    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM APC Symmetra LX GUIDE SPECIFICATIONS FOR 4kVA-16kVA Uninterruptible Power System PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of a continuous duty, single- phase, solid-state, static Uninterruptible Po we ...

  • APC LX - page 2

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM E. The UPS and associated equipment shall opera te in conjunction with a primary power supply and an output distribution s ystem to provide quality uninterrupted power for mission critical, electronic equipment load. F. All programming and miscellaneou ...

  • APC LX - page 3

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM F. External Service Bypass Panel (SBP): Th e maintenance service bypass cabinet shall provide power to the critical load bus from the bypass source, during times where maintenance or service of the UPS frame is required or when removal of the frame is ...

  • APC LX - page 4

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 2.2 SYSTEM CHARACTERISTICS A. System Capacity: The syste m shall be rated for .8 Pf output in the f ollowing frame sizes: 1. 8 kVA/ 6.4kW - Can be configured with up to (3), 3. 2kW power modules for N+1 2. 16 kVA/ 12.8kW - Can be configured with up t o ...

  • APC LX - page 5

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 1) >130% for 4 seconds 2) 105% continuous 3) <130% Continuous at N+1 b. Bypass Operation: 1) 100A continuous 8. System AC-AC Efficiency: >90% at 100% load 10. Output Power Factor Rating: The UPS output shall b e .8 lagging 2.3 ENVIRONMENTAL A. ...

  • APC LX - page 6

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 2. In cases where the source voltage to the UPS is nominal and the applied UPS load is equal to or less than 100% of UPS capacity, input current shall not exceed 130% of UPS output current, while providing f ull battery recharge power and importing nec ...

  • APC LX - page 7

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 2.7 AUTOMATIC BYPASS A. As part of the UPS, a system automatic bypass switch shall be provided. The system automatic bypass shall provide a break <11Ms transfer of the critical load from the Inverter output to the automatic bypass input source durin ...

  • APC LX - page 8

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM B. Metered Data: The following metered data, shall be available on the alphanum eric display: 1. Year, Month, Day , Hour, Minute, Second of occurring events 2. Source Input Voltage 3. Output AC voltage 4. Output AC current 5. Input Frequency 6. Battery ...

  • APC LX - page 9

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 15. Need Battery Replacement 16. The Redundant Intelligence Module is in control 17. UPS Fault 18. On Battery 19. Shutdown or unable to transfer to battery due to overload 20. Load Shutdown from Bypass. Input Frequency Volts outside lim its 21. Fault, ...

  • APC LX - page 10

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM K. Controls: The following controls or prog ramming functions shall be accomplished by use of the display unit. Pushbutton membra ne switches shall facilitate these operations. 1. Silence audible Alarm 2. Display or set the date and time 3. Enable or d ...

  • APC LX - page 11

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM B. The battery jars housed within each removable battery module shall be of the Valve Regulated Lead Acid (VRLA) type. C. The UPS shall incorporate a battery manageme nt system to continuously monitor the health of each removable battery module as we l ...

  • APC LX - page 12

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 1. The UPS, in conjunction with a network interface card, shall be capable of gracefully shutting down one or more operating systems during when the UPS is on reserve mode. 2. The UPS shall also be capable of using an RS232 port to communicate by m ean ...

  • APC LX - page 13

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 1. Inspect equipment for signs of damage. 2. Verify installation per manufacturer s instructions. 3. Inspect cabinets for foreign objects. 4. Inspect Battery Units. 5. Inspect Power Modules. B. Mechanical Inspection 1. Check all UPS and external servic ...

  • APC LX - page 14

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 8. Verify proper charger operation. 9. Document, sign, and date all test results. E. On-Site Operational Training: During the factory assisted start-up, operational training for site personnel shall include key pad operation, LED indicators, start-up a ...

Manufacturer APC Category Power Supply

Documents that we receive from a manufacturer of a APC LX can be divided into several groups. They are, among others:
- APC technical drawings
- LX manuals
- APC product data sheets
- information booklets
- or energy labels APC LX
All of them are important, but the most important information from the point of view of use of the device are in the user manual APC LX.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals APC LX, service manual, brief instructions and user manuals APC LX. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product APC LX.

Similar manuals

A complete manual for the device APC LX, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use APC LX by users. Manuals are usually written by a technical writer, but in a language understandable to all users of APC LX.

A complete APC manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual APC LX - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the APC LX, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the APC LX, that we can find in the current document
3. Tips how to use the basic functions of the device APC LX - which should help us in our first steps of using APC LX
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with APC LX
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of APC LX in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning APC LX?

Use the form below

If you did not solve your problem by using a manual APC LX, ask a question using the form below. If a user had a similar problem with APC LX it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)