Summary
  • Trane WCY042G1 - page 1

    IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING WARNING: Single P ac kag e Heat Pump 13-14 SEER Con ver tible 2 - ...

  • Trane WCY042G1 - page 2

    Page 2 TYPICAL ROOFTOP INSTALLATION WITH FULL PERIMETER CURBS (WCY024-060G Models) GENERAL INFORMA TION IMPORTANT: Read this entire manual before beginning instal- lation procedures. SAFETY NOTICE. THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS POSSESSING ADEQUATE BACK- GROUNDS OF ELECTRICAL AND MECHANICAL EXPERI- ENCE. ANY ATTEMPT TO REPAIR A ...

  • Trane WCY042G1 - page 3

    Page 3 ROOF INSULA TION ROOF DECK FIELD SUPPLIED RIGID INSULA TION SUPPL Y AIR DUCT RETURN AIR DUCT ROOF MOUNTING CURB FIELD SUPPLIED CANT STRIP FIELD SUPPLIE D SUPPORTS A T EACH END OF CURB ROOFING SEE NOTE 1 SEE NOTE 2 CONVERTING HORIZONTAL TO DOWNFLOW TYPICAL ROOFTOP INSTALLATION WITH BAYCURB030A (WCY024-060G Models) NOTE SUPPLY OPENING 1. REMOV ...

  • Trane WCY042G1 - page 4

    Page 4 DIMENSIONAL D A T A 4 MOD EL CORNER WEIGHT(LBS) UNIT WEI G HT AB C D E F G H J KL M N P W1 W2 W3 W4 WCY 024G 79 74 74 104 331 56-1/2 36 29-3/16 18-9/16 11-1/1 6 6-9/16 6-13/16 17 21 25-3/8 17 -1/2 10 3 4-7/16 WCY 030G 82 64 86 110 342 21 24-3 /8 WCY 036G 110 82 88 118 398 64 36 29 -1/16 18-9/16 11 -1/ 16 6-9/16 11-1/8 17 19-1/4 27-1/2 17 -1/ ...

  • Trane WCY042G1 - page 5

    Page 5 DIMENSIONAL D A T A 5 From Dwg. 21D664 MODEL A B C D WCY024G WCY030G 56-1 /2 36 2 9-3/16 12-15 /1 6 WCO36G WCY042G 64 36 29-3/1 6 14- 1/2 WCY048G WCY060G 65-1/8 45 33-3/8 14 -13/1 6 RECOMM ENDED SER VI CE CLEARANC E BA CK * 6.0" LEFT SIDE 30.0" RIGHT SIDE 24.0" FR ONT SI DE 30.0" * 18" WITH F RESH AIR A CCESSO R Y * ...

  • Trane WCY042G1 - page 6

    Page 6 REQUIRED CLEARANCE FOR UNIT INSTALLATION AND ROOF PENETRATION HOLE SIZE REQUIRED LOCA TIONS AND RECOMMEND A TIONS These units are designed for outdoor installation. For proper instal- lation, the following recommendations must be considered. NOTE: Unit shipped for horizontal installation. Convert to downflow per instruction. The discharge ai ...

  • Trane WCY042G1 - page 7

    Page 7 INST ALLA TION IMPORTANT!: DO NOT LIFT THE UNIT WITHOUT TEST- LIFTING FOR BALANCE AND RIGGING.DO NOT LIFT THE UNIT IN WINDY CONDITIONS OR ABOVE PERSONNEL. DO NOT LIFT THE UNIT BY ATTACHING A CLEVIS, HOOKS, PINS OR BOLTS TO THE UNIT CASING, CASING HARD- WARE, ANGLES, TABS OR FLANGES. FAILURE TO OB- SERVE THESE WARNINGS MAY RESULT IN EQUIPMENT ...

  • Trane WCY042G1 - page 8

    Page 8 8 7 NOTE: The inner perimeter of the Drip Lip on all units should be flush with the outer perimeter of the curb on the two sides shown here. See Figure 2 for the location of the unit overhang on the WCY036-060G Models with BAYCURB030A. SPREADER BARS OUTDOOR COIL END OF UNIT GASKET SEAL BASE OF UNIT REST ON TOP OF CURB RAILS DRIP LIP DIMPLE B ...

  • Trane WCY042G1 - page 9

    Page 9 TYPICAL ROOFTOP APPLICATION WITH FRAME (WCY024-060G MODELS) INST ALLA TION ROOFTOP -- UNITS For roof top applications using a field fabricated frame and ducts, use the following procedure: 1. The frame must be located and secured by bolting or welding to the roof. Flashing is required. 2. The hole in the roof must be prepared in advance of i ...

  • Trane WCY042G1 - page 10

    Page 10 TYPICAL GROUND LEVEL APPLICATION (WCY024-060G MODELS) INST ALLA TION GROUND LEVEL -- HORIZONTAL UNITS For ground level installations, the unit should be positioned on a pad the size of the unit or larger. The unit must be level on the pad. The pad must not come in contact with the structure (See Figure 11.) Be sure the outdoor portion of th ...

  • Trane WCY042G1 - page 11

    Page 11 DUCT ATTACHMENT METHODS 3 / 4 " PVC OR COPPER TUBING AND FITTINGS 1-1/2" MIN. TYPICAL CONDENSATE DRAIN PIPING A 3/4-inch female NPT condensate drain connection is pro- vided on the evaporator access panel end of the unit. See Figure 4. Provide a trap and fill it with water before starting the unit to avoid air from being drawn thr ...

  • Trane WCY042G1 - page 12

    Page 12 ELECTRICAL CONNECTIONS Electrical wiring and grounding must be installed in accordance with local codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA 70, Latest Revision. ELECTRICAL POWER It is important that proper electrical power be available for the unit. Voltage variation should remain within the limits ...

  • Trane WCY042G1 - page 13

    Page 13 WCY-G FIELD WIRING DIAGRAM Thermostat System Switch until power has been applied long enough to evaporate any liquid R-22 in the compressor. It is recommended that the sump heater be energized for eight (8) hours prior to starting. After all electrical wiring is complete, set the thermostat system switch in the OFF position so that the comp ...

  • Trane WCY042G1 - page 14

    Page 14 ST AR T - UP To start the unit in the cooling mode, set the thermostat system switch to COOL and move the thermostat COOL indicator to a setting below room temperature. The condenser (outdoor) fan motor compressor and evaporator (indoor) fan motor will operate automatically. OPERATING PRESSURES After the unit has operated in the cooling mod ...

  • Trane WCY042G1 - page 15

    Page 15 SEQUENCE OF OPERA TION GENERAL Operation of the unit heating and cooling cycles is automatic for HEAT and COOL functions. (The optional automatic changeover thermostat, when in the AUTO position, automatically changes to heat or cool with sufficient room temperature change.) The fan switch can be placed in either the ON position, causing co ...

  • Trane WCY042G1 - page 16

    Page 16 FLASH RA TE INDICA TIONS: 1 — Flash/Second = Normal operation. 2 — Flashes/Second = F ault A (Low ∆ T) i.e.: Inoperativ e compressor , loss of charge, open ambient sensor , shor ted coil sensor . 3 — Flashes/Second = F ault B (20 defrosts ter minated on time) F ault C (High ∆ T) i.e.: SO V stuck in heating, shor ted ambient sensor ...

  • Trane WCY042G1 - page 17

    Page 17 DEMAND DEFR OST CONTROL CHECK OUT SYMPTOMS CHECKS YES/NO A CTIONS 1. LED off . 1. 24V R-B & Y -B at board, with unit running? N Repair low v oltage wiring. Y Complete Check #2. 2.Shor t FRC_DFT pin to TEST_COMMON pin. Is defrost cycle initiated? N Replace defrost control. Y LED is bad but control will still funct ion. 2. LED flashing ve ...

  • Trane WCY042G1 - page 18

    Page 18 ROUTINE MAINTENANCE BY OWNER You can do some of the periodic maintenance functions for your WCY-G unit yourself; this includes replacing the dispos- able or cleaning the permanent air filters, cleaning the unit cabinet, clearing the condenser coil, and conducting a general unit inspection on a regular basis. Be sure to inspect them at least ...

  • Trane WCY042G1 - page 19

    Page 19 LIMITED WARRANTY HIGH EFFICIENCY HEAT PUMP WCZ, WCY AND WCX Models Less Than 20 Tons for Residential Use* (Parts Only) This limited w ar ranty is extended by American Standard Inc., to the original purc haser and to any succeeding owner of the real proper ty to whic h the Heat P ump is originally af fixed, and applies to products purc hased ...

  • Trane WCY042G1 - page 20

    Page 20 Technical Literature - Printed in U.S.A. LIMITED WARRANTY HIGH EFFICIENCY HEAT PUMP WCZ, WCY, WCX, WCC, WCD, WCH, WCM AND WSC Models Less Than 20 Tons for Commercial Use* (Parts Only) This warr anty is extended by American Standard Inc., to the original purchaser and to any succeeding owner of the real proper ty to which the Heat Pump is or ...

メーカー Trane カテゴリー Heat Pump

Trane WCY042G1のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- WCY042G1の取扱説明書
- Traneの製品カード
- パンフレット
- またはTrane WCY042G1の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Trane WCY042G1の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Trane WCY042G1の取り付け説明書、サービスマニュアル、簡易説明書、またはTrane WCY042G1のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Trane WCY042G1の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Trane WCY042G1デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがTrane WCY042G1を使用するのを助ける技術的文書のことです。説明書は通常、全てのTrane WCY042G1ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Traneの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Trane WCY042G1の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははTrane WCY042G1の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Trane WCY042G1に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Trane WCY042G1デバイスの基本機能を使うにあたってのヒント。 Trane WCY042G1のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Trane WCY042G1に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるTrane WCY042G1のメーカー/サービスへの連絡先に関する情報。

Trane WCY042G1についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもTrane WCY042G1の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがTrane WCY042G1で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)