    Contr ols Pr ogr amming Guide J anuary 2007 MU A -S VP0 1A -EN DFIA DFO A Dir ect-Fir ed Indoor and Outdoor Mak e-Up Air Units ...

  • Trane MUA-SVP01A-EN - page 2

    Ov erview © 20 05 American Standard Inc. All rights reserved MUA-SVP0 1A-EN A glossary has been pro vided to assist the reader in understanding distinctive terms and phrases. These terms an d phrases appear in italics. T rane's Digital Control S ystem, AdaptAir e, is designed to gi ve the user the ultimate in unit performance and operat ional ...

  • Trane MUA-SVP01A-EN - page 3

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 3 NET WORKING AdaptAire is adaptabl e to a variety of dif ferent netw ork ar c hitectures and protocols. Eac h controller has built-in pr otocol tran slat ion and ca n be config ured for operation on ARCnet1 56 or EIA-485 commun ication networks. See Appendix IV for specific controller speci ...

  • Trane MUA-SVP01A-EN - page 4

    4 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Low Input V a lue 0 -9999.99 – 99999.99 User Control Setpoint 0 -9999.99 – 99999.99 Maximum User Set point 0 -9999.99 – 99999.99 Minimum User Setpoint 0 -9999.99 – 99999.99 T able 1 . Def a ult set tings (continued) ITEM DEFAULT RANGE ...

  • Trane MUA-SVP01A-EN - page 5

    MUA-SVP 0 1A-EN 5 NETWORKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ADAPTAIRE DEFAULT SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Unit Oper ating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 ...

  • Trane MUA-SVP01A-EN - page 6

    6 MUA-S VP0 1A-EN Contents ALARM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HOTKEY - 1 45 RESETS HOTK EY - 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 SCHEDULES HOTKEY- 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Trane MUA-SVP01A-EN - page 7

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 7 There are three dif f erent modes th at control the supply fan and unit operation: •O f f •M a n u a l •A u t o There are also four dif ferent methods for controllin g the operating modes: • "a remote pan el with tw o rot ati ng knob adjustments ( MDT and MR T controls) • &q ...

  • Trane MUA-SVP01A-EN - page 8

    8 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Unit Operating Modes MR T Contr ols: MR T , modulating room temperature , is the most basic AdaptAire cont rol for room temperature. The MR T control system includes a remote cont rol panel equipped with 1 o r 2 potentiometers, 3 or more pilot lights, and up to 2 switc hes. UNIT OFF MODE ...

  • Trane MUA-SVP01A-EN - page 9

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 9 Unit Ope rating Mode s UNIT MANU AL MODE Manual Mode allows the unit to turn on reg ardless of the T ime Cloc k or Night Setba c k functions. A BACview o r PC is required to c hange to this mode. S ee the section related to the MR T Expert for instruct ions on how to use th e BA Cview f or ...

  • Trane MUA-SVP01A-EN - page 10

    10 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Unit Operating Modes to be "of f" and the Cooling Night S etbac k f unction turns the unit "on", the unit will be cycled "of f" once the room air temperatu re has fallen 2° below the Cooling Night S et bac k setpoint. The default for this setpoint is 1 0 0 ...

  • Trane MUA-SVP01A-EN - page 11

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 11 Unit Ope rating Mode s for up to 4 separate On/Of f events w ith any combination of days. The normal sc hedule sets the typical On/Off times for the unit. The holiday sc hedule can be programmed for up to 1 2 separate On/Of f events with an y combination of days. The holiday sc hedule set ...

  • Trane MUA-SVP01A-EN - page 12

    12 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Unit Operating Modes function is activated whenever a contact is closed between the appr opriate terminals on the unit's terminal strip lo cated in the unit's main control panel. Heating and cooling functions use the Ni ght Setbac k Setpoint s. See the T ypical Wiring Sc hemat ...

  • Trane MUA-SVP01A-EN - page 13

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 13 Unit Ope rating Mode s Se tpo int. The allow able temperature ran ge is 55°F - 130°F . This se ts the highest disc harge air temperatur e that will leave the uni t. If the maximum and minimum disc harge temperature setpoints are set for the same temperat ure , the su pp l y air te mpera ...

  • Trane MUA-SVP01A-EN - page 14

    14 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Unit Operating Modes with internal he at ga in. In cer tain condit ions it may be necessary to readjust t he minimum disc harge air or room temperature setpo int upward or adjust th e outside/return air ratio to provid e a w armer supply air temperature. Ener gy Sa vings Mode 1— Non-R ...

  • Trane MUA-SVP01A-EN - page 15

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 15 Unit Ope rating Mode s line downw ard. If the room temperature fa lls to a tem perature that is 2°F below the heating setpoint, the he ating will be enabled, and the unit will be in the heating mode. Continue following the so lid line in a cloc kwise direction to the heating setpoint . O ...

  • Trane MUA-SVP01A-EN - page 16

    16 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Unit Operating Modes T o c hange the desired cooling room temperat ure of an MRT -Pro con trol system, depress the W armer but ton to increase the desired room temperature setp oint or depress the Cooler but ton to decrease the desired room temperature setpoint. Eac h push of a button c ...

  • Trane MUA-SVP01A-EN - page 17

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 17 Unit Ope rating Mode s operating in the heating mode, the unit wi ll automatically keep the minimum outside air at 20%. If the outside air drop s below 20%, t he burner will cy cle of f. See Minimum V entilation. MRT -Pro Contr ols. T o c hange the damper mode on an MR T -Pro control syst ...

  • Trane MUA-SVP01A-EN - page 18

    18 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Unit Operating Modes Building Pr essur e Mode The Building P ressure mode varies the pe rcentages of outsi de air and return air to maintain a constant pressu re with in the space. A pr essure transducer compares the pressure outside the space to the pressure inside the space and transm ...

  • Trane MUA-SVP01A-EN - page 19

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 19 1 0 0% Outside Air The 1 0 0% Outside Air function automatically opens the outside air dampers and closes the return ai r damper s. This functi on i s activated whenever a contact is closed between the appr opriat e terminals on the unit's termin al strip located in the unit's m ...

  • Trane MUA-SVP01A-EN - page 20

    20 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Functions User Configur ed PID Control This function is applicable to non-recirc ulating un its only . The User Configured PID Control function allows the user to control an analog output based on a user defined analog input and setpoint. S ee th e T ypical Wiring and Unit Controller Sp ...

  • Trane MUA-SVP01A-EN - page 21

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 21 Functions to the Max Use r setpoint. In this situat ion the out put value is the great er of the PID output or the over ride output. If the input variable is below the User Control se tpoint, the output could decrease from 1 0 0% to 0% as the input variable decreases f r om the User Contr ...

  • Trane MUA-SVP01A-EN - page 22

    22 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Functions REVERSE A CTING The controller outp ut AO-1 is modulated by a PID loop fro m 0% to 1 0 0% based on the User Control setpoint a nd the input signal to IN -9. As the input signa l increases the output voltage decreases. A dditionally , a secondary control acts to over ride the P ...

  • Trane MUA-SVP01A-EN - page 23

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 23 Functions pressure to be +0.03" but does not want it t o drop below 0.0" or g o above +0.05". The parameters entered on the keypad display will be: The pressure transducer comp ares the pressure outside the space t o the pressure inside t he space and transmits a cor respon ...

  • Trane MUA-SVP01A-EN - page 24

    24 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Functions Unit Resets This section should assist the user in reset ting alarms and cycle counters whic h have been display ed on the BACview . ALARM. T o reset an alarm scroll through the menu tree, locate the Unit Rese ts branc h and select Al arm. Pr ess the Enter key . The word OFF s ...

  • Trane MUA-SVP01A-EN - page 25

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 25 Functions input. A switc h is used in conjunction with eac h resistor . When a switc h is closed, the resistance at the cont roller input c hanges. This allows the controller to identify whic h switc h has closed. The controlle r is programmed to associate e ac h dif ferent resistance wit ...

  • Trane MUA-SVP01A-EN - page 26

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 26 Cr itical F ault Codes This section should assist the user in tr oubleshooting critical fault codes messages that h ave been display ed on the local user interface. These faults require the operator to cor rect the conditi on and reset the alarm before normal unit operat io n r esu m es. ...

  • Trane MUA-SVP01A-EN - page 27

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 27 Diagnostics valve closest to t he burner and measure the disc harge air temperature. Is it less than 130°F? – Y es. There is a problem wit h the contr olle r pro gram or cont rolle r itse lf . Contact the fact o ry . – No. The outside air temper ature is too hot to determine the actu ...

  • Trane MUA-SVP01A-EN - page 28

    28 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Diagnostics SOLUTION: If bur ner was not oper ating pr ior to shutdo wn (chec k pr ior alar m log) 1 . Is there a prior al arm suc h as Safety Ckt. , Airflow Sw ., or Flame F ailure? – Ye s . S ee the Diagnostic secti on for the previous alarm. – No. Continue. 2. Is the room air (R ...

  • Trane MUA-SVP01A-EN - page 29

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 29 Diagnostics – Ye s . This signal is fed to the signal c onditioner . Disconnect the w ires from the signal conditioner's input signal te r minals and measure the v oltage on the wires. Is i t the same as the voltage coming from the controlle r? – No. There is an open in the wirin ...

  • Trane MUA-SVP01A-EN - page 30

    30 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Diagnostics – No. See t he Diagnostic section for Unit On/F an Off . – Ye s . Continue. SOLUTION:If f a n is run ning (chec k pr ior alar m log) 1 . Is the high temperature limit trip ped? – Ye s . Determine cause and rectify . – No. Continue. 2. Is the low gas pressure swit c h ...

  • Trane MUA-SVP01A-EN - page 31

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 31 Diagnostics – No. Continue. 2. Is the burner enable re lay energize d? – No. There is an open in the 24 V AC circuit. Dete rmine cause and rectify . – Ye s . Continue. 3. Is the burner enable relay's normally open cont act closed? – No. R eplace relay . – Ye s . Continue. 4 ...

  • Trane MUA-SVP01A-EN - page 32

    32 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Diagnostics 2. Are the main automatic gas shut off valv es energized ? – No. The main automatic g as shutof f valves are leaki ng. T urn of f unit and close manual g as valves. Deter mine cause of valve fail ure and rectify . – Ye s . Continue. 3. Is the flame re la y energized? – ...

  • Trane MUA-SVP01A-EN - page 33

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 33 Diagnostics F A UL T CODE: Unit of f/F an on PROBLEM: The contro ller ha s not activated the unit enable outp ut t o star t the fan, but the fan status input, is receiving a signal that the fan is running. This f ault will automatically clear a bout 15 se conds af ter the fault is cor rec ...

  • Trane MUA-SVP01A-EN - page 34

    34 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Diagnostics – Ye s . T he r e is a sh ort in the wiri ng be tw e en th es e terminals. De te rm ine cause and rectify . – No. R eplace controller . F A UL T CODE:Unit on/F an off PROBLEM:The controller has activated the unit enable outpu t to star t the fan, but the fan status input ...

  • Trane MUA-SVP01A-EN - page 35

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 35 Diagnostics – Ye s . Continue. 3. Is the unit enab le relay energi zed? – No. There is an open in the wiring be tween these te rminals. Determin e cause and rectify . – Ye s . Continue. 4. Is the unit enable r elay's normally open contact, closed? – No. R eplace relay . – Y ...

  • Trane MUA-SVP01A-EN - page 36

    36 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Diagnostics SOLUTION:If low airflo w switch is opening. Do not adjust the switc h setpoints 1 . Does low airflow sw itc h open when the burner is off – No. Disconnect both pressure sensin g tubes from one of the airflow switc hes and measure the dif ferential pressure by connectin g t ...

  • Trane MUA-SVP01A-EN - page 37

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 37 Diagnostics – Ye s . Clear and continue. – No. Continue. 3. Is the airflow switc h setpoint properly adjusted? – No. Adjust setpoint. – Ye s . Continue. 4. Are the wires connected to the air pressure switc h's normally open contact? – No. R ewire switc h and continu e. – ...

  • Trane MUA-SVP01A-EN - page 38

    38 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Diagnostics – No. Continue. SOLUTION:If setpoints ar e not misadjust ed 1 . Is there a prior al arm suc h as Insuff icient O A? – Ye s . See the Diagnostic sect ion for the previous alarm. – No. Continue. 2. Is the disc harge air temperature (D A T emp), displayed on the BA Cview ...

  • Trane MUA-SVP01A-EN - page 39

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 39 Diagnostics equal to the %O A setpoint. However , at 20% O A the damper s should be at least ½" open. – Ye s . Continue. – No. Chec k the damper motor and linkage connections. When 24V AC is powering the damper actuator and th e control sign al is 0VDC, the outside air damper sh ...

  • Trane MUA-SVP01A-EN - page 40

    40 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Diagnostics SOLUTION: If O A T , RoomT or D A T are suc h that heat is req uired 1 . Is the outside air temperature (O A T emp), display ed on the BA Cv iew remote, reading 1 50°F or more? – Ye s . The outside air sensor circuit or the sensor itself is shorted. Unplug the input jac k ...

  • Trane MUA-SVP01A-EN - page 41

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 41 Diagnostics 4. Do the damper s trac k with a c hange in the %O A setpoint? The dampers utilize d on the unit are not linear with respect to a irflow and openness, and a s suc h, the proportion of outside air damper movement will not be exactly equal to the %O A setpoint. However , at 20% ...

  • Trane MUA-SVP01A-EN - page 42

    42 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Diagnostics – Ye s . The AdaptAire control sy stem must be in the Hea ting mode. In this mode the smallest allow able amount of outside air is 20%. V erify the system is in the Heat ing mode and the MIN VEN T SP is set for 20%. S ee Heating/Cooling Mode and Minimum V e ntilation Secti ...

  • Trane MUA-SVP01A-EN - page 43

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 43 Menu Selection T r ee for BA Cview This section will assist the user in na vig ating the menu functions of the control program. F or conve nience Hotkeys are provided to al low the user to jump directly to a specific menu heading. Simply press and hold the FN key . While holding the FN ke ...

  • Trane MUA-SVP01A-EN - page 44

    44 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Menu Selection Status Alarm SET POINTS HO TKEY - 3 Htg Occupied °F range 55-90 Htg Setback °F range 40-80 Htg Min DA °F range 40-130 Htg Max DA °F range 55-130 Clg Occupied °F r ange 61-96 Clg Setback °F r ange 75-130 Clg Min DA °F r ange 40-130 Clg Max DA °F r ange 55-130 Man V ...

  • Trane MUA-SVP01A-EN - page 45

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 45 Menu Selection S T A TUS MENU HO TKEY - 4 Note: Th e Status Me nu alw ays displays the cur rent status of the fan, burner an d cooling. ALARM HO TKEY - 1 Alar m History (64 Most Recent) • Active Critical Alarms • Active Non-Critical Alarms • Alarms Return-T o-Normal •P r e v i o u ...

  • Trane MUA-SVP01A-EN - page 46

    46 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Menu Selection Home Sc hedules Cloc k Set Help SCHEDULES HO TKEY - 7 Dail y – Sc hedule1 (typical 1 through 4) –U s e — y e s / n o – Star t Time — hr:min – Stop Time— hr:min – D A YS — SUN, MON, TUE, WED, THU, FRI, SA T – Previous – Next –H o m e – Logout Holi ...

  • Trane MUA-SVP01A-EN - page 47

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 47 Menu Selection Low Output V alue User Control S etpoint Maximum User Setpoint Minimum User Setpoint Prev io u s Home Setpoints Help CL OCKSET HO TKEY - 0 Tim e hh:mm:ss Date dd-mm-yy Prev io u s DST – Enable No/Y es – S ou Hem No/Y es – 06Beg Apr /02 – 06End Oct /2 9 – 07Beg Apr ...

  • Trane MUA-SVP01A-EN - page 48

    48 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Menu Selection Alarm Fu el S elect FUEL SELECT HO TKEY - 9 Fue l T y p e Na tural Gas/Propane Login Home Prev io u s Unit Modes ...

  • Trane MUA-SVP01A-EN - page 49

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 49 1 0 K Ohms Ther mistor Output Curv e Ther mostat Output Curve Figure 5. Uses F G.figure# Figure 6. Uses F G.figure# T ypi cal 10, 000 O hm T herm i st or O utput Curve 0 10000 20000 30000 40000 50000 60000 70000 80000 90000 100000 110000 120000 130000 140000 150000 160000 170000 180000 - ...

  • Trane MUA-SVP01A-EN - page 50

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 50 Airflo w Station La y o ut Figure 7 . Airflo w station layout ...

  • Trane MUA-SVP01A-EN - page 51

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 51 POWE R REQUIREMENTS. 24V AC ± 1 0%, 20V A NETW ORK COMMUNICA TION BACnet (n ative), Modbus R TU , or N2 bus at up to 7 6.8K baud or 156K baud o ver ARCnet. LonW orks using plug-in communications board. USER INTERF ACE MDT : modulating disc harge temperature control with manually adjusted ...

  • Trane MUA-SVP01A-EN - page 52

    52 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN I/O Zone 583 Controller Specifications – LED indication • 3 Analog Outputs –0 - 1 0 V D C OUTPUT A SSIGNMENTS - ANAL OG AO1 Burner firing ra te (to signal conditioner) 0 - 1 0 VDC AO2 RA or Mixing Damper Cont rol/ User Configured 0 - 1 0VDC AO 3 Unassigned OUTPUT A SSIGNMENTS - DI ...

  • Trane MUA-SVP01A-EN - page 53

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 53 T ypical Wir ing Schematic Figur e 8. Non-r ecir c ulating with ev ap DFO A and DFIA model diagram ...

  • Trane MUA-SVP01A-EN - page 54

    54 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Typical Wiring Schema tic Figur e 9. Non-r ecir c ulating with ev ap DFO A and DFIA model diagram ...

  • Trane MUA-SVP01A-EN - page 55

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 55 Typical Wiring Schematic Figur e 1 0. Recirculating DFO A and DFIA model diagrams ...

  • Trane MUA-SVP01A-EN - page 56

    56 Direct-F ired Indoor an d Outdoor Units • MUA-SV P0 1A-EN Typical Wiring Schema tic Figur e 1 1 . Recir culating DFO A and DFIA model diagr am ...

  • Trane MUA-SVP01A-EN - page 57

    MUA-SVP0 1A-EN • Direct-Fired Indoo r and Outdoor Units 57 Typical Wiring Schematic ...

  • Trane MUA-SVP01A-EN - page 58

    Tr a n e A business of American Standard Companies www .trane.com For more information, contact your loc al T ran e office or e-mail us at comfort@trane.com Literature Order Number MUA-SVP0 1A-EN Date J anu ary 20 07 Super sedes New T rane has a policy of continuous product and pro duct data improvement and reserve s the right to c hange design and ...

メーカー Trane カテゴリー Wheelchair

Trane MUA-SVP01A-ENのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- MUA-SVP01A-ENの取扱説明書
- Traneの製品カード
- パンフレット
- またはTrane MUA-SVP01A-ENの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Trane MUA-SVP01A-ENの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Trane MUA-SVP01A-ENの取り付け説明書、サービスマニュアル、簡易説明書、またはTrane MUA-SVP01A-ENのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Trane MUA-SVP01A-ENの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Trane MUA-SVP01A-ENデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがTrane MUA-SVP01A-ENを使用するのを助ける技術的文書のことです。説明書は通常、全てのTrane MUA-SVP01A-ENユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Traneの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Trane MUA-SVP01A-ENの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははTrane MUA-SVP01A-ENの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Trane MUA-SVP01A-ENに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Trane MUA-SVP01A-ENデバイスの基本機能を使うにあたってのヒント。 Trane MUA-SVP01A-ENのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Trane MUA-SVP01A-ENに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるTrane MUA-SVP01A-ENのメーカー/サービスへの連絡先に関する情報。

Trane MUA-SVP01A-ENについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもTrane MUA-SVP01A-ENの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがTrane MUA-SVP01A-ENで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)