Manual Powerware FCC 15

32 pages 0.48 mb
Download

Go to site of 32

Summary
  • Powerware FCC 15 - page 1

    Powerware Modbus Card User’s Guide ®® ...

  • Powerware FCC 15 - page 2

    Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with th e limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environm ent. This equipment generates, ...

  • Powerware FCC 15 - page 3

    EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com i Table of Contents 1 Introduction 1 ......................................................... 2 Installing the Modbus Card 3 ............................................. Inspecting the Equipment 3 ................................................................ F ...

  • Powerware FCC 15 - page 4

    TABLE OF CONTENTS EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com ii ...

  • Powerware FCC 15 - page 5

    EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 1 Chapter 1 Introduction The Eaton ® Powerware ® Modbus ® Card is an X - Slot ® connectivity device that allows you to continuously and reliably monitor the UPSs in your Building Management System (BMS). The card uses the Modbus protocol to integrate data from ...

  • Powerware FCC 15 - page 6

    INTRODUCTION EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 2 RS-485 Network Power Meter PLC UPS with Modbus Card Ethernet Gateway Building Management Software Ethernet -270.6 -270.6 Figure 2. UPS Integrated with RS-485 Network ...

  • Powerware FCC 15 - page 7

    EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 3 Chapter 2 Installing the Modbus Card The Modbus Card is available: S as a separate card for use with UPSs that have an X - Slot S factory - installed in a Powerware Expansion Chassis Use the following sequence for installing the Modbus Card: 1. For four - wire ne ...

  • Powerware FCC 15 - page 8

    INSTALLING THE MODBUS CARD EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 4 Four-Wire Communication The factory - default setting for the Modbus Card is for two - wire communication. To change the default setting, adjust the jumpers on the Modbus Card. CAUTION To prevent electrostatic discharge (ESD), pl ace on ...

  • Powerware FCC 15 - page 9

    INSTALLING THE MODBUS CARD EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 5 3. Change the J9 and J10 jumpers to the desired setting as shown in Figure 4. 1 1 J11 23456 ON S2 J7 J8 J10 J9 J9 J10 Four-Wire 1 1 J9 J10 Two-Wire (Default) 1 1 Figure 4. Modbus Card Jumpers 4. Reinstall the Modbus Card into the Powerw ...

  • Powerware FCC 15 - page 10

    INSTALLING THE MODBUS CARD EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 6 Installing the Modbus Card into an X-Slot CAUTION To prevent electrostatic discharge (ESD), pl ace one hand on an unpainted metal surface such as the UPS rear panel. 1. Remove the X - Slot cover (or existing X - Slot module) on the UPS ...

  • Powerware FCC 15 - page 11

    EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 7 Chapter 3 Wiring the Modbus Card The Modbus Card provides an easy path for integrating a Powerware UPS into an RS - 485 Modbus network and also provides isolation of the communication between the UPS and the RS - 485 Modbus network. You can use the DB - 9 port or ...

  • Powerware FCC 15 - page 12

    WIRING THE MODBUS CARD EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 8 Four-Wire Networks The Modbus Card also supports four - wire, half - duplex, RS - 485 networks. Figure 7 shows a detailed view of four - wire connections using the Modbus Card terminal strip. Slave Device #1 Master Device Slave Device #2 *S ...

  • Powerware FCC 15 - page 13

    WIRING THE MODBUS CARD EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 9 For four-wire networks. All four RS -485 network signals including TxD(+), RxD(+), TxD(–), and RxD(–) must be connected to the terminal strip as illustrated in Table 1. Verify that the Modbus Card J9 and J10 jumpers are set to the four ...

  • Powerware FCC 15 - page 14

    WIRING THE MODBUS CARD EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 10 3 8 7 9 1 6 2 4 5 Figure 9. RS-485 DB-9 Pin Numbers Table 2. RS-485 DB-9 Pin Assignments Pin Number Modbus Card Signal Name RS-485 Network Signals Master Signal Name 1 RxD(+) TxD(+) 2 TxD(+) RxD(+) 3 Signal common Signal common 4 Reserved ...

  • Powerware FCC 15 - page 15

    WIRING THE MODBUS CARD EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 11 1 J11 S2 J7 J8 J10 J9 RxD(–) Pull Down (620 Ω) RxD Terminator (120 Ω) Four-Wire Two-Wire ON *OFF 12 34 5 6 TxD(–) Pull Down (620 Ω) TxD(+) Pull Up (620 Ω) TxD Terminator (120 Ω) RxD(+) Pull Up (620 Ω) *Factory-default = OFF ...

  • Powerware FCC 15 - page 16

    WIRING THE MODBUS CARD EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 12 RS-232 Modbus Port It is also possible to use the RS - 232 Modbus port for connecting to your network. 3 8 7 9 1 6 2 4 5 Figure 11. RS-232 DB-9 Pin Numbers Table 3. RS-232 DB-9 Pin Assignments Pin Number Function Direction from the Modbus ...

  • Powerware FCC 15 - page 17

    EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 13 Chapter 4 Modbus Card Configuration The Modbus Card has an RS - 232 configuration port that you can access with a terminal or a computer equipped with a terminal emulation program. To use the configuration screens for the Modbus Card, you need: S A serial commun ...

  • Powerware FCC 15 - page 18

    MODBUS CARD CONFIGURATION EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 14 2. Press [Enter]. The Configuration screen appears (see Figure 13). Powerware Modbus Card Version 1.00 (1-16-02) Current Configuration: Baud Rate: 9600 Slave Address: 29 ------------------------------------------------------------------ ...

  • Powerware FCC 15 - page 19

    MODBUS CARD CONFIGURATION EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 15 4. To configure the slave address, type AD followed by a space and node (1 through 247) and press [Enter]. The default is 29. This setting affects both RS - 232 and RS-485 Modbus connections. 5. To save and exit, type SA and press [Ente ...

  • Powerware FCC 15 - page 20

    MODBUS CARD CONFIGURATION EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 16 ...

  • Powerware FCC 15 - page 21

    EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 17 Chapter 5 Integrating the UPS Powerware provides a software tool named Modbus Profiler that creates a Modbus register map specifically for your Powerware UPS. Refer to the Master Modbus Register Map for a complete list of the Status, Alarm, and Meter data for al ...

  • Powerware FCC 15 - page 22

    INTEGRATING THE UPS EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 18 5. Run profiler from the command prompt or double - click profiler.exe from Microsoft Windows Explorer. By default, Modbus Profiler uses the communication port specified in the [Connection] section of the profiler.ini file. If profiler fails ...

  • Powerware FCC 15 - page 23

    INTEGRATING THE UPS EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 19 Unit Format Value Name Register 113 Rectifier Input Status 1 BOOL Status 114 Bypass Status 0 BOOL Status 115 Bypass Input Status 1 BOOL Status 116 Input Circuit Breaker Status (CB1) 1 BOOL Status 117 Battery Disconnect Status 1 BOOL Status 11 ...

  • Powerware FCC 15 - page 24

    INTEGRATING THE UPS EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 20 Unit Format Value Name Register 162 Building Alarm 2 1 BOOL Status 163 Building Alarm 1 0 BOOL Status 169 Output overload 0 BOOL Status 172 DC link over voltage 0 BOOL Status 173 DC link under voltage 0 BOOL Status 174 Rectifier failed 0 BOOL ...

  • Powerware FCC 15 - page 25

    INTEGRATING THE UPS EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 21 Table 5. Read Input Registers - Modbus Function Code 04 (Input Registers Start at 30000) Register Meter Name Scale Unit 1 OUTPUT VOLTS AB /10 Volts 2 OUTPUT VOLTS BC /10 Volts 3 OUTPUT VOLTS CA /10 Volts 4 INPUT VOLTS AB /10 Volts 5 INPUT VOL ...

  • Powerware FCC 15 - page 26

    INTEGRATING THE UPS EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 22 Unit Scale Meter Name Register 62 INVERTER VOLTS PHASE C /10 Volts 66 LOAD CURRENT PHASE A /10 Amps 67 LOAD CURRENT PHASE B /10 Amps 68 LOAD CURRENT PHASE C /10 Amps 69 LOAD CURRENT PHASE A BAR CHART /10 Amps 70 LOAD CURRENT PHASE B BAR CHART ...

  • Powerware FCC 15 - page 27

    EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 23 Chapter 6 Troubleshooting Problem Possible Cause Corrective Action The Modbus Profiler tool does not generate the f i l f i l The wrong communication port number was entered in the profiler comX command. Verify the correct port number on your computer that is co ...

  • Powerware FCC 15 - page 28

    TROUBLESHOOTING EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 24 1 J11 2 13 4 5 6 ON S2 J7 J8 J10 J9 S2 Termination (Default ”OFF”) J11 Half Duplex Full-Duplex (Default) 1 1 J9 J10 Two-Wire (Default) 1 1 Two-Wire/Four-Wire J7 J8 DCE DCE/DTE (Default) 11 Figure 15. Modbus Card Default Jumper Settings ...

  • Powerware FCC 15 - page 29

    TROUBLESHOOTING EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 25 Service and Support If you have any questions or problems with the Modbus Card, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a Modbus Card technical representative. United States: 1-800-356-57 ...

  • Powerware FCC 15 - page 30

    TROUBLESHOOTING EATON Powerware ® Modbus ® Card User’s Guide S 164201376 Rev C www.powerware.com 26 ...

  • Powerware FCC 15 - page 31

    ...

  • Powerware FCC 15 - page 32

    *164201376C* 164201376 C ...

Manufacturer Powerware Category Network Card

Documents that we receive from a manufacturer of a Powerware FCC 15 can be divided into several groups. They are, among others:
- Powerware technical drawings
- FCC 15 manuals
- Powerware product data sheets
- information booklets
- or energy labels Powerware FCC 15
All of them are important, but the most important information from the point of view of use of the device are in the user manual Powerware FCC 15.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Powerware FCC 15, service manual, brief instructions and user manuals Powerware FCC 15. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Powerware FCC 15.

A complete manual for the device Powerware FCC 15, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Powerware FCC 15 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Powerware FCC 15.

A complete Powerware manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Powerware FCC 15 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Powerware FCC 15, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Powerware FCC 15, that we can find in the current document
3. Tips how to use the basic functions of the device Powerware FCC 15 - which should help us in our first steps of using Powerware FCC 15
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Powerware FCC 15
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Powerware FCC 15 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Powerware FCC 15?

Use the form below

If you did not solve your problem by using a manual Powerware FCC 15, ask a question using the form below. If a user had a similar problem with Powerware FCC 15 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)