    506725-01 Page 1 of 48 Issue 1 109 This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death. As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment. CAU ...

  • Allied 92G1DF - page 2

    506725-01 Page 2 of 48 Issue 1 109 UNIT DIMENSIONS − inches (mm) EXHAUST AIR OUTLET COMBUSTION AIR INT AKE 2−1/16 (52) GAS PIPING INLET (Either Side) ELECTRICAL INLET (Either Side) Return Air Opening W E I V E D I S TOP VIEW 27−3/4 19−1/4 (489) 9−1/8 (232) Right 6−9/16 (167) Left 2 (51) Either Side 3/4 (19) B Supply Air 9/16 (14) 9/16 ( ...

  • Allied 92G1DF - page 3

    506725-01 Page 3 of 48 Issue 1 109 PARTS ARRANGEMENT FIGURE 1 CONTROL BOX (Includes integrated control, transformer and door switch) BAG ASSEMBL Y BLOWER MOTOR (hidden) BLOWER ACCESS P ANEL HEATING ACCESS P ANEL COMBUSTION AIR INDUCER BURNER BOX ASSEMBL Y (includes ame sensor , rollout switches and ignitor) GAS V AL VE BLOWER DECK HEA T EXCHANGE ...

  • Allied 92G1DF - page 4

    506725-01 Page 4 of 48 Issue 1 109 Gas Furnace This Category IV gas furnace is shipped ready for installation in the downflow position. The furnace is equipped for installation in natural gas applications. A conversion kit (ordered sep arately) is required for use in propane/LP gas applications. This unit can be installed as either a Direct V ent o ...

  • Allied 92G1DF - page 5

    506725-01 Page 5 of 48 Issue 1 109 Locations and Clearances This furnace is CSA International certified for installation clearances to combustible material as listed on the unit nameplate and in the table in Figure 1 1. Accessibility and service clearances must take precedence over fire protection clearances. NOTE: When furnace is inst alled on a c ...

  • Allied 92G1DF - page 6

    506725-01 Page 6 of 48 Issue 1 109 • Air filters must be replaced upon construction completion. • The input rate and temperature rise must be set per the furnace rating plate. • One hundred percent (100%) outdoor air must be provided for combustion air requirement s during construction. T emporary ducting may supply outdoor air to the furnace ...

  • Allied 92G1DF - page 7

    506725-01 Page 7 of 48 Issue 1 109 air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a down draft can occur in the furnace vent pipe or chimney . As a result, combustion gases enter the living space creating a potentially dangerous situation. In the absenc ...

  • Allied 92G1DF - page 8

    506725-01 Page 8 of 48 Issue 1 109 Air from Out side If air from out side is brought in for combustion and ventilation, the confined space shall be provided with two permanent openings. One opening shall be within 12” (305 mm) of the top of the enclosure and one within 12” (305 mm) of the bottom. These openings must communicate directly or by d ...

  • Allied 92G1DF - page 9

    506725-01 Page 9 of 48 Issue 1 109 INST ALLA TION – Setting Equipment Shipping Bolt Removal NOTE: Unit s with a 1/2 hp blower motors are equipped with three flexible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a flexible mounting leg). Se ...

  • Allied 92G1DF - page 10

    506725-01 Page 10 of 48 Issue 1 109 W ARNING Improper installation of the furnace can result in personal injury or death. Combustion and flue products must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint t ape to seal return air system to furnace. In platform installations with furnace re ...

  • Allied 92G1DF - page 11

    506725-01 Page 11 of 48 Issue 1 109 2. After opening is cut, set the combustible flooring base into opening. 3. Check fiberglass strips on the combustible flooring base to make sure they are properly glued and positioned. 4. Lower supply air plenum into the combustible flooring base until plenum flanges seal against fiberglass strips. er opening is ...

  • Allied 92G1DF - page 12

    506725-01 Page 12 of 48 Issue 1 109 Filters This unit is not equipped with a filter or rack. A field provided filter is required for the unit to operate properly . T able 3 list s recommended filter sizes. A filter must be in place whenever the unit is operating. CAUTION Solvent cements for plastic pipe are flammable liquids and should be kept away ...

  • Allied 92G1DF - page 13

    506725-01 Page 13 of 48 Issue 1 109 The exhaust and intake connections are made of PVC. Use PVC primer and solvent cement when using PVC vent pipe. When using ABS vent pipe, use transitional solvent cement to make connections to the PVC fitting in the unit. IMPORT ANT Use PVC primer and solvent cement or ABS solvent cement meeting ASTM specificatio ...

  • Allied 92G1DF - page 14

    506725-01 Page 14 of 48 Issue 1 109 Joint Cementing Procedure All cementing of joint s should be done according to the specifications outlined in ASTM D 2855. 1. Measure and cut vent pipe to desired length. 2. Debur and chamfer end of pipe, removing any ridges or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting sock ...

  • Allied 92G1DF - page 15

    506725-01 Page 15 of 48 Issue 1 109 V ent Piping Guidelines This gas furnace can be installed as either a Non-Direct V ent or a Direct V ent gas central furnace. NOTE: In non-Direct V ent installations, combustion air is taken from indoors and flue gases are discharged outdoors. In Direct Vent inst allations, combustion air is taken from outdoors a ...

  • Allied 92G1DF - page 16

    506725-01 Page 16 of 48 Issue 1 109 T ABLE 7 Maximum Allowable Intake or Exhaust V ent Length in Feet *Siz e intake and exhaus t pipe length separately . Values in table are for Intake OR Ex haust, not combined total. Both Intake an d Exhaus t must be same pipe size. St andard T ermination at Elevation 0 − 10,000 ft. Number Of 90° Elbows Used 2& ...

  • Allied 92G1DF - page 17

    506725-01 Page 17 of 48 Issue 1 109 FIGURE 21 TYPICAL INT AKE PIPE CONNECTIONS (DIRECT VENT APPLICATIONS) 2” 2” TRANSITION 2” 3” TRANSITION 3” Pipe size determined in Table 7. 2” 2” or TOP VIEW EXHAUST INTAKE * When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible. NOTE: Intake pipe and exhaust pipe mus ...

  • Allied 92G1DF - page 18

    506725-01 Page 18 of 48 Issue 1 109 Int ake Piping This furnace may be installed in either direct vent or non- direct vent applications. In non-direct vent applications, when int ake air will be drawn into the furnace from the surrounding sp ace, the indoor air quality must be considered. Guidelines listed in Combustion, Dilution and V entilation A ...

  • Allied 92G1DF - page 19

    506725-01 Page 19 of 48 Issue 1 109 FIGURE 23 VENT TERMINA TION CLEARANCES FOR NON−DIRECT VENT INST ALLA TIONS IN THE USA AND CANADA K D E L B C F G A B J A M I H INSIDE CORNER DET AIL VENT TERMINAL AIR SUPPL Y INLET AREA WHERE TERMINAL IS NOT PERMITTED Fixed Closed Operable B Fixed Closed Operable B B A = B = C = D = E = F = G = H = I = J = K = ...

  • Allied 92G1DF - page 20

    506725-01 Page 20 of 48 Issue 1 109 FIGURE 24 VENT TERMINA TION CLEARANCES FOR DIRECT VENT INST ALLA TIONS IN THE USA AND CANADA K D E L B C F G A B J A M I H INSIDE CORNER DET AIL VENT TERMINAL AIR SUPPL Y INLET AREA WHERE TERMINAL IS NOT PERMITTED Fixed Closed Operable B Fixed Closed Operable B B A = B = C = D = E = F = G = H = I = J = K = L = M ...

  • Allied 92G1DF - page 21

    506725-01 Page 21 of 48 Issue 1 109 Details of Int ake and Exhaust Piping T erminations for Direct V ent Inst allations NOTE: In Direct V ent installations, combustion air is t aken from outdoors and flue gases are discharged to outdoors. NOTE: Flue gas may be slightly acidic and may adversely affect some building materials. If any vent termination ...

  • Allied 92G1DF - page 22

    506725-01 Page 22 of 48 Issue 1 109 FIGURE 27 C A E D B A B D D B C A C 12" 1 1 2 2 2" (51mm) V ent Pipe 3" (76mm) V ent Pipe A − Clearance above grade or average snow accumulation B −Horizontal separation between intake and exhaust C −Minimum from end of exhaust to inlet of intake D −Exhaust pipe length E −Wall support dis ...

  • Allied 92G1DF - page 23

    506725-01 Page 23 of 48 Issue 1 109 FIGURE 28 FIELD SUPPLIED W ALL TERMINA TION See venting Table 7 for maximum venting lengths with this arrangement. * Use wall support every 24" (610 mm). Use two wall supports if extension is greater than 24" (610 mm) but less than 48" (1219 mm). NOTE − One wall support must be 6" (152 mm) f ...

  • Allied 92G1DF - page 24

    506725-01 Page 24 of 48 Issue 1 109 FIGURE 30 DIRECT VENT CONCENTRIC ROOFTOP TERMINA TION 71M80, 69M29 or 60L46 (US) 44W92 or 44W93 (Canada) Minimum Above Average Snow Accumulation SHEET MET AL STRAP (Clamp and sheet metal strap must be field installed to support the weight of the termination kit.) FLASHING (Not Furnished) CLAMP FIELD−PROVIDED RE ...

  • Allied 92G1DF - page 25

    506725-01 Page 25 of 48 Issue 1 109 Details of Exhaust Piping T erminations for Non-Direct V ent Applications Exhaust pipe may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figures 34 through 37 show typical terminations. 1. ...

  • Allied 92G1DF - page 26

    506725-01 Page 26 of 48 Issue 1 109 Do Not use copper tubing or existing copper condensate lines for drain line. CAUTION Condensate Piping This unit is designed for either right or left side exit of condensate piping in downflow applications. Refer to Figure 38 for condensate trap locations. NOTE: If necessary the condensate trap may be installed u ...

  • Allied 92G1DF - page 27

    506725-01 Page 27 of 48 Issue 1 109 FIGURE 41 Adapter 1/2 inch slip X 1/2 inch mpt (Not Furnished) Drain T rap Assembly (Furnished) Ve n t Drain T rap Clean Out 5 Feet Maximum Coupling 1/2 inch slip X slip (Not Furnished) 90 ° Elbow 1/2 inch PVC (Not Furnished) 1/2 inch PVC Pipe (Not Furnished) 1/2 inch PVC Pipe (Not Furnished) 1 (25) Minimum Abov ...

  • Allied 92G1DF - page 28

    506725-01 Page 28 of 48 Issue 1 109 Gas Piping 1. Gas piping may be routed into the unit through either the lef t or right hand side. Supply piping enters into the gas valve from the side of the valve as shown in Figure 43. Move bellows grommet to side of the cabinet which the gas line enters. Ensure opposite gas line entrance is plugged with suppl ...

  • Allied 92G1DF - page 29

    506725-01 Page 29 of 48 Issue 1 109 GROUND JOINT UNION AUTOMA TIC GAS V AL VE (with manual shut−o valve) FIELD PROVIDED AND INST ALLED GROUND JOINT UNION Left Side Piping (St andard) Right Side Piping (Alternate) AUTOMA TIC GAS V ALVE (with manual shut−o valve) DRIP LEG DRIP LEG MANUAL MAIN SHUT−OFF VA LV E (With 1/8 in. NPT Plugged T a ...

  • Allied 92G1DF - page 30

    506725-01 Page 30 of 48 Issue 1 109 Removal of the Furnace from Common V ent In the event that an existing furnace is removed from a venting system commonly run with separate gas appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. Conduct the following test while each appliance is operating a ...

  • Allied 92G1DF - page 31

    506725-01 Page 31 of 48 Issue 1 109 Electrical ELECTROST A TIC DISCHARGE (ESD) Precautions and Procedures Electrostatic discharge can af fect electronic components. T ake precautions during furnace installation and service to protect the furnace’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by p ...

  • Allied 92G1DF - page 32

    506725-01 Page 32 of 48 Issue 1 109 One line voltage “HUM” 1/4” spade terminal is provided on the furnace control board. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. If a humidifier rated at greater than one amp is connected t ...

  • Allied 92G1DF - page 33

    506725-01 Page 33 of 48 Issue 1 109 TYPICAL WIRING DIAGRAM FIGURE 48 ...

  • Allied 92G1DF - page 34

    506725-01 Page 34 of 48 Issue 1 109 Unit St art-Up FOR YOUR SAFETY READ BEFORE OPERA TING Do not use this furnace if any part has been underwater . A flood-damaged furnace is extremely dangerous. Attempts to use the furnace can result in fire or explosion. Immediately call a qualified service technician to inspect the furnace and to replace all gas ...

  • Allied 92G1DF - page 35

    506725-01 Page 35 of 48 Issue 1 109 Priming Condensate T rap The condensate trap should be primed with water prior to start-up to ensure proper condensate drainage. Either pour 10 fl. oz. (300 ml) of water into the trap, or follow these steps to prime the trap: 1. Follow the lighting instructions to place the unit into operation. 2. Set the thermos ...

  • Allied 92G1DF - page 36

    506725-01 Page 36 of 48 Issue 1 109 Gas Pressure Adjustment Gas Flow (Approximate) NOTE: T o obt ain accurate reading, shut off all other gas appliances connected to meter . Furnace should operate at least 5 minutes before checking gas flow . Determine time in seconds for two revolutions of gas through the meter . (T wo revolutions assures a more a ...

  • Allied 92G1DF - page 37

    506725-01 Page 37 of 48 Issue 1 109 Nat ur a l to LP / P ropane LP / P ropane to Nat u ra l H i g h Al titu d e Nat u ra l B urner Orifi c e Kit H ig h Altitu d e LP / P ro pa n e Bu r n e r O r if ice Kit A l l 68W 75*† 73W 80 * 51W 01 6 8W 70* † * Conv ers i on r e qui res i ns t al l at ion of a gas v al v e regul at or s pri ng w hi c h i s ...

  • Allied 92G1DF - page 38

    506725-01 Page 38 of 48 Issue 1 109 T esting for Proper V enting and Sufficient Combustion Air for Non-Direct V ent Applications CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following ...

  • Allied 92G1DF - page 39

    506725-01 Page 39 of 48 Issue 1 109 Other Unit Adjustment s Primary Limit The primary limit is located on the heating compartment vestibule panel. This limit is factory set and requires no adjustment. Flame Rollout Switches (T wo) These manually reset switches are located on the front of the burner box. These limits are factory set and require no a ...

  • Allied 92G1DF - page 40

    506725-01 Page 40 of 48 Issue 1 109 BL O WE R D A T A A93DF1D / 92G1DF A93DF1D / 92G1DF 070*12B PERFORMANCE (Less Filter) External Static Pressure in. w .g. Air V olume / Watts at V arious Blower Speeds High Medium- High Medium- Low Low cfm W atts cfm Watts cfm W atts cfm Watts 0.00 1505 660 1310 570 1090 455 940 390 0.10 1480 625 1295 550 1070 435 ...

  • Allied 92G1DF - page 41

    506725-01 Page 41 of 48 Issue 1 109 BL OWE R DA T A A95DF1D / 95G1DF A95DF1D / 95G1DF 070*12B PERFORMANCE (Less Filter) External Static Pressure in. w .g. Air V olume / Watts at V arious Blower Speeds High Medium- High Medium- Low Low cfm W atts cfm Watts cfm W atts cfm Watts 0.00 1515 620 1315 545 1095 465 910 390 0.10 1490 585 1300 525 1075 445 8 ...

  • Allied 92G1DF - page 42

    506725-01 Page 42 of 48 Issue 1 109 Service At the beginning of each heating season, system should be checked as follows by a qualified service technician: Blower Check the blower wheel for debris and clean if necessary . The blower motors are prelubricated for extended bearing life. No further lubrication is needed. The blower access panel must be ...

  • Allied 92G1DF - page 43

    506725-01 Page 43 of 48 Issue 1 109 19. Reinstall heat exchanger into cabinet making sure that the clamshells of the heat exchanger assembly are resting on the support located at the rear of the cabinet. Remove the indoor blower to view this area through the blower opening. 20 . Resecure the supporting screws along the vestibule sides and bottom to ...

  • Allied 92G1DF - page 44

    506725-01 Page 44 of 48 Issue 1 109 Planned Service A service technician should check the following items during an annual inspection. Power to the unit must be shut of f for safety . Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) - Must be open and unobstructed to provide combustion air . Burners - Must ...

  • Allied 92G1DF - page 45

    506725-01 Page 45 of 48 Issue 1 109 REP AIR P ARTS LIST The following repair part s are available through Allied Air dealers. When ordering part s, include the complete furnace model number listed on the CSA nameplate. Example: A93DF045P36B-01. All service must be performed by a licensed professional installer (or equivalent), service agency , or g ...

  • Allied 92G1DF - page 46

    506725-01 Page 46 of 48 Issue 1 109 St art−Up & Performance Check List Gas Supply Pressure SUPPL Y AIR Line V oltage GAS SUPPL Y Natural Gas LP Prop ane Gas Piping Connections Tight Leak T ested 1 INT AKE / EXHAUST PIPE All Joints Primed and Glued T erminations Installed Properly Pipes Supported Condensate T rap Primed / Line Sloped Heat Cabl ...

  • Allied 92G1DF - page 47

    506725-01 Page 47 of 48 Issue 1 109 Contractor’s: Name______________________________________T elephone_ _______________Checklist Completed____________________ Job Address_______________________________________________________T echnician’s Name___________________________________ 1 HEA TING MODE COMBUSTION SAMPLE CO 2 % ______ C O _____ P PM 2 IN ...

  • Allied 92G1DF - page 48

    506725-01 Page 48 of 48 Issue 1 109 REQUIREMENTS for COMMONWEAL TH of MASSACHUSETTS Modifications to NFP A-54, Chapter 10 Revise NFP A-54 section 10.8.3 to add the following requirement s: For all side wall, horizont ally vented, gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purpose ...

Manufacturer Allied Category Furnace

Documents that we receive from a manufacturer of a Allied 92G1DF can be divided into several groups. They are, among others:
- Allied technical drawings
- 92G1DF manuals
- Allied product data sheets
- information booklets
- or energy labels Allied 92G1DF
All of them are important, but the most important information from the point of view of use of the device are in the user manual Allied 92G1DF.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Allied 92G1DF, service manual, brief instructions and user manuals Allied 92G1DF. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Allied 92G1DF.

Similar manuals

A complete manual for the device Allied 92G1DF, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Allied 92G1DF by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Allied 92G1DF.

A complete Allied manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Allied 92G1DF - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Allied 92G1DF, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Allied 92G1DF, that we can find in the current document
3. Tips how to use the basic functions of the device Allied 92G1DF - which should help us in our first steps of using Allied 92G1DF
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Allied 92G1DF
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Allied 92G1DF in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Allied 92G1DF?

Use the form below

If you did not solve your problem by using a manual Allied 92G1DF, ask a question using the form below. If a user had a similar problem with Allied 92G1DF it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)