    WARNING: If the information in these instructions is not followed exactly , a fire or explosion may result causing property damage, per- sonal injury or death. WARNING: Improper inst allation, adjustment, alter- ation, service, or maintenance can cause injury or property damage. Refer to this manual. For assist ance or additional infor- mation, con ...

  • Smith Cast Iron Boilers JW527 - page 2

    – 2 – T ABLE OF CONTENTS I) Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Consumer Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II) Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Smith Cast Iron Boilers JW527 - page 3

    Thank you for purchasing a John Wood Oil Fired W ater Heater . Properly installed and maintained, it will provide years of trouble free service. This Oil Fired W ater Heater has been developed to supply domestic hot water for normal residential demands. Any deviation from this application could affect your warranty . Consumer R esponsibilities This ...

  • Smith Cast Iron Boilers JW527 - page 4

    F or Installations in the United States: “St andard for the Installation of Oil-Burning Equipment (NFP A 31)” and “National Electrical Code (NFP A 70)” available from: American National S tandards Institute, 25 West 43rd S treet, New Y ork, NY 10036 Check your phone listings for the local authorities having jurisdiction over your installati ...

  • Smith Cast Iron Boilers JW527 - page 5

    THESE CONDITIONS CAN RESUL T IN UNSEEN INTER- NAL DAMAGE and are not subject to warranty coverage. This product contains fiberglass wool and ceramic fiber materials. Airborne fibers from these materials have been listed by the S tate of California as a possible cause of can- cer through inhalation. Use special care when handling ceramic fiber (cham ...

  • Smith Cast Iron Boilers JW527 - page 6

    In Earthquake Zones Note: The water heater must be braced, anchored, or strapped to avoid moving during an earthquake. Contact local utilities for code requirements in your area. Clearances and Accessibility The minimum clearances between the heater and com- bustible materials are listed in Figure 1. Note: These requirements are also listed on the ...

  • Smith Cast Iron Boilers JW527 - page 7

    – 7 – 600mm (24 in.) MIN. FOR SERVICING 457mm (18 in.) MIN. FLUE SEE T ABLE TOP SEE T ABLE FLUE SIZES SEE T ABLE NON-COMBUSTIBLE FLOOR COMBUSTIBLE CEILING DRAFT REGULA TOR FLUE SEE T ABLE Figure 1 Rough-In Dimensions NOTE: JWF307V requires additional “Through-the-wall V ent Kit” available in 3 lengths: 5’ (63320), 10’ (63321) or 20’ ( ...

  • Smith Cast Iron Boilers JW527 - page 8

    – 8 – Figure 2 Installation Dimensions (Center Flue Models) A D C B E F G H Figure 3 Installation Dimensions (Center/Rear Flue Models) JW 317/ J W 327 J W 517/ JW 527 J W 717/ J W 727 m m 610 711 813 i n . 2 42 83 2 m m 229 222 229 i n. 9 8 3/ 4 9 m m 508 508 495 i n. 20 20 19 1/ 2 m m 1264 1299 1359 i n. 49 3/ 4 51 1/ 8 53 1/ 2 m m 1492 1499 1 ...

  • Smith Cast Iron Boilers JW527 - page 9

    Air R equirements An adequate supply of combustion and ventilation air is required to: • Ensure proper combustion. • Reduce risk of property damage, severe bodily injury or death from possible flue gas leakage and carbon monox- ide emissions. Do not install an exhaust fan in the same room as the water heater . Satisfactory combustion cannot be ...

  • Smith Cast Iron Boilers JW527 - page 10

    appliances in the enclosure, freely communicating with inte- rior areas that have in turn adequate infiltration from the out- side. It shall also have a combustion air supply opening so that the total air received through the opening will be at least as much as would be admitted by openings having a total free area of 4.5 cm 2 /kWh (1 in 2 /5000 Bt ...

  • Smith Cast Iron Boilers JW527 - page 11

    Chimney Be sure that the chimney is sufficiently high and large enough to meet the specifications of the burner unit installed. Check that there is suf ficient draft for the proper burning of oil. At least -0.015 in. w .c. (-0.004kPa) of over-fire draft is recommended. Block ed V ent Safety Switc h Oil-fired water heaters must be fitted with the bl ...

  • Smith Cast Iron Boilers JW527 - page 12

    • Always use a proper grade of joint compound and be cer- tain that all fittings are drawn up tight. 1. Install the water piping and fittings as shown in Figures 7 or 8. Connect the cold water supply to the fitting (3/4” NPT) marked “COLD” (or “C”). Connect the hot water supply to the fitting (3/4” NPT) marked “HOT” (or “H”). ...

  • Smith Cast Iron Boilers JW527 - page 13

    DO NOT use any pumps, valves, or fittings that are not com- patible with pot able water . DO NOT use valves that may cause excessive restriction to water flow . Use full flow ball or gate valves only . DO NOT use any lead based solder in potable water lines. Use appropriate tin-antimony or other equivalent material. DO NOT tamper with the aquast at ...

  • Smith Cast Iron Boilers JW527 - page 14

    Installation Of T he Aquastat (T emper ature Control) This heater operates automatically under the control of the aquastat, which responds to the demand of hot water . Depending on the model, the aquastat well and wiring is either installed on the heater , or included in the carton con- taining the burner . If the installation of the aquastat is re ...

  • Smith Cast Iron Boilers JW527 - page 15

    – 15 – O I L VA LV E BURNER MOTOR IGNITOR LIMIT JUMPER CAD CELL T T F F WHITE BLACK 48245 BURNER JUNCTION BOX L2 NEUTRAL Figure 1 1 T ypical Primary Control Wiring (48245). BLOCKED VENT SAFETY SWITCH L1 HOT ORANGE GROUND JUNCTION BOX ...

  • Smith Cast Iron Boilers JW527 - page 16

    Installation Chec klist Star tup DO NOT A TTEMPT TO ST ART BURNER IF ANY OF THE FOLLOWING CONDITIONS EXIST : 1. Excess oil has accumulated. 2. The unit is full of vapours. NOTE: Refer to the instruction manual supplied with the burner for installation, st art up and adjustment. After the inst allation is finished and the installation checklist comp ...

  • Smith Cast Iron Boilers JW527 - page 17

    Wa ter Heater Operation Stacking S tacking occurs when a series of short draws of hot water (1 1 litres (3 US gallons) or less) are taken from the water heater tank. This causes increased cycling of the burner and can result in increased water temperatures at the hot water outlet. A tempering device is recommended in the hot water supply line to re ...

  • Smith Cast Iron Boilers JW527 - page 18

    Do not attempt to repair your water heater . Call a qualified Oil-Burner T echnician for service. T urn “OFF” the electric power whenever the water supply is shut off. Before calling for service, check that: 1. The heater is properly filled. 2. The electrical supply has not been interrupted. Professional Maintenance Except for external appearan ...

  • Smith Cast Iron Boilers JW527 - page 19

    Cleaning Instr uctions, Flue Passages Of T he JWF657 Heater Refer to Figure 13 for components of the heater . 1. Remove the casing top and lift the insulation of f com- pletely . It is necessary to disconnect the hot and cold water lines and move them out of the way . Do not remove the nipples from the t ank. 2. Lift of f the flue collector . The f ...

  • Smith Cast Iron Boilers JW527 - page 20

    This section serves as a guide for the installation and use of “Combo” heating systems utilizing a domestic water heater that has been specifically approved for such use. It is writ- ten for those knowledgeable in the required trades and pro- fessionals involved in the design and installation of Combo Heating Systems. It is the responsibility o ...

  • Smith Cast Iron Boilers JW527 - page 21

    Installation The heating mode may be one of the following options: 1. A fan coil/air handler (Figure 14). 2. A hydronic baseboard (finned tube) loop (Figure 15). 3. A hydronic in-floor heating loop (Figure 16). The following is a list of requirements for the inst allation of the heating loop to the water heater . 1. Install shut-of f valves and uni ...

  • Smith Cast Iron Boilers JW527 - page 22

    – 22 – T able 1 Listing Of Oil Burners. M odel M F GR B urner N oz z le & P ump P res s . B l as t t ube Not es B E CK E T T A FG GS W -J3037 0. 75 GP H U. S . O NLY B E CK E T T A FG GS W -J3036 0. 75 GP H M ASS. O N L Y CA RLI N E Z 197297A J W 317 0. 75 GP H CA RLI N 97297A JW 317 0.75 x 60A DE L 85472, 100 ps i 9" B E CK E T T A FG ...

  • Smith Cast Iron Boilers JW527 - page 23

    – 23 – M odel M F GR B urner N oz z le & P ump P res s . B l as t t ube Not es A E RO FA FC-2X 0. 75 GP H A E RO S V -2X 0. 75 GP H A E RO F A F C-2X 0. 75 x 80A 5 15/ 16" A E RO S V -2X 0. 75 x 80A 5 15/ 16" B E CK E T T A FG GS W -J5006 0. 75 GP H CA NA DA B E CK E T T A FG GS W -J5032 0. 75 GP H U. S . B E CK E T T A FG GS W -J ...

  • Smith Cast Iron Boilers JW527 - page 24

    – 24 – LIMITED W ARRANTY RESIDENTIAL ST ORAGE T ANK TYPE W A TER HEA TER FOR INST ALLA TION IN A SINGLE F AMIL Y DWELLING A. WHO IS COVERED. GSW W A TER HEA TING AND ITS SUPPLIERS, (herein collectively referred to as “Manufacturer”) warrants only to the original consumer purchaser (hereinafter “Owner”) of the water heater , within the b ...

  • Smith Cast Iron Boilers JW527 - page 25

    – 25 – d. The water heater or any of its component p arts are damaged or fails from operation with an empty or partially empty tank (such as, but not limited to element s burned out in a dry tank); or e. The water heater or any part has been under water; or f. The water heater is exposed to highly corrosive atmospheric conditions. No warranty e ...

  • Smith Cast Iron Boilers JW527 - page 26

    – 26 – This page intentionally lef t blank. May be used for notes or to record other installation information. ...

メーカー Smith Cast Iron Boilers カテゴリー Water Heater

Smith Cast Iron Boilers JW527のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- JW527の取扱説明書
- Smith Cast Iron Boilersの製品カード
- パンフレット
- またはSmith Cast Iron Boilers JW527の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Smith Cast Iron Boilers JW527の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Smith Cast Iron Boilers JW527の取り付け説明書、サービスマニュアル、簡易説明書、またはSmith Cast Iron Boilers JW527のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Smith Cast Iron Boilers JW527の製品を使用するにあたって最も人気のある説明書を閲覧できます。

Smith Cast Iron Boilers JW527デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがSmith Cast Iron Boilers JW527を使用するのを助ける技術的文書のことです。説明書は通常、全てのSmith Cast Iron Boilers JW527ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Smith Cast Iron Boilersの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Smith Cast Iron Boilers JW527の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははSmith Cast Iron Boilers JW527の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Smith Cast Iron Boilers JW527に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Smith Cast Iron Boilers JW527デバイスの基本機能を使うにあたってのヒント。 Smith Cast Iron Boilers JW527のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Smith Cast Iron Boilers JW527に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるSmith Cast Iron Boilers JW527のメーカー/サービスへの連絡先に関する情報。