    I Condensing Oil-Fired Furnace I Installation Maintenance and Operation Manual ! WARNING Do not store gasoline flammable liquids or vapors in the vicinity of this or any other fuel burning appliance. I CAUTION . Improper installation. adjustment. alteration or maintenance can cause injury or property damage. Please refer to this manual. For assista ...

  • Adams Condensing Oil-Fired Furnace - page 2

    TABLE OF CONTENTS TABLE OF CONTENTS I. Component Identification 2 II. Safety 2 III. Product Application ---------- 4 IV. Location Requirements & Considerations -------4 Clearances and Accessibility -----------------5 Thermostat Location ------- 6 Existing Furnace Removal ------7 V. Combustion and Ventilation Air Requirements ---6 VI. Vent/Flue ...

  • Adams Condensing Oil-Fired Furnace - page 3

    ~_-- PART NO. CTVS24AA GH1033 M-3212 M-3212 M-3212 AGH1059 AGH1059 EE8201 DESCRIPTION FAN TIMER TRANSFORMER BLOWER RELAY AlC RELAY BURNER RELAY 24v TERMINAL STRIP 115v TERMINAL STRIP BLOWER MOTOR TERMINAL BLOCK IGNITION TRANSFORMER ----t- ....... FUEL PUMP ---t---., A B C D E F G H ITEM LETIER I. Component Identification PRESSURE SWITCH II. SAFETY ...

  • Adams Condensing Oil-Fired Furnace - page 4

    I WARNING WE WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES. IF YOU INSTALL OR PERFORM SERVICE ON THIS UNIT, YOU ASSUME RESPONSIBILLITY FOR ANY PERSONAl INJURY OR PROPERTY DAMAGE WHICH MAY RESULT. MANY JURISDICTIONS REQUIRE A LICENSE TO INSTALL OR SERVICE HEATING AND AIR CONDITIONING EQ ...

  • Adams Condensing Oil-Fired Furnace - page 5

    III. PRODUCT APPLICATION This furnace is primarily designed for residential home-heating applications. It is NOT designed or certified for use in mobile home, trailers or recreational vehicles. This unit is NOT designed or certified for outdoor applications. The furnace must be installed indoors (i.e., attic space, crawl space, or garage area prOVi ...

  • Adams Condensing Oil-Fired Furnace - page 6

    Follow the instructions listed below when selecting a furnace location. Refer also to the guidelines provided in Section V. Combustion and Ventilation Air Requirements. o Centrally locate the furnace with respect to the proposed or existing air distribution system. o Ensure the temperature of the return air entering the furnace is between 55 F and ...

  • Adams Condensing Oil-Fired Furnace - page 7

    These clearances must be permanently maintained. Clearances must also accommodate an installation's oil, electrical, and drain trap and drain line connections. If the alternate ventlflue connections are used additional clearance must be provided to accommodate these conditions Section IX, Vent Flue Pipe and Combustion Air Pipe for details. NOT ...

  • Adams Condensing Oil-Fired Furnace - page 8

    A return air duet system is recommended. Where there is no complete return air duct system, a return connection should be run full size to a location outside the confined space and completely sealed so that no air from the confined space can be circulated through the heating duct system. EXISTING FURNACE REMOVAL NOTE: When an existing furnace is re ...

  • Adams Condensing Oil-Fired Furnace - page 9

    PROPER VENT/FLUE AND COMBUSTION AIR PIPING PRACTICES Adhere to these instructions to ensure safe and proper furnace performance. The length, diameter, and number of elbows of the vent/flue pipe and combustion air pipe effects the performance of the furnace and must be carefully sized. All piping must be installed in accordance with local codes and ...

  • Adams Condensing Oil-Fired Furnace - page 10

    FORCED AIR INLET IF '1 IS lESS THAN 10 FT. nEN 'S'IS TO BE 3 FT. MINIMUM ''8'' . , DIRECT VENT TERMINATION IZ' ABOVE EXPECTED SNOW ACCUMULATION LocatIon of Exit T ...... ,naI. of Mechenical Draft end Direct-Venting S~ ..... Figure 2 9 Sidewall Vent System a) Sidewall vented products are susceptible to wind c ...

  • Adams Condensing Oil-Fired Furnace - page 11

    STANDARD FURNACE CONNECTIONS It is the responsibility of the installer to ensure that the piping connections to the furnace are secure, airtight, and adequately supported. All furnaces are shipped with a combustion air connection on the cabinet exterior and a flue connector on the inside of the cabinet on the condensate collector box. VENTIFLUE PIP ...

  • Adams Condensing Oil-Fired Furnace - page 12

    Installations require both a vent/flue pipe and a combustion air intake pipe. Refer to the appropriate section for details concerning piping size, length, number of elbows, furnace connections, and terminations. DIRECT VENT (DUAL PIPE) PIPING - BECKETT NX NON-DIRECT VENT (DUAL PIPE) INTERburner Installations require both a combustion air intake and ...

  • Adams Condensing Oil-Fired Furnace - page 13

    VII. ELECTRICAL CONNECTIONS I WARNING HIGH VOL TAGEI To avoid the risk of electrical shock, wiring to the unit must be polarized and grounded. ! WARNING HIGH VOLTAGEI To avoid personal Injury or death due to electrical shock, disconneCt electrical power before servicing or changing any electrical wiring. I CAUTION Label all wires prior to disconnec ...

  • Adams Condensing Oil-Fired Furnace - page 14

    HI- THERMOSTAT AIR Y ~ CAD=f ~y? : t~ &~;-------~~ ~ C . VI' UL -, I L-,l I 1 OR=t I 1 I I OR : ~iH~~~~==~==1J , lU1~t~. : BK I I ' ~----" tiQIQR SftiEQS I : r-++' HtSH -~t.ACK I ~1 S(fL ME'O-' WE LOW-' '£D I . R I : I ~=====*m~~ : r---------- m Ll-- _-Bm::. ===1~~J " te B RL-o 24 V. --t, -L-f-, &qu ...

  • Adams Condensing Oil-Fired Furnace - page 15

    I WARNING HIGH VOL TAGEI TO AVOID THE RISK OF INJURY, ELECTRICAL SHOCK OR DEATH, THE FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN THEIR ABSENCE, WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE. To ensure proper unit grounding, the ground wire should run from the furnace ground screw located inside the furnace jun ...

  • Adams Condensing Oil-Fired Furnace - page 16

    FLUE PRODUCTS MAKE HOLE HERE FOR C02 MEASUREMENT, SMOKE AND TEMPERATURE READINGS SEAL Vv1TH RTV SILICONE APPROXIMATELY 18' ABOVE CENTERLINE OF TEE • DO NOT USE CEMENT AT METAL COLLAR STAINLESS/RUBBER QUICK CONNECT COUPLER CONDENSATE COLLECTOR VENT TO ATMOSHPERE PREFILL TRAP 1TH WATER CONDENSATE NEUTRALIZER NEUTRALIZER MUST LAY HORIZONTAL ...

  • Adams Condensing Oil-Fired Furnace - page 17

    The furnace may be installed with a one-pipe system with gravity feed or lift. The maximum allowable lift on a single line system is 8 feet. Lift should be measured from the bottom (outlet) of the tank, to the inlet of the burner. Sizing a single line system is complex because of the difficulty estimating the pressure drop through each fitting, ben ...

  • Adams Condensing Oil-Fired Furnace - page 18

    When the furnace is used in connection with a cooling unit, the furnace should be installed in parallel with or on the upstream side of the cooling unit to avoid condensation in the heating element. With a parallel flow arrangement, the dampers or other means used to control the flow of air must be adequate to prevent chilled air from entering the ...

  • Adams Condensing Oil-Fired Furnace - page 19

    Drill a 3/8" hole in the PVC exhaust vent piping approximately 18" above where the PVC exits the side of the furnace for your combustion analysis equipment. (Seal with RTV silicone when finished conducting combustion analysis). BURNER ADJUSTMENT 1) Operate burner for 15 minutes before conducting test work. 2) Adjust burner settings until ...

  • Adams Condensing Oil-Fired Furnace - page 20

    Circulator Blower Speeds Low Red Medium Blue Hiah Black Common/Neutral White XII. NORMAL SEQUENCE OF OPERATION POWER UP MODE The normal power up sequence is as follows: • 115 VAC power applied to furnace • Furnace awaits call from thermostat HEATING MODE The normal operational sequence in heating mode is as follows: • Rand W thermostat contac ...

  • Adams Condensing Oil-Fired Furnace - page 21

    Table 1 System and General Troubleshooting PROBLEM POSSIBLE CAUSE REMEDY Thermostat not calling for heat. Check thermostat and adjust. Be sure it is accurate. If it is mercury type be sure it Is level. Check furnace switch and main electrical Dane! furnace fuse or circuit breaker. No I)OWer to furnace. Thermostat faulty. Remove thermostat wires fro ...

  • Adams Condensing Oil-Fired Furnace - page 22

    Table 1 System and General Troubleshooting PROBLEM POSSIBLE CAUSE REMEDY Electrodes out of adjustment or defective. Check etectrode settings. Check electrodes for dirt build-up or cracks in porcelain. Poor transformer high voltage connections or defective transformer. Check contacts between the igniter and electrodes. If OK, replace the Igniter. Oi ...

  • Adams Condensing Oil-Fired Furnace - page 23

    Table 1 System and General Troubleshooting PROBLEM POSSIBLE CAUSE REMEDY Home does not heat evenly. Improper distribution of heat. This Is unlikely to be a furnace problem. Balance duct system with dampers. Supply air temperature too Airtlow blocked or dirty air filter. Clean or replace air filter. hot. Insufficient airflow. Check all dampers. Open ...

  • Adams Condensing Oil-Fired Furnace - page 24

    Item No. 1A 3 3A 4 4A 5 6 7 9 10 10a 10B 11 12 12A 12B 13 14 15 16 17 17A 17B 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 49A 50 Description Part No. 2.5 Tons Cooling A10001 HEO A1011 HEO A-1 A-2 36TV01 36TV01A A1071HEO A3001HEO A3011HEO A3041HEO A3051 3052HEO A3053HEO A1081HEO A1091HEO A1091AHEO ...

  • Adams Condensing Oil-Fired Furnace - page 25

    Furnace Assembly Drawing 11 ~ 38 13 m ::: ::1 ,., /""' U,' I I I ' ... / ~ ~ . '" 14 15 /6 ...

Manufacturer Adams Category Furnace

Documents that we receive from a manufacturer of a Adams Condensing Oil-Fired Furnace can be divided into several groups. They are, among others:
- Adams technical drawings
- Condensing Oil-Fired Furnace manuals
- Adams product data sheets
- information booklets
- or energy labels Adams Condensing Oil-Fired Furnace
All of them are important, but the most important information from the point of view of use of the device are in the user manual Adams Condensing Oil-Fired Furnace.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Adams Condensing Oil-Fired Furnace, service manual, brief instructions and user manuals Adams Condensing Oil-Fired Furnace. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Adams Condensing Oil-Fired Furnace.

A complete manual for the device Adams Condensing Oil-Fired Furnace, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Adams Condensing Oil-Fired Furnace by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Adams Condensing Oil-Fired Furnace.

A complete Adams manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Adams Condensing Oil-Fired Furnace - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Adams Condensing Oil-Fired Furnace, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Adams Condensing Oil-Fired Furnace, that we can find in the current document
3. Tips how to use the basic functions of the device Adams Condensing Oil-Fired Furnace - which should help us in our first steps of using Adams Condensing Oil-Fired Furnace
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Adams Condensing Oil-Fired Furnace
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Adams Condensing Oil-Fired Furnace in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Adams Condensing Oil-Fired Furnace?

Use the form below

If you did not solve your problem by using a manual Adams Condensing Oil-Fired Furnace, ask a question using the form below. If a user had a similar problem with Adams Condensing Oil-Fired Furnace it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)