    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S www .rosemount.com Section 3 Configuration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Device Cap abilities . . . . . . . . . . . . . . . . ...

  • Emerson 3051S - page 2

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-2 DEVICE CAP ABILITIES Link Active Scheduler The Rosemount 3051S can be designated to act as the backup Link Active Scheduler (LAS) in the event that the LAS is disconnected from the segment. As the backup LAS, the 3051S will take over the management of communications until the h ...

  • Emerson 3051S - page 3

    Reference Manual 00809-0200-4801, Rev BA April 2007 3-3 Rosemount 3051S GENERAL BLOCK INFORMATION Modes The Resource, T ransducer , and all functi on blocks in the device have modes of operation. These modes govern the o peration of the block. Every block supports both automatic (AUT O) and out of service (OOS) modes. Other modes may also be suppor ...

  • Emerson 3051S - page 4

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-4 Block Inst antiation The Rosemount 3051S supports the us e of Function Block Instantiation. When a device supports block inst antiati on, the number of blocks and block types can be defined to match specific application needs.The number of blocks that can be instantiated is onl ...

  • Emerson 3051S - page 5

    Reference Manual 00809-0200-4801, Rev BA April 2007 3-5 Rosemount 3051S SOFT W LOCK and HARD W LOCK Inputs to the security and write lock f unctions include the hardware security switch, the hardware and software write lock bit s of the FEA TURE_SEL parameter , the WRITE_LOCK parame ter , and the DEFINE_WRITE_LOCK para me te r . The WRITE_LOCK para ...

  • Emerson 3051S - page 6

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-6 PlantWeb ™ Alarms The alarms and recommended actions s hould be used in conjunction with Section 2: T roubleshooting. The Resource Block will act as a coordinator for PlantWeb alarms. There will be three alarm parameters (F AILED_ALARM, MAINT_ALARM, and ADVISE_ALARM) which wi ...

  • Emerson 3051S - page 7

    Reference Manual 00809-0200-4801, Rev BA April 2007 3-7 Rosemount 3051S MAINT_ALARMS A maintenance alarm indicates the device or some part of the device needs maintenance soon. If the condition is ignored, the device will eventually fail. There are five parameters associ ated with MAINT_ALARMS, they are described below . MAINT_ENABLED The MAINT_ENA ...

  • Emerson 3051S - page 8

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-8 1. Process Anomaly Detected (SPM) 2. LOI Failure 3. PW A Simulate Active 4. Defer NV Memory Write Detected 5. Mass Flow T ransducer Block Reverse Flow 6. Mass Flow T ransducer Block Sensor Out of Range 7. Mass Flow T ransducer Block Out of Range 8. Process Anomaly Detected (SPM ...

  • Emerson 3051S - page 9

    Reference Manual 00809-0200-4801, Rev BA April 2007 3-9 Rosemount 3051S CHANNEL Select the channel that corresponds to the desired sensor measurement. The 3051S measures both pressure (channel 1) and sensor temperature (channel 2). NOTE Channel 3 and channels 12-19 are on ly available when the Advanced Diagnostic Block is licensed. Channels 5- 9 ar ...

  • Emerson 3051S - page 10

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-10 XD_SCALE and OUT_SCALE The XD_SCALE and OUT_SCALE each include three parameters: 0%, 100%, and, engineering units. Set these based on the L_TYPE: L_TYPE is Direct When the desired output is the measured variable, set the XD_SCALE to the “Primary_V alue_Range”. This is f ou ...

  • Emerson 3051S - page 11

    Reference Manual 00809-0200-4801, Rev BA April 2007 3-1 1 Rosemount 3051S Configuration Examples Pressure transmitter Situation #1 A pressure transmitter with a range of 0 – 100 psi. Solution T able 3-2 lists the appropriate configuration settings. T able 3-2. Analog Input function block configuration for a typical pressure transmitter . . Pressu ...

  • Emerson 3051S - page 12

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-12 Solution to Situation #2 T able 3-3 lists the appropriate configuration settings. T able 3-3. Analog Input function block configuration for a pressure transmitter used in level measurement (situation #1). Output calculation for Situation #2 When the L_T ype is configured as In ...

  • Emerson 3051S - page 13

    Reference Manual 00809-0200-4801, Rev BA April 2007 3-13 Rosemount 3051S Solution to situation #3 T able 3-4 lists the appropriate configuration settings. T able 3-4. Analog Input function block configuration for a pressure transmitter used in level measurement (Situation #3). In this example, when the PV is 4 ps i, OUT will be calculated as follow ...

  • Emerson 3051S - page 14

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-14 Filtering The filtering feature changes the resp onse time of the device to smooth variations in output readings caused by rapid changes in input. Adjust the filter time constant (in seconds) using the PV_FTIME parameter . Set the filter time constant to zero to disable the fi ...

  • Emerson 3051S - page 15

    Reference Manual 00809-0200-4801, Rev BA April 2007 3-15 Rosemount 3051S Process Alarms Process Alarm detection is based on the OUT value. Configure the alarm limits of the following st andard alarms: • High (HI_LIM) • High high (HI_HI_LIM) • Low (LO_LIM) • Low low (LO_LO_LIM) In order to avoid alarm chattering when the variable is oscillat ...

  • Emerson 3051S - page 16

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-16 Advanced Features The AI Function Block provides added capability through the addition of the following parameters: ALARM_TYPE ALARM_TYPE allows one or more of the process alarm conditions detected by the AI function block to be used in setting its OUT_D p arameter . OUT_D OUT ...

  • Emerson 3051S - page 17

    Reference Manual 00809-0200-4801, Rev BA April 2007 3-17 Rosemount 3051S T able 3-6. Block Error Conditions Modes The MAI Function Block supports three modes of operation as defined by the MODE_BLK parameter: Manual (Man) The block output ( OUT ) may be set manually Automatic (Auto) OUT_1 to OUT_8 reflects the analog input measurement or the simula ...

  • Emerson 3051S - page 18

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-18 LCD T RANSDUCER BLOCK The LCD meter connects directly to the 3051S electronics F OUNDATION fieldbus output board. The meter indica tes output and abbreviated diagnostic messages. The meter features a four-line display and a 0-100% scaled bar graph. The first line of five chara ...

  • Emerson 3051S - page 19

    Reference Manual 00809-0200-4801, Rev BA April 2007 3-19 Rosemount 3051S DISPLA Y_P ARAM_SEL The DISPLA Y_P ARAM_SEL paramete r specifies how many process variables will be displayed. Select up to four display parameters. BLK_T AG_# (1) Enter the Block T ag of the function block that contains the parameter to be displayed. BLK_TYPE_# (1) Enter the ...

  • Emerson 3051S - page 20

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-20 CUSTOM_UNITS_# (1) S pecify custom units to be displayed with the p arameter . Enter up to six characters. T o display Custom Unit s the UNITS_TYPE_# must be set to CUSTOM. Displaying a variable from another device on the segment (Example) Any variable from a device on the ne ...

  • Emerson 3051S - page 21

    Reference Manual 00809-0200-4801, Rev BA April 2007 3-21 Rosemount 3051S ADVANCED DIAGNOSTICS T RANSDUCER BLOCK (ADB) The Advanced Diagnostics Function Block is a licensable block. It will be licensed on a new transmitter if the D01 option is ordered or can be licensed in the field via a licensing code. Please contact your local sales person on how ...

  • Emerson 3051S - page 22

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-22 Configuration of the Plugged Impulse Line Detection T o configure the PIL, open the ADB tr ansducer block and refer to the host documentation. The three p arameters below are the minimum required for configuration. PLINE_Affect_PV_S tatus PLINE_Affect_PV_S tatus determines whe ...

  • Emerson 3051S - page 23

    Reference Manual 00809-0200-4801, Rev BA April 2007 3-23 Rosemount 3051S NOTE For most applications the above para meters are all that are needed to configure the PIL for detection. In order to use the Advanced Set of parameters below , fully underst and the underlying technology of the PIL. These pa rameters will fine tune the PIL to fit process c ...

  • Emerson 3051S - page 24

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-24 PLINE_Learn_Sensitivity The PLINE_Learn_Sensitivity parameters provide very specific adjustment s to the sensitivity during the learning phase. • Insufficient Dynamics Check: Ignores the insuf ficient dynamic check if not selected. Use only when there is very low process noi ...

  • Emerson 3051S - page 25

    Reference Manual 00809-0200-4801, Rev BA April 2007 3-25 Rosemount 3051S St atistical Process Monitoring (SPM) S tatistical Process Monitoring algorithm is intended to provide basic information regarding the behavior of process measurements such as PID control block and actual valve position. The algorithm can monitor up to four user selected varia ...

  • Emerson 3051S - page 26

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-26 V erify Phase The verifying phase is similar to the l earning phase. It calculates a baseline value which is then compared to the l earning phase baseline value. This is done to ensure a steady process before the dete ction phase. The amount of acceptable deviation between t h ...

  • Emerson 3051S - page 27

    Reference Manual 00809-0200-4801, Rev BA April 2007 3-27 Rosemount 3051S SPM#_Thresholds The SPM#_Thresholds are used to allow alerts to be sent when the values are beyond the threshold values that have been set for each parameter . Mean Limit Alert Limit value in percent change of the Mean compared with the baseline mean value. High V ariation Ale ...

  • Emerson 3051S - page 28

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-28 If you already own a National Instrum ents Fieldbus interface device, you can go to rosemount.com to download the 3051S revision 23 Device Description. If you don’t already own a National In struments Fieldbus interface device, contact your local sales person for ordering op ...

  • Emerson 3051S - page 29

    Reference Manual 00809-0200-4801, Rev BA April 2007 3-29 Rosemount 3051S Est ablish Communications with the 3051S F OUNDATION Fieldbus T ransmitter using 3095 EA for F OUNDATION Fieldbus 1. Connect the 9-pin communications cable into the PCMCIA card port located in the computer . 2. Connect communication wiring to the cable connectors labeled “D ...

  • Emerson 3051S - page 30

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-30 Create and Send a Mass Flow Configuration using 3051S EA for F OUNDATION Fieldbus A mass flow configuration file can be created in either OFFLINE or ONLINE mode. 1. Select the device tag name requiring a new or updated mass flow configuration file. The selected device tag will ...

  • Emerson 3051S - page 31

    Reference Manual 00809-0200-4801, Rev BA April 2007 3-31 Rosemount 3051S Figure 3-9. EA Wizard View 4. Upon completing a mass flow configuration using the EA Wizard, the file can be saved to disk. The file must be saved for review or to edit the mass flow configuration file in the future. F OUNDATION Fieldbus mass flow configuration files ca nnot b ...

  • Emerson 3051S - page 32

    Reference Manual 00809-0200-4801, Rev BA April 2007 Rosemount 3051S 3-32 Figure 3-10. Download Mass Flow Configuration File Selected Device (Highlighted) Send Mass Flow Configuration File to Selected Device St atus Confirms Mass Flow Configuration File Installations T able 3-7. Mass Flow Block Device - S pecific Parameter V a lues Index Parameter D ...

メーカー Emerson カテゴリー Lawn Mower

Emerson 3051Sのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 3051Sの取扱説明書
- Emersonの製品カード
- パンフレット
- またはEmerson 3051Sの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Emerson 3051Sの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Emerson 3051Sの取り付け説明書、サービスマニュアル、簡易説明書、またはEmerson 3051Sのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Emerson 3051Sの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Emerson 3051Sデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがEmerson 3051Sを使用するのを助ける技術的文書のことです。説明書は通常、全てのEmerson 3051Sユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Emersonの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Emerson 3051Sの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははEmerson 3051Sの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Emerson 3051Sに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Emerson 3051Sデバイスの基本機能を使うにあたってのヒント。 Emerson 3051Sのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Emerson 3051Sに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるEmerson 3051Sのメーカー/サービスへの連絡先に関する情報。

Emerson 3051Sについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもEmerson 3051Sの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがEmerson 3051Sで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)