  • Goodman Mfg SSZ 14 SEER - page 1

    SSZ 14 SEER S plit System Heat Pump s • Refer to Service Manual RS6200005 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. • Models listed on page 3. RT6213005 Rev. 3 August 2010 Cop ...

  • Goodman Mfg SSZ 14 SEER - page 2

    PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause p ...

  • Goodman Mfg SSZ 14 SEER - page 3

    PRODUCT IDENTIFICA TION 3 The United States Environmental Protection Agency (“EPA”) has issued various regulations re- garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. These regulations may vary by ju ...

  • Goodman Mfg SSZ 14 SEER - page 4

    PRODUCT DESIGN 4 SSZ14 models are available in 1 1/2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet. These units are designed for ...

  • Goodman Mfg SSZ 14 SEER - page 5

    HEA T PUMP SPECIFICA TIONS 5 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...

  • Goodman Mfg SSZ 14 SEER - page 6

    HEA T PUMP SPECIFICA TIONS 6 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/ circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. S S Z 140181AF S S Z 140241AJ S S Z 140301AF S S Z 140361AH S S Z 140421AF S S Z 140481AF S S Z ...

  • Goodman Mfg SSZ 14 SEER - page 7

    7 COOLING PERFORMANCE DA T A SSZ140181A* EXP AN DE D PE RFORM ANCE DA T A C OOL I N G OP E R A TION M O DE L : S S Z 1 40181A* / CA*F 3131*6A* + TX V / M BR800** - 1 O ut door Am bi e nt Te m per at ure 65 75 8 5 95 105 115 E nter i ng I ndo or Wet B u lb Te m pe rat ure I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 ...

  • Goodman Mfg SSZ 14 SEER - page 8

    8 COOLING PERFORMANCE DA T A SSZ140181A* EXP AN DE D PERF O RM ANCE DA T A C OOL I N G OP E R ATION M O DE L : S S Z 1 40181A* / CA*F 3131* 6A* + T X V / M BR8 00**-1 O ut door Am bi e nt Tem pe ra ture 65 75 8 5 95 105 115 E nter i ng I ndoor W e t B u lb Te m pe rat ur e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 9 ...

  • Goodman Mfg SSZ 14 SEER - page 9

    9 COOLING PERFORMANCE DA T A SSZ140241A* EXPANDED PERF O RM ANCE DA T A C OOL I N G OP E R ATIO N M O DE L : S S Z 14 0241A* / CA*F3 636*6A*+ T X V / M B R800**-1 O utdoor Am bi e nt Te m pe r ature 65 75 85 95 105 1 15 E nte ring I ndoor We t B ulb Te m pe r ature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 77 ...

  • Goodman Mfg SSZ 14 SEER - page 10

    10 COOLING PERFORMANCE DA T A SSZ140241A* EX PANDED P ERF ORM ANCE DAT A C OOL IN G OP E R ATION M ODEL: S S Z 140241A* / CA*F3636*6A*+ T X V / M BR800**-1 O utdoor Am bi e nt Tem pe r ature 65 75 85 95 105 115 E nte r ing I ndoor We t B ul b Te m pe r ature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 77 15 96 3 ...

  • Goodman Mfg SSZ 14 SEER - page 11

    11 COOLING PERFORMANCE DA T A SSZ140301A* EXPA NDED PERFO RM ANC E DA T A C OOLI N G OP E R ATI O N M O D EL: S S Z 140301A* / CA*F 3642*6A*+T X V / M BR1600**- 1 O utdoo r Am bi e nt Te m pe ra ture 65 75 85 95 105 11 5 E nte r ing I ndoor We t B ul b Te m pe r a ture I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 ...

  • Goodman Mfg SSZ 14 SEER - page 12

    12 COOLING PERFORMANCE DA T A SSZ140301A* EX PANDED PERF O RM ANCE DAT A C O O L IN G O P E R A T IO N M O D EL: S S Z 140301A* / CA*F 3642*6A*+ TX V / M BR1600**-1 O utdoo r Am bi e nt T e m pe ra ture 65 75 85 95 105 115 E nte r i ng Indoo r We t B ul b Te m pe r at ure I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 ...

  • Goodman Mfg SSZ 14 SEER - page 13

    13 COOLING PERFORMANCE DA T A SSZ140361A* EXPA N DED PER FORM AN CE D ATA M ODEL: S S Z 140361A* / CA* F 4860*6A*+ TX V / M BR1600* *-1 O utdoo r Am bie nt Te m pe r a tur e 65 75 85 95 105 115 E n t e r in g In d o o r We t B u lb T e m pe r at u r e ID B Air flo w 5 9 63 67 71 59 6 3 67 71 59 63 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 M Bh 33. ...

  • Goodman Mfg SSZ 14 SEER - page 14

    14 COOLING PERFORMANCE DA T A SSZ140361A* EX PANDED PE RF O RM ANCE DATA C OOL IN G OP E R AT ION M ODEL: S S Z 140361A* / CA* F 4860*6A*+ TX V / M BR1600* *-1 O utdoor Am bie nt Te m pe r a tur e 65 75 85 95 105 115 E nter ing I nd oor Wet B u l b T e m pe r ature I D B * A i r f l o w 5 9 6 3 6 77 1 5 9 6 36 7 7 1 5 9 6 3 6 77 15 9 6 3 6 7 7 15 9 ...

  • Goodman Mfg SSZ 14 SEER - page 15

    15 COOLING PERFORMANCE DA T A SSZ140421A* EXPAN DED PERFORMAN CE DATA M ODEL : S S Z140421A* / CA*F 4860*6 A*+ T X V / M BR 2000**-1 O utdoor Am bi e n t Te m p e rature 65 75 85 95 105 115 E nte r ing I ndoo r We t B ulb Te m pe r atur e ID B A ir flo w 59 63 67 71 59 63 67 71 5 9 63 67 71 59 63 67 71 59 63 6 7 71 59 63 67 71 M Bh 39. 2 40.6 4 4.5 ...

  • Goodman Mfg SSZ 14 SEER - page 16

    16 COOLING PERFORMANCE DA T A SSZ140421A* EXPA NDED PER F O RM AN CE DA TA C OOL I N G OP E R AT I ON M O DE L : S S Z140421A* / CA*F 4860*6 A*+ TX V / M BR2000* *- 1 O u tdoor Am bi e n t Te m pe r ature 65 75 85 95 105 115 E nte r ing I ndoo r We t B ulb Te m pe r atur e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 ...

  • Goodman Mfg SSZ 14 SEER - page 17

    17 COOLING PERFORMANCE DA T A SSZ140481A* EXPA ND ED PER FOR M AN CE D ATA C OOL I N G OP E R ATIO N M O DEL: S S Z 14 0481A* / CA*F 4860*6A* + T X V / M BR20 00**-1 O u tdoor Am bi e n t Te m pe rature 65 75 85 95 105 115 E n te r ing Ind o o r We t Bulb T e m p e r at u r e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 ...

  • Goodman Mfg SSZ 14 SEER - page 18

    18 COOLING PERFORMANCE DA T A SSZ140481A* EXPA ND ED PER FO RM AN CE D ATA C OOLIN G OP E R AT I O N M O DEL: S S Z 14 0481A* / CA*F 4860* 6A*+ T X V / M BR2000* *-1 O utdoor Am bi e n t Te m pe rature 65 75 85 95 105 115 E n te r in g In d o o r W e t B u lb Te m p e r a t u r e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 ...

  • Goodman Mfg SSZ 14 SEER - page 19

    19 COOLING PERFORMANCE DA T A SSZ140601A* EXP AND E D PERF O RM A NCE DATA C OOL I N G OP E R ATION M O DE L: S S Z 140601 A* / CA*F4860*6 A*+ T X V / M BE2 000**- 1 O utdoor A m bi e nt Te m pe r a ture 65 75 8 5 95 105 115 E nter i ng I ndoor W e t B ul b Te m p e ra ture ID B Air flow 59 63 67 71 5 9 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 ...

  • Goodman Mfg SSZ 14 SEER - page 20

    20 COOLING PERFORMANCE DA T A SSZ140601A* EXP AND E D PERF ORM ANCE DAT A C OOL I N G OP E R ATION M ODEL: S S Z 140601A* / CA*F4860*6A *+ TX V / M BE 2000**- 1 O utd oor Am bi e nt Te m pe ra ture 65 75 8 5 95 105 115 E nter i ng I ndoor W e t B ul b Te m peratu r e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 7 ...

  • Goodman Mfg SSZ 14 SEER - page 21

    21 PERFORMANCE DA T A Out door Temp. ° F . Total Btuh Sensible Btu h La te nt Btuh Total Wat ts 75° 36,330 24,713 11,617 2,662 80° 35,898 24,729 11,169 2,742 85° 35,465 24,738 10,727 2,822 90° 35,033 24,830 10,203 2,892 95° 34,600 24,912 9,688 2,963 100° 33,735 24,749 8,986 3,0 23 105° 32,870 24,563 8,307 3,0 83 110° 31,659 23,757 7,902 3, ...

  • Goodman Mfg SSZ 14 SEER - page 22

    22 EXPA NDED PERFORM A NCE DATA M ODEL: SSZ140361A * / CA*F4860C6A *+TXV / M BR1600**-1 HEATING O PERATION Outdoo r Ambient Tem p era ture 65 60 55 50 47 45 40 35 30 25 2 0 17 15 10 5 0 -5 -10 MBh 4 3.5 41.2 38.8 36.2 34.6 33.5 31 .1 28.7 28.8 26.6 24.5 23. 1 22 .3 20.0 17.7 1 5.5 13.2 10.8 Delta T 38.4 36.3 34.2 31.9 30.5 29. 6 27.5 25.3 2 5.4 23. ...

  • Goodman Mfg SSZ 14 SEER - page 23

    23 EXPANDED PERFORM ANCE DA TA MO DEL: SSZ140481A* / CA*F4860*6A *+TXV / MBR2000**-1 HEA T ING OPERATION Outdoor Ambie nt Temperat ure 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 - 5 -10 MBh 57.8 5 4.7 5 1.5 48. 2 46.0 4 4.6 41.4 38.2 36 .6 33.8 31.1 29. 4 28.3 25.4 22. 5 19.6 16.8 13. 7 D e l t a T 3 4 . 53 2 . 73 0 . 82 8 . 8 2 7 . 5 2 6 . 62 4 ...

  • Goodman Mfg SSZ 14 SEER - page 24

    24 HEA TING SPECIFICA TIONS capacit y btuh c.o.p. 4.8 9.6 1 4.4 19. 2 65 22.63 4.23 39.01 55.39 71.77 88.16 60 21.42 4.09 37.80 54.18 70.57 86.95 55 20.16 3.93 36.54 52.92 69.31 85.69 50 18.85 3.75 35.23 51.61 67.99 84.38 45 17.44 3.54 33.82 50.21 66.59 82.97 40 16.20 3.36 32.58 48.96 65.35 81.73 35 14.94 3.16 31.32 47.70 64.09 80.47 30 12.80 2.70 ...

  • Goodman Mfg SSZ 14 SEER - page 25

    25 HEA TING SPECIFICA TIONS capaci t y btuh c. o. p. 4 .8 9.6 14. 4 19. 2 65 51.5 4 4 .44 67 .92 84. 30 100. 68 117. 07 60 48.7 9 4 .28 65 .17 8 1. 55 97. 94 114. 32 55 45.9 2 4 .11 62 .30 7 8. 68 95. 07 111. 45 50 42.9 3 3 .92 59 .31 7 5. 69 92. 07 108. 46 45 39.7 3 3 .70 56 .11 7 2. 49 88. 88 105. 26 40 36.9 0 3 .50 53 .28 6 9. 66 86. 05 102. 43 ...

  • Goodman Mfg SSZ 14 SEER - page 26

    26 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a ...

  • Goodman Mfg SSZ 14 SEER - page 27

    WIRING DIAGRAMS 27 HIGH VOL T AGE! DIS CONNECT ALL POWER BEFORE SERVICING OR INST A LLIN G THIS UNIT . MUL T IPLE POW ER SOURCES MA Y BE PRESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAGE, PERSONAL I NJURY OR DEA TH . Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. SSZ140[18,30,42-60 ...

  • Goodman Mfg SSZ 14 SEER - page 28

    WIRING DIAGRAMS 28 HIGH VOL T A GE! DISCO NNECT A LL POWE R BEFORE SERVICI NG OR INS T A LLIN G THIS UNIT . M UL T IPLE POW ER SOURCES MA Y BE PRESENT . F AI LURE TO DO SO MA Y C AUS E PROP ERTY DAMAG E, PERSONAL I NJURY OR DE A TH . USE N.E .C. CL ASS 2 WI R E NOTES: 1) TO INDO OR UNI T LO W VOLT A GE TER M IN AL BLOC K & IN DO O R T H E R MO ...

メーカー Goodman Mfg カテゴリー Heat Pump

Goodman Mfg SSZ 14 SEERのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- SSZ 14 SEERの取扱説明書
- Goodman Mfgの製品カード
- パンフレット
- またはGoodman Mfg SSZ 14 SEERの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Goodman Mfg SSZ 14 SEERの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Goodman Mfg SSZ 14 SEERの取り付け説明書、サービスマニュアル、簡易説明書、またはGoodman Mfg SSZ 14 SEERのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Goodman Mfg SSZ 14 SEERの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Goodman Mfg SSZ 14 SEERデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがGoodman Mfg SSZ 14 SEERを使用するのを助ける技術的文書のことです。説明書は通常、全てのGoodman Mfg SSZ 14 SEERユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Goodman Mfgの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Goodman Mfg SSZ 14 SEERの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははGoodman Mfg SSZ 14 SEERの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Goodman Mfg SSZ 14 SEERに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Goodman Mfg SSZ 14 SEERデバイスの基本機能を使うにあたってのヒント。 Goodman Mfg SSZ 14 SEERのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Goodman Mfg SSZ 14 SEERに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるGoodman Mfg SSZ 14 SEERのメーカー/サービスへの連絡先に関する情報。

Goodman Mfg SSZ 14 SEERについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもGoodman Mfg SSZ 14 SEERの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがGoodman Mfg SSZ 14 SEERで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)