    Constant Pr essur e W ater System S ub D rive 300 Installation Manual ...

  • Franklin 5870206300 - page 2

    2 Contents Description and Features ................................................................................ 4 Included Items .................................................................................................. 5 How It W orks ..................................................................................................... ...

  • Franklin 5870206300 - page 3

    3 T able 1: SubDrive Models Model Name Part Number Use with Motor Series SubDrive300 5870206300 (NEMA 4) 234 317 xxxx (5.0 Hp) ...

  • Franklin 5870206300 - page 4

    4 Description and Featur es The Franklin Electric SubDrive300 is a dependable residential and light commercial water system contr oller that uses advanced electronics to enhance the performance of standard submersible pumps. When used with the speci fi ed Franklin Electric motor (see T able 1), the SubDrive eliminates pressur e cycling associated ...

  • Franklin 5870206300 - page 5

    5 Included Items A. Controller Unit B. Strain Relief Fittings C. Pressur e Shut-off Sensor and Boot D. Pr essure Sensor and Boot Franklin Ele ctri c is n ow o f fer ing an int rod uct ory warran ty exte nsion on S ubDriv e 75, Sub Driv e 150 and M onoDr ive. The ex ten ded war ran ty i s f ree, bu t the Su bDriv e/M ono - Driv e must be registered ...

  • Franklin 5870206300 - page 6

    6 How It W orks The Franklin Electric SubDrive300 is designed to be part of a system that consists of only four components: A. Standard Pump and Franklin Electric Motor . B. SubDrive Controller . C. Small Pressur e T ank (for tank size, see T able 3). D. Franklin Electric Pressure Sensor (pr ovided). E. Franklin Electric Pressur e Shut-Off Sensor ( ...

  • Franklin 5870206300 - page 7

    7 Motor Soft Start Normally , when there is a demand for water , the SubDrive300 will be operating to accurately maintain system pressur e. Whenever the SubDrive300 detects that water is being used, the controller always “ramps up” the motor speed while gradually increasing voltage, r esulting in a cooler motor and lower start-up current compar ...

  • Franklin 5870206300 - page 8

    8 Pump Sizing The SubDrive300 is con fi gur ed at the factory for use with 3 Hp pumps that are mounted to 5 Hp Franklin Electric thr ee-phase motors. In general, the SubDrive300 will enhance the performance of a 3 Hp pump to a similar or better performance than a conventional 5 Hp pump of the same fl owrating (pump series). T o select the proper ...

  • Franklin 5870206300 - page 9

    9 Underload Sensitivity for Shallow W ells The SubDrive300 controller is con fi gured at the factory to ensur e detection of Underload faults in a wide variety of pumping applications. In rare cases (as with certain pumps in shallow wells) this trip level may result in nuisance faults. If the pump is installed in a shallow well, activate the contr ...

  • Franklin 5870206300 - page 10

    10 ▲ WARNING ! Serious or fatal electrical shock may result fr om failure to connect the ground terminal to the motor , SubDrive controller , metal plumbing, or other metal near the motor or cable, using wire no smaller than motor cable wir es. T o minimize risk of electrical shock, disconnect power before working on or around the SubDrive300 sys ...

  • Franklin 5870206300 - page 11

    11 Contr oller Location Selection The SubDrive controller is intended for operation in ambient temperatur es up to 125°F (51°C) at 230 V AC input. The following r ecommendations will help in selection of the proper location of the SubDrive unit: 1. A tank tee is recommended for mounting the tank, pr essure sensor , pressur e gauge, and pressur e ...

  • Franklin 5870206300 - page 12

    12 4. For indoor or outdoor installations. 5. The SubDrive300 should only be mounted with the wiring end oriented downward. The contr oller should not be placed in direct sunlight or other locations subject to direct rain or snow . 6. The mounting location should have access to 230 V AC electrical supply and to the submersible motor wiring. T o avo ...

  • Franklin 5870206300 - page 13

    13 Cir cuit Breaker and Wir e Sizing The minimum circuit br eaker size and maximum allowable wire lengths for connection of motor to the SubDrive300 are given in the following table: A 10-foot section of cable is provided with the SubDrive300 to connect the pressur e sensors. NOTE: • Maximum allowable wire lengths ar e measured between the contro ...

  • Franklin 5870206300 - page 14

    14 Pow er Supply Fr om Circuit Breaker* Quick Refer ence Guid e P/N 587 020 6300 P u Fr a El e M o PRESSURE SENSOR SHUT-OFF INT FAN INV FAN PFC FAN NO NO COM RELAY SW2 SW1 O N Congur a 1 OFF ON Outp u From P ower Sourc e L1 L2 (Input) * Note : T o avoid possible interference with other appliances, please refer to the enclosed installation guide ...

  • Franklin 5870206300 - page 15

    15 e SubDrive300 (not to scale) T ank Precharge Ination Valve Pressur e Gauge Pressur e Sensor T o Residence Pressure S witch Set Point (PSI) 25 30 35 40 45 55 60 65 70 75 80 Pressure T ank Pre-Charge (PSI) 18 21 25 28 32 35 39 42 46 49 53 56 Pressur e Setting Guide 50 (F actory set) Pressur e Relief V alve Discharge into drain rated for max pum ...

  • Franklin 5870206300 - page 16

    16 Pr essure T ank The SubDrive needs only a small pressur e tank to maintain constant pressur e (see table below for recommended tank size). For pumps rated 12 gpm or more, a slightly lar ger tank is r ecommended for optimum pressur e regulation. The SubDrive can also use an existing tank with a much lar ger capacity . T able 3: Minimum Pressur e ...

  • Franklin 5870206300 - page 17

    17 Installation Pr ocedure 1. Disconnect electrical power at the main breaker . 2. Drain the system (if applicable). 3. Install the pressur e sensor and pressur e shut-off sensor at the pressur e tank tee downstream of the pr essure tank (the pr essure tank should be between the pressur e sensor and the pump). The sensors have a ¼-18 National Pipe ...

  • Franklin 5870206300 - page 18

    18 Wiring Connections 1. V erify that the power has been shut off at the main breaker . 2. V erify that the dedicated branch circuit for the SubDrive300 is equipped with a properly-sized cir cuit breaker . Refer to T able 2 (Page 13) for minimum breaker size. 3. Use the appropriate strain r elief or conduit connectors. T ype B liquid tight fi ttin ...

  • Franklin 5870206300 - page 19

    19 6. Feed the 230 V AC power leads thr ough the bottom left side of the SubDrive300 controller and connect them to the terminals marked L1, L2, and GND (Figure 3). A 10-foot section of pr essure sensor cable is pr ovided with the controller , but it is possible to use similar 22 AWG wire for distances up to 100 feet from the pr essure sensor . A 1 ...

  • Franklin 5870206300 - page 20

    20 10A. Connect the other end of the pressure sensor cable with the two spade terminals to the pressur e sensor . The connections are interchangeable (Figur e 4A). 10B. Connect the other end of the pr essure sensor cable with the two ¼" quick connect terminals to the pressur e shut-off sensor . The connections are inter changeable (Figure 4B) ...

  • Franklin 5870206300 - page 21

    21 Start-Up and Operation Apply power to the controller . A steady green light indicates that the SubDrive300 has power but the pump is not running. The green light will fl ash continuously when the pump is running. Leaky Systems Leaky water systems might keep the controller running due to the accurate pressur e sensing capability of the pressur e ...

  • Franklin 5870206300 - page 22

    22 NOTES: (A) Operating temperature is speci fi ed at full output power when installed as described in Controller Location Selection on Page 11. (B) Refer to Page 23 for detailed mounting dimensions. (C) If a pump other than the default rating is used, refer to Page 8 for drive con fi guration. Input from Power Source (single-phase) V oltage 190- ...

  • Franklin 5870206300 - page 23

    23 Mounting Dimensions 14.75” 12.00” 15.34” 8.75” 4.75” ...

  • Franklin 5870206300 - page 24

    24 Diagnostic Fault Codes Should an application or system problem occur , built-in diagnostics will protect the system. The r ed “F AUL T” light on the front of the SubDrive300 controller will fl ash a given number of times to indicate the nature of the fault. In some cases, the system will shut itself off until corr ective action has been tak ...

  • Franklin 5870206300 - page 25

    25 System T roubleshooting Guide Symptom Possible Cause Corrective Action W ater fl ow rate is not as high as expected. Motor is running backwards. V erify motor connections. See Figure 2 in the “Wiring Connections” section. T emperature in the controller is too high. If the controller’ s heat exchanger becomes too hot, the controller will r ...

  • Franklin 5870206300 - page 26

    26 Underload Smart Reset If a motor Underload fault condition occurs, the most likely cause is an overpumped or dry well. T o allow the well to recover , the SubDrive300 controller will wait 30 seconds to 5 minutes, determined by duration of the previous run time, befor e restarting the motor . For example, the fi rst time the fault occurs, the co ...

  • Franklin 5870206300 - page 27

    TOLL-FREE HELP FROM A FRIEND Franklin Electric Submersible Service Hotline 800-348-2420 ...

  • Franklin 5870206300 - page 28

    400 E. Spring Street Bluffton, IN 46714 Tel: 260-824-2900 Fax: 260-824-2909 www.franklin-electric.com M1491 11.05 225286101 Rev. 1 ...

メーカー Franklin カテゴリー Water Pump

Franklin 5870206300のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 5870206300の取扱説明書
- Franklinの製品カード
- パンフレット
- またはFranklin 5870206300の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Franklin 5870206300の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Franklin 5870206300の取り付け説明書、サービスマニュアル、簡易説明書、またはFranklin 5870206300のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Franklin 5870206300の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Franklin 5870206300デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがFranklin 5870206300を使用するのを助ける技術的文書のことです。説明書は通常、全てのFranklin 5870206300ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Franklinの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Franklin 5870206300の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははFranklin 5870206300の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Franklin 5870206300に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Franklin 5870206300デバイスの基本機能を使うにあたってのヒント。 Franklin 5870206300のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Franklin 5870206300に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるFranklin 5870206300のメーカー/サービスへの連絡先に関する情報。

Franklin 5870206300についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもFranklin 5870206300の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがFranklin 5870206300で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)