    WeatherMaker 8000™ 58ZAV Downflow/Horizontal Induced-Combustion Furnaces Installation, Start-Up, and Operating Instructions Sizes 050—135, Series 140 NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. Index Page SAFETY CONSIDERATIONS ............................... ...

  • Carrier 58ZAV - page 2

    ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will pre- vent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions w ...

  • Carrier 58ZAV - page 3

    INTRODUCTION The model 58ZAV Series 140 Furnaces are available in sizes 46,000 through 135,000 Btuh input capacities. The design of the downflow/horizontal gas-fired furnace is A.G.A./C.G.A. certified for natural and propane gases and for installation on noncombustible flooring. The furnace is factory- shipped for use with natural gas. A factory ac ...

  • Carrier 58ZAV - page 4

    Improper installation, adjustment, alteration, service, mainte- nance, or use can cause carbon monoxide poisoning, explo- sion, fire, electrical shock, or other conditions which may cause personal injury, loss of life, or property damage. Consult a qualified installer, service agency, local gas sup- plier, or your distributor or branch for informat ...

  • Carrier 58ZAV - page 5

    The operation of exhaust fans, kitchen ventilation fans, clothes dryers, or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST be provided for the ventilation devices, in addition to that required by the furnace. All fuel-burning equipment must be supplied with air for combus- tion of the fuel. Sufficient air MUS ...

  • Carrier 58ZAV - page 6

    Step 3—Supply Air Connections DOWNFLOW FURNACES Connect supply-air duct to supply-air opening on furnace. The supply-air duct attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used), when installed on non-combustible material. When installed on combus- tible material, supply-air duct attachment must ...

  • Carrier 58ZAV - page 7

    to attach any portion of return-air duct. Bypass humidifier connec- tions should be made at ductwork or coil casing sides exterior to furnace. Step 5—Downflow Installation NOTE: This furnace is approved for use on combustible materials or wood flooring. A factory accessory floor base, as listed on the furnace rating plate, MUST be used. A factory ...

  • Carrier 58ZAV - page 8

    Fig. 6—Furnace, Plenum, and Subbase Installed on a Combustible Floor A96285 DOWNFLOW SUBBASE SHEET METAL PLENUM FLOOR OPENING FURNACE (OR COIL CASING WHEN USED) COMBUSTIBLE FLOORING Fig. 7—Furnace, Plenum, and Coil Assembly or Coil Box Installed on a Combustible Floor A96284 CD5 OR CK5 COIL ASSEMBLY OR KCAKC COIL BOX ...

  • Carrier 58ZAV - page 9

    INSTALL FURNACE 1. Position furnace in desired location. 2. Connect gas supply pipe. See Fig. 8 for typical piping entry. 3. Install field-supplied filter retainers as indicated in Fig. 11 and Table 4 before connecting return-air duct to furnace. 4. Connect supply- and return-air ducts. 5. Install 24- X 24-in. sheet metal shield on platform in fron ...

  • Carrier 58ZAV - page 10

    Use the proper length of pipes to avoid stress on the gas control manifold. Failure to follow this warning could result in a gas leak, causing fire, explosion, personal injury, or death. Connect the gas pipe to the furnace using a backup wrench to avoid damaging gas controls. Never purge a line into a combustion chamber. Never use matches, candles, ...

  • Carrier 58ZAV - page 11

    Canadian installations, all electrical connections must be made in accordance with Canadian Electrical Code CSA C22.1, or authori- ties having jurisdiction. NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control status code indicator light will flash rapidly and furnace will not operate. The cabinet MUST have a ...

  • Carrier 58ZAV - page 12

    Fig. 15—Heating and Cooling Application Wiring Diagram A98521 115-V FIELD- SUPPLIED DISCONNECT AUXILIARY J-BOX 24-V TERMINAL BLOCK THREE-WIRE HEATING-ONLY FIVE WIRE NOTE 1 NOTE 2 FIELD-SUPPLIED DISCONNECT CONDENSING UNIT TWO WIRE FURNACE C O N T R O L R G C WC R GY GND GND FIELD 24-V WIRING FI ...

  • Carrier 58ZAV - page 13

    Step 12—Start-up, Adjustment, and Safety Check GENERAL NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control status indicator light will flash rapidly and furnace will not operate. The furnace must have a 115-v power supply properly connected and grounded. Proper polarity must be maintained for correct opera ...

  • Carrier 58ZAV - page 14

    Fig. 17—Furnace Wiring Diagram A98200e PCB BLOWER O FF DE LAY SELECTI O N CH ART 90 SEC 135 SEC 180 SEC 225 SEC GVR H I/L O RELAY SEC-1 SEC- 2 PL1 32 1 6 5 4 987 LED TEST/TW IN BLOWER OFF DELAY G R Y W C HUM HSIR IDR BLWR BLOWER SPEED SELECT FU1 COOL HEAT L2 PL3 PL2 VAC 120 L1 PR1 1 2 1 2 3 PR2 24 VAC-3A FUSE SPARE-2 SPARE-1 EAC-1 EAC-2 C 1. 5 ...

  • Carrier 58ZAV - page 15

    until the end of the ignition warm up and trial for ignition periods (a total of 24 sec). The blower then comes back on at heating speed. When the W input signal disappears, the control begins the normal inducer post-purge period and the blower changes to cooling speed after a 1-sec delay. If the W-Y-G signals disappear at the same time, the blower ...

  • Carrier 58ZAV - page 16

    → Table 7—Model 58ZAV Orifice Size† and Manifold Pressure for Correct Input (Tabulated Data Based on 23,000 BTUH Per Burner, Derated 4 Percent per 1000 Ft Above Sea Level)* ALTITUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0.64 0.66 Orifice No. Manifold Pressure Orifice No. Manifold ...

  • Carrier 58ZAV - page 17

    → Table 7—Model 58ZAV Orifice Size† and Manifold Pressure for Correct Input (Continued) (Tabulated Data Based on 23,000 BTUH Per Burner, Derated 4 percent per 1000 Ft Above Sea Level)* ALTITUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0.64 0.66 Orifice No. Manifold Pressure Orifice N ...

  • Carrier 58ZAV - page 18

    NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame characteristics. (3.) After correct manifold pressure is obtained, replace gas valve regulator adjustment ...

  • Carrier 58ZAV - page 19

    EXAMPLE: (0—2000 ft altitude) Btu heating input = Btu/cu ft X cu ft/hr Heating value of gas = 1050 Btu/cu ft Time for 1 revolution of 2-cu ft dial = 82 sec Gas rate = 88 cu ft/hr (from Table 9) Btu heating input = 88 X 1050 = 92,400 Btuh In this example, the orifice size and manifold pressure adjustment is within ± 2 percent of the furnace input ...

  • Carrier 58ZAV - page 20

    Recheck temperature rise. It must be within limits specified on unit rating plate. Recommended operation is at midpoint of rise or above. 3. Set thermostat heat anticipator. The thermostat heat anticipation must be set to match the amp draw of the electrical components in the R-W circuit. Accurate amp draw readings can be obtained at thermostat sub ...

メーカー Carrier カテゴリー Furnace

Carrier 58ZAVのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 58ZAVの取扱説明書
- Carrierの製品カード
- パンフレット
- またはCarrier 58ZAVの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Carrier 58ZAVの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Carrier 58ZAVの取り付け説明書、サービスマニュアル、簡易説明書、またはCarrier 58ZAVのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Carrier 58ZAVの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Carrier 58ZAVデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがCarrier 58ZAVを使用するのを助ける技術的文書のことです。説明書は通常、全てのCarrier 58ZAVユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Carrierの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Carrier 58ZAVの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははCarrier 58ZAVの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Carrier 58ZAVに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Carrier 58ZAVデバイスの基本機能を使うにあたってのヒント。 Carrier 58ZAVのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Carrier 58ZAVに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるCarrier 58ZAVのメーカー/サービスへの連絡先に関する情報。