    A/23 MFFI - A/27 MFFI G.C .N. 47-116-10 / 47-116-12 Installation Instructions T ype C Boilers LEA VE THESE INSTRUCTIONS ADJA CENT TO THE GAS METER Countr y of destination: GB ...

  • Ariston 47-116-10 - page 2

    2 B023 T ABLE OF CONTENTS 1. GENERAL INFORMA TION 1.1 General Instructions 1.2 T echnical Information 1.3 Ov erall View 2. INST ALLA TION 2.1 Ref erence Standards 2.2 Siting the Appliance 2.3 Ov erall Dimensions 2.4 Clearances 2.5 Mounting the Appliance 2.6 Electrical Connection 2.7 Gas Connection 2.8 W ater Connections 2.9 Flue Connection 2.10 Roo ...

  • Ariston 47-116-10 - page 3

    3 B023 This manual is an integr al and essential par t of the product. It should be kept with the appliance so that it can be consulted by the user and our authorised personnel. Please carefully read the instructions and notices about the unit contained in this manual, as the y provide impor tant information regarding the saf e installation, use an ...

  • Ariston 47-116-10 - page 4

    CE Cer tification Heat Input max/min kW 25.6/11.0 Heat Output max/min kW 23.1/9.2 Efficiency of Nominal Heat Input % 90.2 Efficiency at 30% of Nominal Heat Input % 87.8 Heat Loss to the Casing (³T=50°C) % 1.2 Flue Heat Loss with Burner Operating % 8.6 Flue Heat Loss with Burner Off % 0.4 Maximum Discharge of Fumes (G20-G25) Kg/h 59 Residual Disch ...

  • Ariston 47-116-10 - page 5

    5 B023 A/23 MFFI - A/27 MFFI Legend: 1. Flue Connector 2. Combustion Chamber Hood 3. Main Heat Exchanger 4. Combustion Chamber Insulation P anel 5. Burner 6. Expansion V essel 7. Ov erheat Ther mostat 8. Spark Generator 9. Diverter V alv e 10. Main Circuit T emperature Probe 11. Main Circuit Flo w Switch 12. Div er ter V alv e Microswitch 13. Filte ...

  • Ariston 47-116-10 - page 6

    6 B023 The technical inf or mation and instructions provided herein below are intended f or the installer so that the unit may be installed correctly and saf ely . The installation and initial star t up of the boiler m ust be by a CORGI Approv ed Installer in compliance with the installation standards currently in eff ect, as well as with any and a ...

  • Ariston 47-116-10 - page 7

    7 B023 Legend: A = Central Heating Flow (3/4”) B = Domestic Hot W ater Outlet (1/2”) C = Gas Inlet (3/4”) D = Domestic Cold W ater Inlet (1/2”) E = Central Heating Return (3/4”) 2.3 Overall Dimensions 890 365 (A-B-D-E) (C) 465 In order to allow f or access to the interior of the boiler for maintenance purposes, the boiler must be installe ...

  • Ariston 47-116-10 - page 8

    8 B023 F asten the boiler in place using the template and anchors supplied with the unit. It is highly recommended that a spirit lev el be used to position the boiler so that it is perf ectly lev el. F or additional information, please consult the instructions contained in the connection kit and the flue kit. F or safety purposes, hav e a competent ...

  • Ariston 47-116-10 - page 9

    9 B023 2.9 W ater Connections Legend A = Central Heating Flow B = Domestic Hot W ater Outlet C = Gas Inlet D = Domestic Cold W ater Inlet E = Central Heating Return I = Saf ety V alve Central Heating Detailed recommendations are given in BS 6798:1987 and BS 5449-1:1990, the f ollowing notes are giv en for gener al guidance. Pipe W or k: Copper tubi ...

  • Ariston 47-116-10 - page 10

    10 B023 public access . Air Release P oints: These must be fitted at all high points where air naturally collects and m ust be sited to f acilitate complete filling of the system. The appliance has an integral sealed e xpansion v essel to accommodate the increase of water v alue when the system is heated. It can accept up to 7 l (1.5 gal) of e xpan ...

  • Ariston 47-116-10 - page 11

    TERMINAL POSITION mm A - Directly below an open windo w or other opening 300 B - Below gutters , solid pipes or drain pipes 75 C - Below ea ves 200 D - Below balconies or car-port roof 200 E - F rom vertical drain pipes and soil pipes 75 F - F rom internal or external cor ners 300 G - Abov e ground or below balcon y lev el 300 H - F rom a surf ace ...

  • Ariston 47-116-10 - page 12

    12 B023 This procedure must be done as f ollows: 1 - Remov e the air vent intak e you w ant to use, in the area indicated in Fig. 2.8, b y breaking the perfor ated r ing. 2 - Use a tool to gr asp the lid and remov e it completely . 3 - Clean any b urrs or shar p edges with a knif e or an appropr iate tool. In Fig. 2.10 below , se veral diff erent t ...

  • Ariston 47-116-10 - page 13

    13 B023 In calculating the lengths of the pipes, the maximum length m ust also take into consideration the v alues for the e xhaust/air intak e end ter minals, as well as 90° elbows f or coaxial systems. The C52 types must comply with the f ollowing requirements: 1. The discharge/intak e v ent pipes must hav e the same diameter of ø 80 mm. 2. The ...

  • Ariston 47-116-10 - page 14

    14 B023 5 Remov e the grommet “D” shown in photo 5, mak e a hole in it and pass the room ther mostat wire through. 6 Remov e the link located on the ter minal and connect the wire. 7 Replace the grommet and the terminal to their or iginal positions, close the cov er on the grommet compar tment and f asten the wire-clamp “C” in place. 8 If a ...

  • Ariston 47-116-10 - page 15

    15 B023 2.11 Electrical Diagram Legend: A T = High V oltage P .C .B. BT = Low V oltage P .C .B. B = Flame F ailure L.E.D . C = Insufficient W ater Pressure L.E.D . D = W ater T emperature Indicator L.E.D .s E = Overheat Thermostat Warning L.E.D . F = System Reset Button G = Selector Knob f or Operating Mode H = Domestic Hot W ater T emp . Adjustmen ...

  • Ariston 47-116-10 - page 16

    16 B023 A/23 MFFI - A/27 MFFI EX C-MI/FFI 8 A/23 MFFI - A/27 MFFI ...

  • Ariston 47-116-10 - page 17

    2.12 W ater Cir cuit Diagram 17 B023 A/23 MFFI - A/27 MFFI Legend 1. Air Pressure Switch 2. F an 3. Main Heat Exchanger 4. Main Burner 5. Ignition Electrodes Detection Electrode 6. Gas V alv e 7. Ov erheat Ther mostat 8. Main Circuit T emperature Probe 9. Div er ter V alv e 10. Main Circuit Flo w Switch including Saf ety Pressure Switch for Primar ...

  • Ariston 47-116-10 - page 18

    40 50 60 70 80 C C 3.3 Contr ol P anel A - Ignition Loc kout Reset Button/Saf ety (Overheat)Thermostat Reset B - Ignition Loc kout L.E.D . C - Selector Knob for Summer/Winter/Flue Analysis Modes* D - Low System W ater Le vel L.E.D . E - T emperature Adjustment Knob f or Domestic Hot W ater F - Heating System Thermometer G - Saf ety (Ov erheat)Ther ...

  • Ariston 47-116-10 - page 19

    19 B023 3.4 Initial Start-up The chec ks to be run before initial start-up are as follows: 1. Make sure that: - the screw on the automatic air v alve has been loosened when the system is full; - If the water pressure in the system is below 1 bar , br ing it up to the appro- priate lev el; - Check to see whether the gas cock is closed; - Make sure t ...

  • Ariston 47-116-10 - page 20

    20 B023 The boiler is designed to make it easy to analyse the comb ustion by-products . Using the especially designed aper tures, readings can be tak en on the temperature of the comb ustion by-products and of the comb ustion air , as well as of the concentrations of O 2 and CO 2 , etc. The best maximum-pow er test conditions for the heating system ...

  • Ariston 47-116-10 - page 21

    21 B023 off status. After the system has been allowed to cool, the system can be reset by pressing the b utton “A”. 4 - Limescale Build-up This is an indirect control (actuated through the regulation of the temperature in the primar y heat exchanger) on the f ormation of limescale in the secondar y heat e xchanger . Regardless of the flow r ate ...

  • Ariston 47-116-10 - page 22

    22 B023 4.1 Changing the T ype of Gas The boiler can be con verted to use either methane (natural) gas (G20) or LPG (G30 - G31) by an A uthorised Service Centre. The operations that must be perf ormed are the follo wing: 1. Replace the jets on the main burner (see table in section 4); 2. Adjust the maximum and minimum thermal capacity values f or t ...

  • Ariston 47-116-10 - page 23

    6. MISCELLANEOUS 6.1 Wiring Diagram f or T wo Heating Zones V4043H VA LV E BRO WN 8 BLUE 2 GREY 9 ORANGE 10 GREEN/YELLO W 3 Honeywell ST 699B 1002 63 N L Link L-5-8 ST 6400/ST 6300 ST 6200 3 4 N L Drayton T empus 7 3 4 N L Horstmann 425, 525, 527 14 E N L Link L-2-5 Landis & Gyr RWB2 34 N L Glowworm Mastermind Landis & Gyr RWB20 34 N L Micr ...

  • Ariston 47-116-10 - page 24

    24 B023 6.2 Wiring Diagram f or Connection to Ariston Un vented Cylinder V4043H VA LV E BRO WN 8 BLUE 2 GREY 9 ORANGE 10 GREEN/YELLO W 3 Honeywell ST 699B 1002 63 N L Link L-5-8 ST 6400/ST 6300 ST 6200 3 4 N L Drayton T empus 7 3 4 N L Horstmann 425, 525, 527 14 E N L Link L-2-5 Landis & Gyr RWB2 34 N L Glowworm Mastermind Landis & Gyr RWB2 ...

  • Ariston 47-116-10 - page 25

    NO TES 25 B023 ...

  • Ariston 47-116-10 - page 26

    26 B023 NO TES ...

  • Ariston 47-116-10 - page 27

    27 B023 ...

  • Ariston 47-116-10 - page 28

    Manuf acturer : Merloni T ermoSanitari SpA - Italy Commercial subsidiar y: MTS (GB) LIMITED MTS Building Hughenden A ven ue, High Wycombe Bucks HP13 5FT T elephone: (01494) 755600 - F ax: (01494) 459775 T echnical Service Hotline: (01494) 539579 Cod. 23 99 84 1260 112 - B023 ST AMP A: Azienda Grafica BIEFFE srl - Recanati ...

メーカー Ariston カテゴリー Boiler

Ariston 47-116-10のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 47-116-10の取扱説明書
- Aristonの製品カード
- パンフレット
- またはAriston 47-116-10の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Ariston 47-116-10の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Ariston 47-116-10の取り付け説明書、サービスマニュアル、簡易説明書、またはAriston 47-116-10のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Ariston 47-116-10の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Ariston 47-116-10デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがAriston 47-116-10を使用するのを助ける技術的文書のことです。説明書は通常、全てのAriston 47-116-10ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Aristonの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Ariston 47-116-10の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははAriston 47-116-10の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Ariston 47-116-10に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Ariston 47-116-10デバイスの基本機能を使うにあたってのヒント。 Ariston 47-116-10のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Ariston 47-116-10に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるAriston 47-116-10のメーカー/サービスへの連絡先に関する情報。

Ariston 47-116-10についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもAriston 47-116-10の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがAriston 47-116-10で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)