    GENERA C POWER SYSTEMS, INC. R R Installation and Owner’ s Man ual Air -cooled A utomatic Standb y Generators Models: 04758-0 (6 kW NG, 7 kW LP) 04759-0 (12 kW NG, 12 kW LP) 04760-0 (13 kW NG, 15 kW LP) DEADL Y EXHAUST FUMES. OUTDOOR INST ALLA TION ONL Y!! D ANGER Not intended f or use as Primary P o wer in place of utility or in life-support app ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 2

    I NTRODUCTION Thank you for purchasing this model by Generac P ower Systems Inc.. This model is a compact, high performance, air - cooled, engine - driven generator designed to automatically supply electrical power to operate critical loads during a utility power failure. This unit is factory installed in an all-weather , metal enclo- sure that is ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 3

    T able of Cont ents Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators 1 Introduction ........................Inside F ront Cover Read This Manual Thoroughly ........................IFC Contents ..........................................................IFC Operation and Maintenance ............................IFC How to Obtain Service ........ ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 4

    2 Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely , efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rule ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 5

    3 ELE CTR ICAL HA Z AR DS • All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in opera- tion. A void contact with bare wires, terminals, con- nections, etc., w ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 6

    Only qualified electricians or contractors should attempt such installations, which must comply strictly with applicable codes, standards and regulations. 1.1 U N P ACKING/I NSP ECTION After unpacking, carefully inspect the contents for damage. • This standby generator set has been factory sup- plied with a weather protective enclosure that is in ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 7

    Section 1 — General Information Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators 5 1.4 Y OU R GEN ER A T OR Control P anel Battery Compartment Fuel Regulator Air Filter Exhaust Enclosure Oil Filter Data Decal Control Panel Air Filter Exhaust Enclosure Battery Compartment Fuel Regulator Oil Filter Oil Dipstick Data Decal Figure 1.2 – 12 k ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 8

    6 Section 1 — General Information Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators 1.5 SP E CI F ICA TIONS 1.5.1 GEN ERA T OR Model 04758 Model 04759 Mo de l 04760 Rated Max. Continuous P ower Capacity (W atts*) 6,000 NG/7,000 LP 12,000 NG/12,000 LP 13,000 NG/15,000 LP† Rated V oltage 120/240 120/240 120/240 Rated Max. Continuous Load Cu ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 9

    7 1 . 6 FUE L RE QUIRE MEN T S AN D R E C OM M EN D A TIONS W ith LP gas, use only the vapor withdrawal system. This type of system uses the vapors formed above the liquid fuel in the storage tank. The engine has been fitted with a fuel carburetion system that meets the specifications of the 1997 California Air Resources Board for tamper -proof dua ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 10

    3. Remove the small hose clamp and hose from the fuel regulator . It may be necessary to pry the hose off of the brass fitting using a screw driver to gen- tly lift up the hose edge. 4. Remove the brass hose fitting screwed into the fuel regulator . 5. Locate and identify the brass idle jet. This will be located in the fuel regulator casting facing ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 11

    9 1.1 0 B A TTER Y INST ALLA TION Fill the battery with the proper electrolyte fluid if nec- essary and have the battery fully charged before installing it. Before installing and connecting the battery , complete the following steps: 1. Set the generator's Auto/Off/Manual switch to OFF . 2. T urn off utility power supply to the transfer switch ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 12

    10 The following procedur es are to be observed: • Wear full eye pr otection and protective clothing; • Where electr olyte contacts the skin, wash it of f immediately with water; • Where electr olyte contacts the eyes, immediately flush thoroughly with water and seek medical attention; and • Spilled electrolyte is to be washed down with an ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 13

    11 8. Connect an accurate AC voltmeter and a frequen- cy meter across transfer switch terminal lugs E1 and E2. V oltage should be 242-252 volts; fre- quency should read about 61-63 Hertz. 9. Connect the AC voltmeter test leads across termi- nal lug E1 and neutral; then across E2 and neu- tral. In both cases, voltage reading should be 121- 126 volts ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 14

    12 2.6 ADJ US TI NG TH E R E GU L A T OR (NA TUR AL GAS ONL Y) Although the generator has been factory set to pro- vide maximum power , it may be necessary in some areas to adjust this setting . Because natural gas has different BTU or power content across the country the engine may not perform as designed. If you experience engine problems at high ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 15

    13 Section 3 — Operation Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators Figure 2.3 — Engine Governor Adjustment 2.7 .2 1 2 KW AND 15 KW UN IT S 1. Loosen governor clamp bolt (See Figure 2.3). 2. Completely remove the idle spring . 3. W ith governor arm at wide open throttle position, rotate governor shaft fully clockwise. Tighten clamp ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 16

    14 Section 3 — Operation Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators 8. T urn ON the utility power supply to the transfer switch, which will allow the transfer switch to transfer back to utility power . The unit will con- tinue to run for one minute and then shut down. 9. Allow the unit to cool. 10. Drain the oil and remove the oil fi ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 17

    15 D . Utility V oltage Pickup Sensor • This sensor monitors utility power supply volt- age. When that voltage is restored to above 70 percent of the nominal source voltage, a retrans- fer time delay starts timing . E. Retransfer Time Delay • This timer runs for about 15 seconds. • At end of a 15- second delay , circuit board action de - ener ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 18

    16 3.6 SE T TI NG TH E EXERCISE TI M ER Y our generator is equipped with an exercise timer . Once it is set, the generator will start and exercise once every seven days, on the day of the week and at the time of day you complete the following sequence. During this exercise period, the unit runs for approx- imately 12 minutes and then shuts down. Tr ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 19

    17 4.1 F USE The generator panel’s 15 amp fuse (Figure 4.1) protects the DC control circuit against overload. The fuse is wired in series with the battery output lead to the panel. If the fuse element has melted open, you cannot crank or start the engine. Y ou should replace the fuse using only an identical 15-amp replacement. The generator panel ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 20

    18 4.3.2 OI L CHANGE PROCEDU R E T o change the oil, proceed as follows: 1. Run the engine until it is thoroughly warmed up then shut OFF the engine. 2. Immediately after the engine shuts OFF , pull the oil drain hose (Figure 4.4) free of its retaining clip. Remove the cap from the hose and drain the oil into a suitable container . Figure 4.4 – O ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 21

    19 4.6 SP AR K P L UG(S) Reset the spark plug(s) gap or replace the spark plug(s) as necessary . See Section 4.13 (P age 22) for maintenance requirements. 1. Clean the area around the base of the spark plug(s) to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and commercial solvent. Do not blast the spark pl ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 22

    20 4.8 ADJ US TI NG V AL VE CLEAR ANCE After the first 50 hours of operation, you should adjust the valve clearance in the engine. Important: If you feel uncomfortable about doing this procedure or you don't have the proper tools, please contact your Generac Authorized dealer for service assistance. This is a very important step to insure long ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 23

    21 4.1 0 A TTENTION AF TER S U B M ERSION If the generator has been submerged in water , it MUST NOT be started and operated. F ollowing any sub- mersion in water , have a Generac Authorized Dealer thor- oughly clean and dry the generator . 4.1 1 C OR ROSION P RO TECTION P eriodically wash and wax the enclosure using automo- tive type products. F r ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 24

    22 Section 4 — Maintenance Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators 4.1 3 SERVICE S CH EDU LE A TTENTION: It is recommended that all service work be performed by your nearest Generac Authorized Dealer . SYSTEM/COMPONENT PROCEDURE FREQUENCY X = Action Inspect Change Clean W = W eekly R = Replace as Necessary M = Monthly * = Notify D ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 25

    23 Section 5 — T roubleshooting Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators 5.1 TROU B LE SHOO TI NG GUI DE P ROB LEM CAUSE C OR R E CTION The engine will not crank. 1. F use blown 1. Replace 15A fuse on generator control panel. 2. Loose, corroded or defective 2. Tighten, clean or replace battery cables as necessary . 3. Defective sta ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 26

    24 Section 6 — Electrical Data Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators Wiring Diagram – 1 2 & 15 kW – Drawing No. 0D85 00-B TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA ( DUAL SEC. ) 0 CUS T O MER SU PPLIE D BLA CK BATTERY 12V L OP HT O 0 S P 2 S P 1 IM2 86 85 IM1 D D DIA G RAM KE Y D S W - P C B M OU NTED DIP S WIT CH ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 27

    25 Section 6 — Electrical Data Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators Wiring Diagram – 1 2 & 15 kW – Drawing No. 0D85 00-B C L OS E S T T O BEARIN G G R D 0 4 S TAT OR 1 94 224 224 22 5 1 5 224 17 4 22 5 224B 22 5 0 0 OU TP U T T O TRAN S FE R 22 22 MAN U A L F2 0 1 5A 66A 2 39 1 3 1 5 1 3 1 3 0 F1 1 5 17 17 V O LTA GE RE ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 28

    26 Section 6 — Electrical Data Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators Electrical Schematic – 1 2 & 1 5 kW – Drawing No. 0D85 0 1 -B IM1 - IGNITION MODULE , CYLINDER # 1 IM2 - IGNITION MODULE , CYLINDER # 2 L O P - L O W O IL PRE SSU RE S WIT CH SP1 , SP2 - SPARK PLUG S S W1 - A U T O / O FF / MAN U AL S WIT CH S W2 - S ET ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 29

    27 Section 6 — Electrical Data Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators Electrical Schematic – 1 2 & 1 5 kW – Drawing No. 0D85 0 1 -B 2 39 IM2 1 5 1 8 S P 2 24 0V IM1 0 1 94 17 1 5 2 3 1 5 2 39 S W 1 1 94 1 5A 22 11 2 3 11 22 11 S P 1 44 WINDIN G 12 0V 12 0V 33 NEUTRAL N2 N1 2 3 CUS T O ME R CO NNE C TI O N S 1 94 0 0 SC F ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 30

    TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA ( DUAL SEC. ) CB2 - CIRCUIT BREAKER , ALTERNATOR EXCITATIO N BLA CK CUS T O MER SU PPLIE D BATTERY 12V L OP HT O SP 86 85 IM D D S W - P C B M OU NTED DIP S WIT CH C B1 - MAIN OU TP U T BREAKE R BA - BR US H A SS EMBL Y B C R - BATTERY C HAR G E RELA Y D - DI O D E SC - S TARTER CO NTA C T OR I C T - ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 31

    29 0 4 C L OS E S T T O BEARI N G R D S TAT OR OU TP U T T O TRAN S FE R 24 0 V G ENERAT OR S WIT C H CO NTA C T OR 8 2 0 66A 1 94 1 5 0 66A 1 5A 2 39 2 3 1 5 1 5A F2 1 3A 1 3 0 1 3 F1 1 3 351 14 N2 0 22 4 22 5 0 351 1 3 224 4 0 22 5 14 N2 N1 1 3A N1 V O LTA GE RE GU LAT OR 0 66A 0 1 62 2 2 0 4 6 11 4 4 11 2 2 4 MAN U A L A U T O 1 7 1 5 S W 1 2 39 ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 32

    CB1 - CIRCUIT BREAKER , MAIN OUTPU T HT O - HI G H O IL TEMPERAT U RE S WIT CH S W1 - A U T O / O FF / MAN U AL S WIT CH CB2 - CIRCUIT BREAKER , ALT. EXCITATIO N TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA ( DUAL SEC. ) B C R - BATTERY C HAR G E RELA Y BA - BR US H A SS EMBL Y F1 - F US E 1 5 AM P F2 - F US E 5 AM P S P - S PARK PL UG F S - F ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 33

    31 INP UT 12V dc U TILIT Y CO I L RELAY TRAN S FE R NE U TRA L 120 V 24 0 VA C CUS T O ME R SU PPLIE D 2 3 S W 1 2 39 C 1- 6 0 1 5 17 0 1 8 C 1- 5 0 1 8 0 17 56 1 8 14 1 5A 17 0 1 5 0 C 1- 1 56 2 39 1 3 1 5 SC 14 1 5A 1 94 2 3 1 5 IM 0 D BLA CK SP P O WE R WINDIN G ( STATOR ) F S 14 C 1- 2 1 94 22 RED SC SM 24 0V 44 11 C B 1 33 12 0V C 2- 5 N2 22 5 ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 34

    32 ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 35

    33 ITEM P ART NO .QTY . DESCRIPTION 1 0C6140 1 ASSEMBL Y , ENCLOSURE BASE 0D1901 1 ASSEMBL Y , ENCLOSURE BASE (7KW) 2 0C6735 2 SUPPORT , ROOF FOLDING 3 0C7061 1 ENCLOSURE, FRONT 4 0C7062 1 ENCLOSURE, EXHA UST SIDE 0C7062A 1 ENCLOSURE, EXHAUST SIDE (7KW) 5 0C7063 1 ENCLOSURE, SIDE & BA CK 0C7063A 1 ENCLOSURE, SIDE & BACK (7KW) 6 0C7064 1 ENC ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 36

    34 46 22 37 7 38 83 2 8, 9 27 44 47 0 13 19 14 15 35 15 17 49 14 15 5 3 4 16 23 36 39 38 45 48 2 28 29 17 16 4 6 7 23 27 42 12 45 44 20 40 11 1 43 35 14 30 3 41 24 45 47 3 1 47 45 31 3 13 ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 37

    35 ITEM P ART NO . QTY . DESCRIPTION 1 0A9947E 1 CIRCUIT BREAKER 30 X 2 240V SQD QOU230 (7KW) 0A9947G 1 CIRCUIT BREAKER 40 X 2 240V SQD QOU240 (8.5KW) 0A9947F 1 CIRCUIT BREAKER 50 X 2 240V SQD QOU250 (12KW) 0A9947C 1 CIRCUIT BREAKER 60 X 2 240V SQD QOU260 (13KW) 0A9947D 1 CIRCUIT BREAKER 70 X 2 240V SQD QOU260 (15KW) 2 0A1801 1 ASSEMBL Y , BA TTER ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 38

    36 17 15 18 22 13 12 9 7 8 24 3 27 32 19 6 5 65 6 4 63 6 2 6 1 60 59 58 5 2 51 50 49 48 47 46 45 44 43 57 1 42 38 3 7 36 35 3 4 33 3 40 2 3 26 10 4 34 25 11 30 20 66 2, 5 , 19 , 20 , 39 , 40 , 47 , 64 , 93 , 14 0 8, 11 , 12 , 13 6 7 4, 5 , 6 68 1 6A , 16B , 17 , 18 69 7, 47 , 48 , 49 , 50 , 51 , 52 , 53 , 54 , 56 , 57 , 58 , 59 , 60 , 63 , 64 70 4 ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 39

    37 ITEM P ART NO . QTY . DESCRIPTION 1 0C5729 1 ASSEMBL Y , CRANKCASE HOUSING WITH SLEEVE 2 0C3008 1 SEAL, 38 I.D . CRANKSHAFT 3 090388 8 SCREW , T APTITE M6-1.0 X 12 YC 4 0C5372 1 ASSEMBL Y , BREA THER 5 0C3005 1 GASKET , BREA THER CO VER 6 0E3372B 1 SEP ARA TOR, OIL BREA THER 7 0D8067A 1 ASSEMBL Y , HEAD #1 G&S 8 071983 4 RET AINER, PISTON PI ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 40

    38 ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 41

    39 ITEM P ART NO . QTY . DESCRIPTION 74 0C5136A 2 KNOB, AIR CLEANER 75 0C3024 1 CO VER, AIRBO X NG/LP 76 0C3040 1 PRE-CLEANER, 77 0C8127 1 ELEMENT , AIR CLEANER 78 0D8564A 1 ASSEMBL Y , MIXER/AIRBO X 990 0D8564B 1 ASSEMBL Y , MIXER/AIRBO X 760 79 0D2595 4 SCREW SHOULDER (8MM) M6-1.0 X 18 80 0D4417 4 W ASHER,R UBBER 1/4" X 1/8" THICK 81 0C ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 42

    40 3 7 6 51 7 8 21 53 9 3 2 1 4 5 23 11 3 1 3 1 12 5 22 14 20 38 15 3 0 24 26 32 10 19 16 28 27 17 10 1 28 3 1 3 2 17 3 2 3 1 33 28 13 39 18 4 0 28 3 4 35 3 4 44 48 30 45 46 3 4 36 47 5 2 Section 7 — Exploded Views and P arts Lists Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators 7 kW Generator – Drawing No. 0D35 04-C ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 43

    41 Section 7 — Exploded Views and P arts Lists Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators 7 kW Generator – Drawing No. 0D35 04-C ITEM P ART NO . QTY . DESCRIPTION 1 0C6934 1 AD APT OR, ENGINE 2 0C9935H 1 ST A TOR 3 0C9934H 1 RO TOR 4 0C6043A 1 CARRIER, REAR BEARING 5 0C8096 1 F AN, 8" CUR VED BLADE 6 0C9593 1 MUFFLER 7 0D3220 ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 44

    42 29 3 4 11 2 5 24 43 21 7 13 33 12 38 17 3 2 3 1 28 3 1 20 19 10 17 15 32 16 22 39 8 6 37 14 3 2 40 32 24 25 10 30 19 26 28 27 28 3 2 3 1 41 10 18 36 35 29 41 42 ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 45

    43 Section 7 — Exploded Views and P arts Lists Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators 1 2 kW and 1 5 kW Generator – Drawing No. 0D3 4 1 7-E ITEM P ART NO . QTY . DESCRIPTION 1 0C6934 1 AD APT OR, ENGINE 2 0C7930 1 ST A TOR 12KW 0D2359 ST A T OR 13KW / 15KW 3 0C7944 1 RO TOR 12KW 0D2356 R O T OR 13KW / 15KW 4 0C6043 1 CARRIER, R ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 46

    44 11 47 33 3 4 36 35 3 7 27 45 43 39 18 19 20 23 3 2 44 48 2 4 46 11 22 29 28 3 1 30 17 5 2 1 14 13 26 38 25 25 40 41 12 16 6 1 2 4 42 10 5 7 3 8 9 4 9 5 1 50 5 4 ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 47

    45 ITEM P ART NO . QTY . DESCRIPTION 1 071978 1 ASSEMBL Y , CONNECTING ROD 2 071980 1 PIN, PIST ON D20 3 021533 1 SET , PIST ON RING 90MM 4 0C5848 1 PIST ON, HC 5 071983 2 RET AINER, PIST ON PIN 20 6 0D4287 1 ASSEMBL Y , CRANKSHAFT GH410 SMALL T APER 7 0A7628 1 ARM, GO VERNOR RC45 8 078658 1 PIN, "R" GO VERNOR ARM 9 078659 2 W ASHER, GO V ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 48

    46 ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 49

    47 ITEM P ART NO . QTY . DESCRIPTION 1 0C1069 5 SCREW , T APTITE M6-1.0X8 YELLO W CHROME 2 0D2922 1 HOUSING, BLO WER 3 0C8435 1 TUBE, DIPSTICK 4 0C9997 1 GU ARD , F AN 5 088434 1 WRAPPER, BO TT OM 6 045756 11 SCREW , T APTITE M6-1X10 YELLO W CHROME 7 088433B 1 WRAPPER, T OP 8 0D9004A 1 ASSY , ST AR TER 9 059985 2 SCREW , SHC M8-1.25 X 45 G12.9 10 0 ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 50

    1 2 5 4 ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 51

    49 ITEM P ART NO . QTY . DESCRIPTION 1 0D5694 1 CASTING, TWIN REGULA T OR HOUSING 2 0C5765 1 SOLENOID , TWIN REGULA T OR 3 0C4647 1 GASKET , SOLENOID 4 0C4680 1 PLUNGER, LP REGULA T OR ASSEMBL Y 5 0C6070 1 SPRING-SOLENOID , PLUNGER 6 022985 4 W ASHER, FLA T #6 7 022264 4 W ASHER, LOCK M4 8 075475 4 SCREW PPHM M4-0.7 X 10 9 0C5760A 1 JET , GN 410 EN ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 52

    50 Section 8 — Mounting Dimensions Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators Drawing No. 0D3 7 3 9-B T M6PEM-T M6P M6PEM PE REAR VIEW L EFT S IDE VIEW TRANSFER SWITCH R I G HT S IDE VIE W F R O NT VIEW AIR NTAKE ( IF SUPPLIED ) " D O N O T LIFT BY THE R OO F" L IFTIN G H O LE S 4- CO RNER S Ø 3 0.2mm [ Ø 1 .19" ] R ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 53

    51 Section 9 — Notes Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 54

    52 Section 1 0 – W arranty Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators NOTE: This Emission Control W arranty Statement pertains to this product only IF the generator size is 15 kW or below . CALIFORNIA AND FEDERAL EMISSION CONTR OL W ARRANTY ST A TEMENT Y OUR W ARRANTY RIGHTS AND OBLIGA TIONS The California Air Resources Board (CARB) ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 55

    53 Section 1 0 – W arranty Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators EMISSION CONTROL SYSTEM W ARRANTY Emission Control System Warranty (ECS W arranty) for 1997 and later model year engines: (a) Applicability: This warranty shall apply to 1997 and later model year engines. The ECS Warranty Period shall begin on the date the new engi ...

  • Generac Power Systems 04758-0, 04759-0, 04760-0 - page 56

    Part No. 0E1370 Revision F (09/16/03) Printed in U.S.A. Section 1 0 – W arranty Guardian Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators GEN ERAC PO WER SY STEMS S T AN D AR D "T WO YEAR" LIM ITED W ARR ANT Y FOR GU AR DIAN “EM ERGENCY AUT OMA TIC S T AN DBY GENER A T ORS” F or a period of two years from the date of original sale, Ge ...

メーカー Generac Power Systems カテゴリー Portable Generator

Generac Power Systems 04758-0, 04759-0, 04760-0のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 04758-0, 04759-0, 04760-0の取扱説明書
- Generac Power Systemsの製品カード
- パンフレット
- またはGenerac Power Systems 04758-0, 04759-0, 04760-0の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Generac Power Systems 04758-0, 04759-0, 04760-0の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Generac Power Systems 04758-0, 04759-0, 04760-0の取り付け説明書、サービスマニュアル、簡易説明書、またはGenerac Power Systems 04758-0, 04759-0, 04760-0のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Generac Power Systems 04758-0, 04759-0, 04760-0の製品を使用するにあたって最も人気のある説明書を閲覧できます。

Generac Power Systems 04758-0, 04759-0, 04760-0デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがGenerac Power Systems 04758-0, 04759-0, 04760-0を使用するのを助ける技術的文書のことです。説明書は通常、全てのGenerac Power Systems 04758-0, 04759-0, 04760-0ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Generac Power Systemsの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Generac Power Systems 04758-0, 04759-0, 04760-0の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははGenerac Power Systems 04758-0, 04759-0, 04760-0の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Generac Power Systems 04758-0, 04759-0, 04760-0に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Generac Power Systems 04758-0, 04759-0, 04760-0デバイスの基本機能を使うにあたってのヒント。 Generac Power Systems 04758-0, 04759-0, 04760-0のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Generac Power Systems 04758-0, 04759-0, 04760-0に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるGenerac Power Systems 04758-0, 04759-0, 04760-0のメーカー/サービスへの連絡先に関する情報。

Generac Power Systems 04758-0, 04759-0, 04760-0についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもGenerac Power Systems 04758-0, 04759-0, 04760-0の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがGenerac Power Systems 04758-0, 04759-0, 04760-0で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)