ON OFF OFF OFF OFF ON ON 99 OFF ON ON OFF OFF OFF ON ON 68 OFF ON OFF OFF OFF ON OF ...

  • Toshiba PDP002Z - page 8

    E6581343 ③ - 7 - 2.4. Status indicator The PDP002Z has two LEDs, ST (status) and DX (data exchange) to indicate the statuses of PROFIBUS-DP and the PDP002Z itself. ST (Status): Red LED LED Meanings Off No diagnostics present Flashes Waiting for parameter isation or configuration Lights DP status error * For example, a station addr ess is not setc ...

  • Toshiba PDP002Z - page 9

    E6581343 ③ - 8 - 3. “PROFIdrive” Profile 3.1. PPO TYPE The PPO type of PDP002Z is set up by this parameter. The PROFIBUS-DP protocol uses so-called PPOs (Parameter/Process Data Object s) in cyclic communication. The figures below show the PPO types and configurations that the PDP002Z supports . PKW PZD PKE IND PWE PZD1 STW ZSW PZD2 HSW HIW PZ ...

  • Toshiba PDP002Z - page 10

    E6581343 ③ - 9 - 3.2. STW Control Word Data PDP002Z supports only speed control mode. Bit Value Name Note 1 ON Drive can be started if all other start conditions are fulfilled. 0 0 OFF 1 Normal stop. 1 Operating condition Drive can be started if all other start conditions are fulfilled. 1 0 OFF 2 Coast stop. 1 Operating condition Drive can be sta ...

  • Toshiba PDP002Z - page 11

    E6581343 ③ - 10 - 3.3. ZSW Status Word Data Bit Valur Name Note 1 Ready to sw itch-on Control w ord bit 0 = 0 and bit1, 2, 10 are set to 1. 0 0 Not ready sw itch-on Control w ord bit 0 = 0, 1, 2 or 10 are set to 0, or the inverter is tri pp ed. 1 Ready Refer to control word, bit 0. 1 0 Not ready - 1 Operating enabled Refer to control word, bit 3. ...

  • Toshiba PDP002Z - page 12

    E6581343 ③ - 11 - 3.4. State Macine CW: Control Word ST: Status Word : Status SWITCH-ON INHIBIT NOT READY TO SWITCH-ON READY TO SWITCH-ON OPERATING READY TO OPERATE OPERATION INHIBIT OFF1 ACTIVE OFF3 ACTIVE OFF2 ACTIVE FAULT ENABLE OPERATION SW: Bit6 = 1 CW: Bit0 = 0 CW: xxxx xxxx xxxx x110 SW: Bit0 = 1 CW: xxxx xxxx xxxx x111 from any state FAUL ...

  • Toshiba PDP002Z - page 13

    E6581343 ③ - 12 - 3.4.1. Examples of driv ing by the State Machine When using the PROFIdrive profile, the frequenc y reference is set to HSW. The setting value “0x0000” - ”0x4000” is equivalent to ”0” - ”Base frequency (parameter vl )”. When the reverse operation, the frequency referenc e is set with two's complement of the f ...

  • Toshiba PDP002Z - page 14

    E6581343 ③ - 13 - 3.5. The Access to the PROFIBUS parameter In the cyclic PROFIBUS-DP communication, the parameter data is transferred via PPO TYPE1 and 2. If the requirement is not execut ed, the cause is distinguished by octet 7 and 8. PKW (Parameter ID/value) PZD Process data (cyclically) PKE IND PWE PZD1 STW ZSW PZD2 HSW HIW Octet 1 Octet 2 O ...

  • Toshiba PDP002Z - page 15

    E6581343 ③ - 14 - PNU (the parameter number) PNU R/W data type Note 915 R/W Array [10] Unsigned16 PNU 915, IND 1 = the inverter parameter f831 PNU 915, IND 2 = the inverter parameter f832 PNU 915, IND 3 = the inverter parameter f833 PNU 915, IND 4 = the inverter parameter f834 PNU 915, IND 5 = the inverter parameter f835 PNU 915, IND 6 = the inve ...

  • Toshiba PDP002Z - page 16

    E6581343 ③ - 15 - 3.5.1. Examples of reading or changing the PROFIdrive parameter 3.5.1.1. Example 1. R eading the PNU 964 (ID number) AK = 1 (Request parameter value) SPM = 0 PNU = 964 (0x03C4) PKE 0 0 0 1 0 0 1 1 1 1 0 0 0 1 0 0 1 3 C 4 Requirement PKW PZD PKE IND PWE 13 C4 00 00 00 00 00 00 ・・・ ・・・ Response (Value: 0x093C) 13 C4 00 ...

  • Toshiba PDP002Z - page 17

    E6581343 ③ - 16 - 3.5.1.3. Example 2. Changing t he PNU 933 (Control word, bit 11) AK = 2 (Change parameter value (word)) SPM = 0 PNU = 933 (0x03A5) PWE = 10 (0x000A) PKE 0 0 1 0 0 0 1 1 1 0 1 0 0 1 0 1 2 3 A 5 Requirement (PNU 933 = 10 ( f111 = 10)) PKW PZD PKE IND PWE 23 A5 00 00 00 00 00 0A ・・・ ・・・ Response (Value: 0x000D = Inverte ...

  • Toshiba PDP002Z - page 18

    E6581343 ③ - 17 - 3.6. Access to the VF-AS1/PS1 parameter When access to the VF-AS1/PS1 parameter, set “1” to the PNU. The communication number of the inverter parameter is set to the subindex IND. Refer to the inverter instruction m anual about the communication number and unit. 3.6.1. Examples of reading or changing the VF-AS1/PS1 parameter ...

  • Toshiba PDP002Z - page 19

    E6581343 ③ - 18 - 3.6.1.3. Example 3. Reading t he status monitor parameter ( fe02 (The operation frequency)) AK = 6 (Request parameter value (array)) SPM = 0 PNU = 1 IND = 0xFE02( fe02 communication number) PKE 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1 6 0 0 1 Requirement PKW PZD PKE IND PWE 60 01 FE 02 00 00 00 00 ・・・ ・・・ Response (Value: 0x0 ...

  • Toshiba PDP002Z - page 20

    E6581343 ③ - 19 - 4. ”USER DEFIND” Profile Cyclic command transmission (the value of the parameter f831 - f836 ) and monitoring (the value of the parameter f841 - f846 ) are possible for PDP002Z by the original profile Select the ”USER DEFIND” as the profile on the configuration. Refer to the PLC configurator documents. f831 - f836 setup ...

  • Toshiba PDP002Z - page 21

    E6581343 ③ - 20 - 4.1. How to use The purposes are adjustment by real time command transmission, and the monitor of an operation state by using cyclic communication of PROFIBUS. Example 1: Command transmitting When you want to set "0xC400" to parameter fa06 , set “1 (FA06)” to parameter f831 . And Since 0 and 1 byte of the PZD1 supp ...

  • Toshiba PDP002Z - page 22

    E6581343 ③ - 21 - 4.2. The overview of the VF-AS1/PS1 parameter Refer to a communication functional description (VF-AS1: E6581315/VF-PS1: E6581413) for details. 4.2.1. FA06 (Command word 1 from internal option PCB) bit Function 0 1 Note 0 Preset Speed1 1 Preset Speed2 2 Preset Speed3 3 Preset Speed4 OFF .................... 0000, 1 - 15 ......... ...

  • Toshiba PDP002Z - page 23

    E6581343 ③ - 22 - 4.2.3. FA07 (Frequency reference from internal option PCB) Frequency reference is set up by 0. 01Hz unit and the hexadecimal number. For example, when "Frequency reference" is set up to 80Hz, since the minimum unit is 0.01Hz, 80 / 0.01 = 8000 = 0x1F40 (Hex.) 4.2.4. FA33 (Torque reference from internal option PCB) Torqu ...

  • Toshiba PDP002Z - page 24

    E6581343 ③ - 23 - 4.2.8. FD01 (Inverter status (real time)) bit Function 0 1 Note 0 FL No output Under output - 1 EMG No fault Under fault The rtry status and the trip retention status are also regarded as tripped statuses. 2 ALARM No alarm Under alarm - 3 (Reserved) - - - 4 tHr2(VF2+tH2) Motor 1 (THR1) Motor 2 (THR2) THR1: thr THR2: f173 5 PI PI ...

  • Toshiba PDP002Z - page 25

    E6581343 ③ - 24 - 4.2.11. FE36 (Analog input value VI/II) The value inputted into the VI/II terminal is read. The value range is 0 - 10000 (0 - 100.00 %). Also the same as the parameter FE35 (RR Input). 4.2.12. FE37 (RX Input) The value inputted into the RX terminal is read. The value range is -10000 - 10000 (-100.00 - +100.00 %). 4.2.13. FE60 - ...

  • Toshiba PDP002Z - page 26

    E6581343 ③ - 25 - 4.2.16. FC91 (Alarm code) bit Function 0 1 Note 0 Over current alarm Normal Under alarm “ c ” blinking 1 Inverter over load alarm Normal Under alarm “ l ” blinking 2 Motor over load alarm Normal Under alarm “ l ” blinking 3 Over heat alarm Normal Under alarm “ h ” blinking 4 Over voltage alarm Normal Under alarm ...

  • Toshiba PDP002Z - page 27

    E6581343 ③ - 26 - 4.2.19. FC90, FE10 - FE 13 (Inverter fault) Data (hexa- decimal) Data (decimal) Code Description 0 0 nerr No error 1 1 oc1 Over-current during acceleration 2 2 oc2 Over-current during deceleration 3 3 oc3 Over-current during c onstant speed operation 4 4 ocl Over-current in load at startup 5 5 oca1 U-phase arm over-current 6 6 o ...

  • Toshiba PDP002Z - page 28

    E6581343 ③ - 27 - 4.3. About GSD file As for acquisition of an GSD file, it is possible to download from homepage of our company. Please use what was in agreement with t he software version of usage's VF-AS1/PS1. VF-AS1: http://www.inverter.c o.jp/product/inv/vfas1/pdp/ VF-PS1: http://www.inverter.c o.jp/product/inv/vfps1/pdp/ - 27E - ...

メーカー Toshiba カテゴリー Power Supply

Toshiba PDP002Zのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- PDP002Zの取扱説明書
- Toshibaの製品カード
- パンフレット
- またはToshiba PDP002Zの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Toshiba PDP002Zの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Toshiba PDP002Zの取り付け説明書、サービスマニュアル、簡易説明書、またはToshiba PDP002Zのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Toshiba PDP002Zの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Toshiba PDP002Zデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがToshiba PDP002Zを使用するのを助ける技術的文書のことです。説明書は通常、全てのToshiba PDP002Zユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Toshibaの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Toshiba PDP002Zの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははToshiba PDP002Zの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Toshiba PDP002Zに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Toshiba PDP002Zデバイスの基本機能を使うにあたってのヒント。 Toshiba PDP002Zのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Toshiba PDP002Zに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるToshiba PDP002Zのメーカー/サービスへの連絡先に関する情報。

Toshiba PDP002Zについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもToshiba PDP002Zの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがToshiba PDP002Zで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)