Manual Powerware 9315 UPS

84 pages 0.58 mb
Download

Go to site of 84

Summary
  • Powerware 9315 UPS - page 1

    Powerware 9315 UPS 200–300 kVA Operation Manual ® ...

  • Powerware 9315 UPS - page 2

    IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference. Consignes de sécurité CONSIGNES DE SÉCURITÉ IMPORTANTES CONS ...

  • Powerware 9315 UPS - page 3

    i EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Table of Contents 1 Introduction 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 Conventions Used in This Manual 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Powerware 9315 UPS - page 4

    Table of Contents ii EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 4 Starting and Stopping the UPS 4−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1 Using the Control Panel 4−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Powerware 9315 UPS - page 5

    Table of Contents iii EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7.6 Terminal Mode 7−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.6.1 Printing Selected Information 7−9 . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Powerware 9315 UPS - page 6

    Table of Contents iv EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com List of Figures Figure 2-1. Typical Powerware 9315 UPS System 2−2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 2-2. Main Elements of the UPS System 2−3 . . . . . . . . . . . . . . . ...

  • Powerware 9315 UPS - page 7

    1−1 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Chapter 1 Introduction The Powerware ® 9315 uninterruptible power supply (UPS) online power protection prevents loss of valuable electronic information, minimizes equipment downtime, and/or minimizes the adverse effect on equipment production due ...

  • Powerware 9315 UPS - page 8

    Introduction 1−2 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 1.2 For More Information Refer to the Powerware 9315 UPS (200–300 kVA) Installation Manual for the following additional information: A How to prepare your site and plan for installation A Detailed step-by-step procedures for install ...

  • Powerware 9315 UPS - page 9

    2−1 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Chapter 2 Getting Started 2.1 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all in ...

  • Powerware 9315 UPS - page 10

    Getting Started 2−2 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com A Keep surroundings uncluttered, clean, and free from excess moisture. A Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment. 2.2 Typical Powerware 9315 UPS System Each component of t ...

  • Powerware 9315 UPS - page 11

    Getting Started 2−3 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 2.3 Looking Inside the UPS The Powerware 9315 is a continuous−duty, solid-state UPS that supports the following equipment: process control, data processing, telecommunications/PBX, research, and medical. The Powerware 9315 mainta ...

  • Powerware 9315 UPS - page 12

    Getting Started 2−4 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 2.4 UPS Standard Features The UPS has many standard features that provide cost-effective and consistently reliable power protection: 2.4.1 Monitor Panel The Monitor Panel on the front of the UPS contains an LCD screen to display th ...

  • Powerware 9315 UPS - page 13

    Getting Started 2−5 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 2.4.5 Emergency Load Off A LOAD OFF button is provided for situations where you must immediately remove all power to the critical load. The button is located on the front of the UPS for quick access and is covered with a clear plas ...

  • Powerware 9315 UPS - page 14

    Getting Started 2−6 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 2.5.3 Power Distribution Module (LV models only) An optional output Power Distribution Module (PDM) is available to distribute the output power of the UPS to the critical load. The PDM cabinet has one or two panels, each containing ...

  • Powerware 9315 UPS - page 15

    Getting Started 2−7 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 2.5.9 Output Transformer An optional 480/208 Vac output auto transformer provides a 208 Vac output for applications that require 208 Vac. The transformer is contained in a separate cabinet. 2.5.10 Modem An optional modem is availab ...

  • Powerware 9315 UPS - page 16

    Getting Started 2−8 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 2.6 Symbols, Controls, and Indicators These symbols may appear on the UPS system or on labels inside the UPS. They are accepted by most international safety agents. Everyone in your organization who works with your UPS should under ...

  • Powerware 9315 UPS - page 17

    3−1 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Chapter 3 Understanding UPS Operation The UPS functions automatically to supply AC electrical power to the critical load. The UPS always operates in one of three modes: A In Normal mode, the critical load is supplied by the inverter, which derives ...

  • Powerware 9315 UPS - page 18

    Understanding UPS Operation 3−2 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Bypass Input Rectifier Input Output Path of electrical power Battery Rectifier Inverter Bypass K4 Transformer K3 (Closed) CB1 Figure 3-1. Path of Current Through the UPS in Normal Mode If the utility AC power is interru ...

  • Powerware 9315 UPS - page 19

    Understanding UPS Operation 3−3 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 3.2 Bypass Mode The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure. The bypass source supplies the commercial AC power to the load directly. C A U T I O N The critic ...

  • Powerware 9315 UPS - page 20

    Understanding UPS Operation 3−4 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 3.3 Battery Mode The UPS transfers to Battery mode automatically if a utility power outage occurs, or if the utility power does not conform to specified parameters. In Battery mode, the battery provides emergency DC pow ...

  • Powerware 9315 UPS - page 21

    Understanding UPS Operation 3−5 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 3.4 Monitoring and Controlling UPS Operation After you start the UPS, no operator intervention is necessary except for periodic checks of the UPS status. Manual operation is required only during routine maintenance or s ...

  • Powerware 9315 UPS - page 22

    Understanding UPS Operation 3−6 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com This page intentionally left blank. ...

  • Powerware 9315 UPS - page 23

    4−1 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Chapter 4 Starting and Stopping the UPS This chapter describes how to use the Control Panel to start and stop the UPS. NOTE Before starting the UPS, ensure all installation tasks are complete and a preliminary startup has been performed by authori ...

  • Powerware 9315 UPS - page 24

    Starting and Stopping the UPS 4−2 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com The following describes the switches on the Control Panel (see Figure 4-1): A The MODE switch is a two-position rotary switch that controls the manual transfer of the UPS to and from Bypass mode. The MODE switch is us ...

  • Powerware 9315 UPS - page 25

    Starting and Stopping the UPS 4−3 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com When the inverter reaches full voltage, it turns on and supplies power to the critical load. It takes less than one minute for the UPS to achieve Normal mode. If a bypass source is available when you turn the START sw ...

  • Powerware 9315 UPS - page 26

    Starting and Stopping the UPS 4−4 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com This page intentionally left blank. ...

  • Powerware 9315 UPS - page 27

    5−1 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Chapter 5 Using the Monitor Panel This chapter describes the Monitor Panel and how to monitor and control UPS operation. The Monitor Panel is a black rectangular area on the front of the UPS (see Figure 5-1). 1 2 3 4 Figure 5-1. UPS Monitor Panel ...

  • Powerware 9315 UPS - page 28

    Using the Monitor Panel 5−2 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 5.1 Using the LCD Screen The LCD screen at the top of the Monitor Panel provides an operator interface with the UPS. Figure 5-2 identifies the display fields discussed in the following sections. Uninterruptible Power System ...

  • Powerware 9315 UPS - page 29

    Using the Monitor Panel 5−3 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com You can use the LCD screen and the buttons beneath it to: A Monitor UPS operation A Look at a log of UPS events (alarms, notices, and commands) 5.2 Using the Buttons The buttons below the LCD screen are labeled with arrows ...

  • Powerware 9315 UPS - page 30

    Using the Monitor Panel 5−4 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 5.5 Reading the Status Indicators The six symbols on the left side of the monitor panel are status indicators. They are backlit by colored light emitting diodes (LEDs), and they work in conjunction with the alarm horn to le ...

  • Powerware 9315 UPS - page 31

    Using the Monitor Panel 5−5 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com A Graphics − Displays a real-time graphic representation of the flow of current through the internal UPS components. A Setup − Allows you to configure the UPS communication port and set the date and time for the timesta ...

  • Powerware 9315 UPS - page 32

    Using the Monitor Panel 5−6 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Uninterruptible Power System System Normal Alarm: None Notice: None Meters System Load Amps Events Statistics Graphics Setup Meters Output Current 125% 100% 75% 50% 25% 0% Phase A Phase B Phase C 04 NOV 1997 14:23:45 Batter ...

  • Powerware 9315 UPS - page 33

    Using the Monitor Panel 5−7 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Select History from the Events menu to display the Event History Log. The Event History Log lists up to 400 system events in chronological order, with the most recent event listed last. The end of the log appears when you d ...

  • Powerware 9315 UPS - page 34

    Using the Monitor Panel 5−8 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Select Active from the Events menu to display a listing of all system events that are currently active. The most recent system event is listed first. As events clear, they are removed from the Active System Events listing. ...

  • Powerware 9315 UPS - page 35

    Using the Monitor Panel 5−9 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Select Unit from the Statistics menu to display a listing of statistics about UPS operation. Figure 5-7 shows the Unit Statistics screen. Uninterruptible Power System UPS System Normal Alarm: None Notice: None 04 NOV 1997 1 ...

  • Powerware 9315 UPS - page 36

    Using the Monitor Panel 5−10 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Select Mimic from the Graphics menu to display a real-time graphical representation of the flow of current through the UPS. Figure 5-8 shows the Mimic screen. Uninterruptible Power System UPS System Normal Alarm: None Noti ...

  • Powerware 9315 UPS - page 37

    Using the Monitor Panel 5−11 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Select Time from the Setup menu to display the Time Setup screen. The Time Setup screen allows you to set the internal timestamp of the UPS. The timestamp is used for logging events in the Event History Log. Figure 5-9 sho ...

  • Powerware 9315 UPS - page 38

    Using the Monitor Panel 5−12 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Select Port 1 or Port 2 from the Setup menu to display one of the Port Setup screens. The Port Setup screens allow you to specify settings for the two serial communication ports on the UPS. Figure 5-10 shows the Setup Seri ...

  • Powerware 9315 UPS - page 39

    6−1 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Chapter 6 Using Features and Options You can add available options and accessories to enhance the performance of your UPS system. This chapter provides detailed descriptions of some of the features and options introduced earlier in this manual. 6. ...

  • Powerware 9315 UPS - page 40

    Using Features and Options 6−2 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 6.2 Summary Alarm Contacts Two summary alarm contacts are provided as a standard feature on the UPS. The alarm contacts (one notice and one alarm) are located inside the UPS on the customer interface panel (see Figure 6- ...

  • Powerware 9315 UPS - page 41

    Using Features and Options 6−3 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 6.3 Remote Monitor Panel As an option, you can install RMPs to monitor the operation of the UPS system from virtually any location within your facility, up to 500 ft from the UPS. Each RMP contains backlit status indicat ...

  • Powerware 9315 UPS - page 42

    Using Features and Options 6−4 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Table 6-1. Optional Monitoring Accessories Number and Type of Accessories Permitted Remote Monitor Panel Relay Interface Module Supervisory Contact Module 2    2    2 1 1  1  1  1 1 The RMP con ...

  • Powerware 9315 UPS - page 43

    Using Features and Options 6−5 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 6.4 Battery Cabinets You can enhance the protection time provided by your UPS by adding one or more battery cabinets. The battery cabinets provided by the UPS manufacturer are equipped with sealed lead-acid, maintenance- ...

  • Powerware 9315 UPS - page 44

    Using Features and Options 6−6 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 6.6 Relay Interface Module An optional RIM uses relay contact closures to indicate the operating status and alarm condition of the UPS system. A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be installe ...

  • Powerware 9315 UPS - page 45

    Using Features and Options 6−7 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 6.7 Supervisory Contact Module An optional SCM establishes an interface between the UPS manufacturer’s equipment and the customer’s monitor. This interface allows the customer to monitor operational status of the UPS ...

  • Powerware 9315 UPS - page 46

    Using Features and Options 6−8 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com This page intentionally left blank. ...

  • Powerware 9315 UPS - page 47

    7−1 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Chapter 7 Communication This chapter describes the communication features of the Powerware 9315 UPS and provides information about connecting hardware and using Terminal mode. 7.1 Locating the Communication Bays The Communication Panel inside the ...

  • Powerware 9315 UPS - page 48

    Communication 7−2 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Port 2 (DB−25F) RS−232 Connection (disabled by default) Port 1 (DB−9F) RS−485 Connection TB1 and TB2 Communication Panel X−Slot Communication Bay Card Slot Figure 7-1. Location of Communication Bays on the UPS (Powerware 93 ...

  • Powerware 9315 UPS - page 49

    Communication 7−3 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com A ConnectUPS SNMP Card − has Ethernet, modem, and SNMP capabilities. A Modem Card − provides out−of−band" remote notification and monitoring using modem communication directly to cell phones and pagers. A Multi−Serv ...

  • Powerware 9315 UPS - page 50

    Communication 7−4 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com NOT USED 485– 485+ RETURN 7 8 9 1 5 4 3 2 +24V RS-232 TXD RS-232 RXD NOT USED RETURN 6 Figure 7-3. Port 1 (DB−9) Pin Assignments Table 7-1. Pin Assignments for Port 1 (DB-9) Pin Number Symbol Function Comments 1 +24V +24 Volts DC ...

  • Powerware 9315 UPS - page 51

    Communication 7−5 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Table 7-2. Pin Assignments for Port 2 (DB-25) Pin Number Symbol Function Comments 1 GND Chassis Ground 2 TXD Transmit Data Input to UPS 3 RXD Receive Data Output from UPS 4 RTS Request to Send Input to UPS 5 CTS Clear to Send Output ...

  • Powerware 9315 UPS - page 52

    Communication 7−6 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7.5 Configuring the Serial Ports You must configure the port for communication using the LCD screen and buttons on the UPS Monitor Panel. Select Port 1 from the Setup menu to display one of the Setup Port screens. The screens for Por ...

  • Powerware 9315 UPS - page 53

    Communication 7−7 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Table 7-3 shows which options are available for each port. The sections that follow describe the configuration settings you can change. Table 7-3. Available Options for Each Communication Port Port 1 Port 2 Options X X Terminal Mode ...

  • Powerware 9315 UPS - page 54

    Communication 7−8 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7.5.3 Data/Stop The data size and stop bits of the equipment connected to this port. These settings determine the number of bits transmitted per ASCII character. The data size and stop bits you specify depend on the configuration of ...

  • Powerware 9315 UPS - page 55

    Communication 7−9 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7.6 Terminal Mode In this mode, system events are continually logged through the serial port to the device connected to the port. Port 2 operates by default in Terminal mode. The printed log entries contain a time and date stamp and ...

  • Powerware 9315 UPS - page 56

    Communication 7−10 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7.6.2 Entire Log – [Ctrl]+[P] This key sequence prints the entire Event History Log of the UPS at the time the data is requested. The printout begins with the oldest alarm entry in the queue and ends with the most recent. Any alar ...

  • Powerware 9315 UPS - page 57

    Communication 7−11 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7.6.3 Meters Printout – [Ctrl]+[M] This key sequence prints the current readings of the UPS system meters. The input area shows the phase-to-phase voltage, frequency, and phase current of the incoming utility, followed by the kVA, ...

  • Powerware 9315 UPS - page 58

    Communication 7−12 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7.6.4 System Information Printout – [Ctrl]+[A] This key sequence prints a listing of all available serial data. This printout contains the information shown on the Event History Log and System Meters screens of the UPS (both Figur ...

  • Powerware 9315 UPS - page 59

    Communication 7−13 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7.7 System Configuration The System Configuration mode allows you to modify special functions in your UPS. These functions include programming of building alarms, customizing building alarm messages, adjusting the nominal output vol ...

  • Powerware 9315 UPS - page 60

    Communication 7−14 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7.7.3 Enable/Disable Default Functions From this menu you may either enable the building alarms for general functions or special functions such as On Generator, Go To Bypass, and Go To UPS. You may also customize the alarm messages ...

  • Powerware 9315 UPS - page 61

    Communication 7−15 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7.7.4 Customize Alarm Messages If Customize Alarm Messages is selected from the Program Building Alarm menu, you can select a custom message for a building alarm or disable a previously enabled building alarm custom message. When th ...

  • Powerware 9315 UPS - page 62

    Communication 7−16 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7.7.5 Program Unit Name If Program Unit Name is selected from the main menu, the following is displayed: Program Unit Name Unit Name: Enter New Name or <CR> No Change: NOTE Unit Name is 45 characters maximum. The current unit ...

  • Powerware 9315 UPS - page 63

    Communication 7−17 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7.7.8 Battery Test Setup If Battery Test Setup is selected from the main menu, the following menu is displayed: Battery Test Setup 1. Setup One-time Delayed Battery Test 2. Setup Monthly Battery Test 3. Setup Quarterly Battery Test ...

  • Powerware 9315 UPS - page 64

    Communication 7−18 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7.7.9 Modify Low Battery Time This menu allows you to modify the low battery time warning. When selected, the following menu is displayed: Modify Low Battery Time Low Battery Time (Minutes): 004 Enter New Low Battery Time: NOTE Low ...

  • Powerware 9315 UPS - page 65

    Communication 7−19 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7.11 Remote Notification NOTE The X−Slot communication bay is connected internally to the DB−25 port by default; the DB−25 is disabled for other uses. Contact your Eaton service representative to purchase, install, and set up ...

  • Powerware 9315 UPS - page 66

    Communication 7−20 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com This page intentionally left blank. ...

  • Powerware 9315 UPS - page 67

    8−1 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Chapter 8 Maintaining the UPS System W A R N I N G Only qualified service personnel (such as a licensed electrician) should perform the battery installation and maintenance. Risk of electrical shock. The components inside the UPS cabinet are secur ...

  • Powerware 9315 UPS - page 68

    Maintaining the UPS System 8−2 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com W A R N I N G A Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is required. Refer to your local codes for disposal requirements. A Do not open or mutilate the ba ...

  • Powerware 9315 UPS - page 69

    Maintaining the UPS System 8−3 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ANNUAL maintenance − Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact your nearest field service office for more ...

  • Powerware 9315 UPS - page 70

    Maintaining the UPS System 8−4 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com This page intentionally left blank. ...

  • Powerware 9315 UPS - page 71

    9−1 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Chapter 9 Product Specifications The UPS systems are housed in freestanding, double-front cabinets with safety shields behind the doors. The UPS systems are available in 50/60 Hz with various output power ratings. Smaller models within a system ma ...

  • Powerware 9315 UPS - page 72

    Product Specifications 9−2 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Table 9-3. System Output Rectifier/Charger Capacity 125% DC Filtering Ripple voltage less than 0.5% peak to peak UPS Output Capacity 100% rated current Output Voltage Regulation 1% (10% to 100% load) Output Voltage Adjustmen ...

  • Powerware 9315 UPS - page 73

    Product Specifications 9−3 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com These specifications are for batteries supplied by the UPS manufacturer in line-up–and–match cabinets: Table 9-5. Battery Specifications Battery Type Sealed, maintenance-free, high rate discharge, lead-acid cells Nominal ...

  • Powerware 9315 UPS - page 74

    Product Specifications 9−4 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com This page intentionally left blank. ...

  • Powerware 9315 UPS - page 75

    10−1 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Chapter 10 Responding to System Events When the UPS system is running in Normal mode, it continually monitors itself and the incoming utility power. In Battery or Bypass modes, the UPS may issue alarms to let you know exactly what event caused th ...

  • Powerware 9315 UPS - page 76

    Responding to System Events 10−2 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com INVERTER MESSAGES − NOTICES INVERTER MESSAGES − ALARMS Over Temperature Shutdown Battery Not Charged Clear Battery Not Charged 100% Overload Shutdown Bypass is Not Available Bypass is Available 125% Overload Shutdo ...

  • Powerware 9315 UPS - page 77

    Responding to System Events 10−3 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com RECTIFIER MESSAGES − ALARMS RECTIFIER MESSAGES − NOTICES Rectifier DC Over Voltage Clear Rectifier DC Over Voltage Input AC Over Voltage Clear Input AC Over Voltage Rectifier DC Under Voltage Clear Rectifier DC Und ...

  • Powerware 9315 UPS - page 78

    Responding to System Events 10−4 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com MONITOR PANEL ALARMS MONITOR PANEL NOTICES Load Over 100% Clear Load Over 100% Output AC Over Voltage Clear Output AC Over Voltage Overload 100% Clear Overload 100% Output AC Under Voltage Clear Output AC Under Voltage ...

  • Powerware 9315 UPS - page 79

    11−1 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Chapter 11 Using the LOAD OFF Button Load Off is initiated by the covered, red LOAD OFF button on the Monitor Panel. This button is protected by a clear plastic shield to prevent accidental activation. In an emergency, you can press this button t ...

  • Powerware 9315 UPS - page 80

    Using the LOAD OFF Button 11−2 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 11.2 Resetting the UPS System after Load Off C A U T I O N Do not attempt to restart the system after Load Off until the cause of the emergency has been identified and cleared. The Load Off PUSH TO RESET button is a smal ...

  • Powerware 9315 UPS - page 81

    W−1 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com Warranty LIMITED FACTORY WARRANTY FOR THREE-PHASE POWERWARE ® UPS PRODUCTS WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delaware Corporation (Eaton"). LIMITED WARRANTY: This limited warr ...

  • Powerware 9315 UPS - page 82

    Warranty W−2 EATON Powerware ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com This page intentionally left blank. ...

  • Powerware 9315 UPS - page 83

    ...

  • Powerware 9315 UPS - page 84

    *164201036G* 164201036 G ...

Manufacturer Powerware Category Power Supply

Documents that we receive from a manufacturer of a Powerware 9315 UPS can be divided into several groups. They are, among others:
- Powerware technical drawings
- 9315 UPS manuals
- Powerware product data sheets
- information booklets
- or energy labels Powerware 9315 UPS
All of them are important, but the most important information from the point of view of use of the device are in the user manual Powerware 9315 UPS.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Powerware 9315 UPS, service manual, brief instructions and user manuals Powerware 9315 UPS. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Powerware 9315 UPS.

Similar manuals

A complete manual for the device Powerware 9315 UPS, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Powerware 9315 UPS by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Powerware 9315 UPS.

A complete Powerware manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Powerware 9315 UPS - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Powerware 9315 UPS, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Powerware 9315 UPS, that we can find in the current document
3. Tips how to use the basic functions of the device Powerware 9315 UPS - which should help us in our first steps of using Powerware 9315 UPS
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Powerware 9315 UPS
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Powerware 9315 UPS in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Powerware 9315 UPS?

Use the form below

If you did not solve your problem by using a manual Powerware 9315 UPS, ask a question using the form below. If a user had a similar problem with Powerware 9315 UPS it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)