    1 WITH ELECTRONIC INTERMITTENT PILOT IGNITION AND INST ALLA TIONS W ARNING: If the information in this manual is not followed exactly , a fire or explosion may result causing property damage, personal injury or loss of life. — Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. — W ...

  • A.O. Smith DB/DW-720-1810 - page 2

    2 FOREWORD CA UTION TEXT PRINTED OR OUTLINED IN RED CONT AINS INFORMA TION RELA TIVE TO YOUR SAFETY . PLEASE READ THOROUGHL Y BEFORE USING APPLIANCE. Detailed installation diagrams are in this manual. These diagrams will serve to provide the installer with a reference for the materials and method of piping suggested. IT IS NECESSARY THA T ALL W A T ...

  • A.O. Smith DB/DW-720-1810 - page 3

    3 W ARNING AN AMPLE SUPPL Y OF AIR MUST BE PROVIDED FOR PROPER COMBUSTION AND VENTILA TION. Minimum Clearances T o Combustibles Water Blank T op Side Side Rear V ent Front All Models 12" (305mm) 18" (457mm) 6" (155mm) 6" (155mm) 6" (155mm) Alcove CAUTION Label all wires prior to disconnection when servicing controls. Wiring ...

  • A.O. Smith DB/DW-720-1810 - page 4

    4 W ARNING Y our Dura-Max boiler is not designed to operate with a boiler inlet water temperature of less than 100 ° F (38 ° C). Colder inlet water temperatures will result in significant condensation developing on the heat exchanger . This situation can cause a corrosive environment for the heat exchanger , burners and venting resulting in prema ...

  • A.O. Smith DB/DW-720-1810 - page 5

    5 FEA TURES IMPORT ANT Only qualified personnel shall perform the initial firing of the heater . At this time the user should not hesitate to ask the individual any questions regarding the operation and maintenance of the unit. Lighting and Operating instructions are included at the rear of this manual. By using this checklist the user may be able ...

  • A.O. Smith DB/DW-720-1810 - page 6

    6 AUT OMA TIC RESET HIGH TEMPERA TURE LIMIT CONTROL CAUTION LIMIT CONTROLS ARE NOT TO BE USED AS THERMOST A TS. ALL MODELS - This limit is a safety device wired in series with the ignition system. Set the limit control dial to a minimum of 10 ° F (6 ° C) above the maximum designed system temperature. If the boiler outlet water temperature should ...

  • A.O. Smith DB/DW-720-1810 - page 7

    7 INST ALLA TION INSTRUCTIONS REQUIRED ABILITY INST ALLA TION OR SERVICE OF THIS BOILER REQUIRES ABILITY EQUIV ALENT TO THA T OF A LICENSED TRADESMAN IN THE FIELD INVOL VED. PLUMBING, AIR SUPPL Y , VENTING, GAS SUPPL Y AND ELECTRICAL WORK ARE REQUIRED. W ARNING THE INLET/OUTLET W A TER MANIFOLD ON YOUR A. O. SMITH UNIT INCORPORA TES AN "O RING ...

  • A.O. Smith DB/DW-720-1810 - page 8

    8 If the confined space is within a building of tight construction, air for combustion, ventilation, and draft hood dilution must be obtained from outdoors. When directly communicating with the outdoors or communicating with the outdoors through vertical ducts, two permanent openings, located in the aforementioned manner , shall be provided. Each o ...

  • A.O. Smith DB/DW-720-1810 - page 9

    9 W ARNING F AILURE TO CORRECT BACK DRAFTS MA Y CAUSE AIR CONT AMINA TION AND UNSAFE CONDITIONS. V ent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure. 3. CONNECTING BOILER TO A COMMON VENT Do not connect the boiler to a common vent or chimne ...

  • A.O. Smith DB/DW-720-1810 - page 10

    10 T ABLE 5 Multipliers T o Be Used W ith T able 1 When Applying The Gravity Factor T o Other Than .60 Specific Gravity Specific Specific Gravity Multiplier Gravity Multiplier .35 1.31 1.00 .78 .40 1.23 1.10 .74 .45 1.16 1.20 .71 .50 1.10 1.30 .68 .55 1.04 1.40 .66 *.60 (Nat.) 1.00 *1.50 (Prop.) .63 .65 .96 1.60 .61 .70 .93 1.70 .59 .75 .90 1.80 .5 ...

  • A.O. Smith DB/DW-720-1810 - page 11

    11 Applications of the gravity factor converts the figures given in table 1 to capacities with another gas of different specific gravity . Such application is accomplished by multiplying the capacities given in table 1 by the multipliers shown in table 5. T o determine the size of each section of gas piping in a system within the range of table 4 p ...

  • A.O. Smith DB/DW-720-1810 - page 12

    12 IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED WITH THE APPLIANCE, MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE 105 ° C WIRE OR ITS EQUIV ALENT , EXCEPT FOR THE FLAME SENSOR AND IGNITION CABLE WHICH ARE 250 ° C. SERVICING WIRING AND/OR CONTROL CAUTION Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper ...

  • A.O. Smith DB/DW-720-1810 - page 13

    13 The flow switch shall be mounted in the top opening of the reducing tee and provide adequate paddle length in the flow stream. For example in a 2" pipe installation use a 2" x 2" x 1" reducing tee. For 2" or 3" pipe use the paddle segments as supplied. For other pipe sizes (i.e. 2-1/2") trim the paddle to the p ...

  • A.O. Smith DB/DW-720-1810 - page 14

    14 Thereafter , during the heating season, lubricate the three oil cups at least once every four months. Combination heating/cooling systems or water heating (Cer-temp) systems should be lubricated every four months year-round. Use 2 or 3 teaspoonfuls in bearing oil cups, fig. 9, and 10 or 12 drops in the motor oil cups. Use No. 20 non-detergent mo ...

  • A.O. Smith DB/DW-720-1810 - page 15

    15 A system bypass should be installed as shown in fig. 10 to prevent boiler circulation starvation when the system zones call for reduced flow . This bypass may also be used with multiple boilers manifolded for reverse-return flow . The system bypass would be installed from boiler outlet to suction side of pump. Standard Dura-Max models are factor ...

  • A.O. Smith DB/DW-720-1810 - page 16

    16 NOTES: 1. BUILDING TEMPERA TURE CONTROLS SUPPLY ELECTRIC POWER T O BUILDING CIRCULA T OR. 2. MAIN FLOW SWITCH PROVES MAIN W A TER FLOW BEFORE ENERGIZING, SEQUENCING AND RESETTING CONTROLS. 3. OUTDOOR THERMOST A T REQUIRED IF BUILDING CONTROLS DO NOT PROVIDE AUTOMA TIC SHUT-DOWN OF RESET CONTROLS DURING W ARM WEA THER. ...

  • A.O. Smith DB/DW-720-1810 - page 17

    17 BYP ASS BALANCING With systems where water temperature can be expected to drop appreciably due to long standby periods, or heavy draw down, a bypass pipe of at least 1" size with a balancing cock should be installed between the boiler inlet and outlet (see fig. 10). When the system first starts, the valve should be slowly opened until the c ...

  • A.O. Smith DB/DW-720-1810 - page 18

    18 generator type boilers establish temperature rises. The deciding factor in choice of boiler temperature rise relates to the boiler inlet temperature. Boiler outlet, minus system temperature drop, is boiler inlet temperature. THE BOILER TEMPERA TURE RISE SHOULD NOT RAISE THE OUTLET TEMPERA TURE UP TO THE MAXIMUM 250 ° F (1 15 ° C) SETTING OF TH ...

  • A.O. Smith DB/DW-720-1810 - page 19

    19 FIGURE 14 NO . SUGGESTED ITEMS FOR INST ALLA TION 1. SHORT PIPE NIPPLE AND P AIR OF BOILER LOOP TEES IN PIPING BETWEEN SYSTEM SUPPL Y AND RETURN - ONE SET PER EACH BOILER 2. BOILER PIPE LOOP (See Piping Sizing Data T able 3.) 3. BOILER CIRCULA TING PUMP (See Piping Sizing Data T able 3.) 4. THERMOMETER 5. PRESSURE GAUGE 6. LOW W A TER CUT-OFF (I ...

  • A.O. Smith DB/DW-720-1810 - page 20

    20 USE ONY TYPE 105 ° C THERMOPLASTIC OR ITS EQUIV ALENT IF ANY OF THE ORIGINAL WIRES AS SUPPLIED MUST BE REPLACED. USE ONY TYPE 105 ° C THERMOPLASTIC OR ITS EQUIV ALENT IF ANY OF THE ORIGINAL WIRES AS SUPPLIED MUST BE REPLACED. BOILER CONVENTIONAL SYSTEM FIGURE 15 ONE BOILER LINEAR-TEMP SYSTEM FIGURE 16 ...

  • A.O. Smith DB/DW-720-1810 - page 21

    21 DURA-MAX - PUMP MOUNT - SINGLE ST AGE - SCHEMA TIC DIAGRAM DURA-MAX - SINGLE ST AGE FIRING - UNITED ST A TES MODELS WITH PUMP . 120 VOL T SYSTEM CONTROLLER ...

  • A.O. Smith DB/DW-720-1810 - page 22

    22 DURA-MAX - PUMP MOUNT - DUAL ST AGE - SCHEMA TIC DIAGRAM DURA-MAX - DUAL ST AGE FIRING - UNITED ST A TES MODELS WITH PUMP . 120 VOL T SYSTEM CONTROLLER ...

  • A.O. Smith DB/DW-720-1810 - page 23

    23 DURA-MAX - PUMP MOUNTED - MODULA TING - SCHEMA TIC DIAGRAM DURA-MAX - MODULA TED FIRING - UNITED ST A TES MODELS WITH PUMP . 120 VOL T SYSTEM CONTROLLER ...

  • A.O. Smith DB/DW-720-1810 - page 24

    24 DURA-MAX - SINGLE ST AGE FIRING - SCHEMA TIC DIAGRAM DURA-MAX - SINGLE ST AGE FIRING - UNITED ST A TES & CANADIAN MODELS WITHOUT PUMP . 120 VOL T SYSTEM CONTROLLER ...

  • A.O. Smith DB/DW-720-1810 - page 25

    25 DURA-MAX - DUAL ST AGE FIRING - SCHEMA TIC DIAGRAM DURA-MAX - DUAL ST AGE FIRING - UNITED ST A TES & CANADIAN MODELS WITHOUT PUMP . 120 VOL T SYSTEM CONTROLLER ...

  • A.O. Smith DB/DW-720-1810 - page 26

    26 DURA-MAX - MODULA TED FIRING - SCHEMA TIC DIAGRAM DURA-MAX - MODULA TED FIRING - UNITED ST A TES & CANADIAN MODELS WITHOUT PUMP . 120 VOL T SYSTEM CONTROLLER ...

  • A.O. Smith DB/DW-720-1810 - page 27

    27 HOT W A TER SUPPL Y APPLICA TIONS Cer-T emp 80 Recovery Systems W A TER LINE CONNECTIONS This section provides detailed installation diagrams for typical methods of application for the unit using a Cer-T emp 80 Recovery System (for one temperature water). This equipment must be protected against loss of water or loss of water flow by the install ...

  • A.O. Smith DB/DW-720-1810 - page 28

    28 ONE DURA-MAX (MODEL DW) COMMERCIAL BOILER WITH HORIZONT AL T ANK CAUTION TO PREVENT CONDENSA TION THE MINIMUM BOILER INLET TEMPERA TURE IS 100 ° F (38 ° C) IMPORT ANT SAFETY FLOW SWITCH AS SHOWN TO PROTECT THE BOILER IN CASE OF WA TER SERVICE INTERRUPTION OR CIRCULA TOR F AILURE. CAUTION PUMP MUST BE RA TED FOR SYSTEM OPERA TING TEMPERA- TURES ...

  • A.O. Smith DB/DW-720-1810 - page 29

    29 TWO DURA-MAX (MODEL DW) HOT W A TER SUPPL Y BOILERS WITH VERTICAL T ANK CAUTION TO PREVENT CONDENSA TION THE MINIMUM BOILER INLET TEMPERA TURE IS 100 ° F (38 ° C) SEE P AGE 31 FOR ADDITIONAL PIPING INFORMA TION. CAUTION PUMP MUST BE RA TED FOR SYSTEM OPERA TING TEMPERA TURE AND PRESSURE . * SAFETY RELIEF V AL VE RA TING SHOULD NOT EXCEED PRESS ...

  • A.O. Smith DB/DW-720-1810 - page 30

    30 TWO DURA-MAX (MODEL DW) HOT W A TER SUPPL Y BOILERS WITH HORIZONT AL T ANK CAUTION TO PREVENT CONDENSA TION THE MINIMUM BOILER INLET TEMPERA TURE IS 100 ° F (38 ° C) IMPORT ANT THE INST ALLA TION OF SAFETY FLOW SWITCHES AS SHOWN IS REQUIRED TO PROTECT THE BOILER IN CASE OF W A TER SERVICE INTERRUPTION OR CIRCULA TO R F AILURE. NOTE: THERMOMETE ...

  • A.O. Smith DB/DW-720-1810 - page 31

    31 FIGURE 24 MANIFOLDING OF MODEL TJV-120M & TJV-200M T ANKS NOTE: PIPE SIZES BETWEEN MANIFOLDS AND BOILER(S) TO BE SELECTED FROM THE CER-TEMP 80 DIAGRAM FOR THE HEA TER MODEL TO BE INST ALLED. ALL PIPING FROM TEES TO BE EQUIDIST ANT TO T ANKS. INST ALL IN ACCORDANCE WITH ALL LOCAL CODES. PRESSURE RELIEF V AL VE RA TING SHOULD NOT EXCEED PRESSU ...

  • A.O. Smith DB/DW-720-1810 - page 32

    32 ST ART-UP AND OPERA TING INSTRUCTIONS W ARNING After placing boiler into operation, the ignition system safety shutoff device must be tested by the following test method. 1. Reset Manual High T emperature Safety Limit Control (High Limit) to the lowest setting. (See figures 3 or 4, pages 5 or 6). 2. Reset System Controller to maximum setting, ca ...

  • A.O. Smith DB/DW-720-1810 - page 33

    33 LIGHTING AND OPERA TING INSTRUCTIONS WARNING: HOT W A TER CAN PRODUCE 3rd DEGREE BURNS IN 6 SECONDS A T 140 ° F . (60 ° C). IN CASE OF POWER F AILURE DO NOT A TTEMPT TO OPERA TE BOILER. IMPROPER INST ALLA TION, ADJUSTMENT , AL TERA TION, SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE. REFER TO THE USER'S ...

  • A.O. Smith DB/DW-720-1810 - page 34

    34 INTERNAL CONT AMINANTS The system must be internally cleaned and flushed after a new or replacement unit has been installed to remove contaminants that may have accumulated during installation. This is doubly important when a replacement unit is installed into an existing system where Stop Leak or other boiler additives have been used. All syste ...

  • A.O. Smith DB/DW-720-1810 - page 35

    35 1. Remove main burners from unit. 2. Check that burner venturi and ports are free of foreign matter . 3. Clean burners with bristle brush and/or vacuum cleaner 3/4" DO NOT distort burner ports or pilot location. 4. Reinstall burners in unit. Making sure front and rear of burners are installed correctly in burner support brackets. Also check ...

  • A.O. Smith DB/DW-720-1810 - page 36

    36 CHECKING HONEYWELL S8600H OR S8610M (NA T . GAS) INTERMITTENT IGNITION CONTROLS NO SP ARK A T PILOT BURNER NO Replace ignition module Is voltage (24 V ac) across the 24 V terrminals on module during “ call for heat ” ? YES Is voltage (24 V ac) across the PV & MV/PV terminals on “ call for heat ” ? NO NOTE: S8610M will automatically r ...

  • A.O. Smith DB/DW-720-1810 - page 37

    37 SP ARK A T PILOT BURNER BUT PILOT WILL NOT LIGHT Ensure all manual shutoff valves are fully open; All filters are clean; All gas connections are gas tight; Pilot tubing is not damaged, obstructed or kinked; and pilot orifice is unclogged. Check for air in gas line, purge (bleed) line if necessary . NO Attach wires firmly. Are the wires securely ...

  • A.O. Smith DB/DW-720-1810 - page 38

    38 PILOT BURNER LIGHTS BUT MAIN BURNER DOES NOT LIGHT Correct the situation by consulting N O the installation or user ’ s manual Does the pilot flame cover 3/8 ° to 1/2" on how to adjust pilot flame. (10 mm to 12 mm) of igniter/sensor rod? YES Replace ignition NO NO module. Is voltage (24 V ac) across Does spark stay on for more than 30 se ...

  • A.O. Smith DB/DW-720-1810 - page 39

    39 CAUTION DO NOT USE A NYLON BRUSH OR OTHER ST A TIC CREA TING MA TERIAL TO CLEAN DUST AND CARBON DEPOSITS FROM HEA TING SURFACES AND VENT . SUCH DEPOSITS ARE FLAMMABLE AND MA Y BE IGNITED BY ST A TIC ELECTRICITY . USE A MET AL BRUSH TO MINIMIZE THE DANGER OF EXPLOSION 1. Turn of f the electrical power , main manual gas shutoff and pilot valves. ? ...

  • A.O. Smith DB/DW-720-1810 - page 40

    40 The time between cleaning will vary from two to six months depending upon water conditions and usage. A change of approximately 5 ° F in the normal temperature rise through the boiler is usually an indication that scale should be removed. For long life, copper or brass is recommended for all valves, pipe and fittings used between gate valves ? ...

  • A.O. Smith DB/DW-720-1810 - page 41

    41 DURA-MAX LIMITED W ARRANTY A. O. Smith Corporation, the warrantor, extends the following LIMITED W ARRANTY to the owner of this hydronic boiler: 1. If within TEN years after initial installation of the boiler , the heat exchanger shall prove upon examination by the warranto r to be defective in material or workmanship, the warrantor , at his opt ...

  • A.O. Smith DB/DW-720-1810 - page 42

    42 ...

  • A.O. Smith DB/DW-720-1810 - page 43

    43 ...

  • A.O. Smith DB/DW-720-1810 - page 44

    44 REPLACEMENT P ARTS 5621 W . 1 15TH STREET , ALSIP , IL 60803 PHONE: 800-433-2545 F AX: 800-433-2515 ww w .hotwater .com E-Mail: parts@hotwater .com ...

Manufacturer A.O. Smith Category Boiler

Documents that we receive from a manufacturer of a A.O. Smith DB/DW-720-1810 can be divided into several groups. They are, among others:
- A.O. Smith technical drawings
- DB/DW-720-1810 manuals
- A.O. Smith product data sheets
- information booklets
- or energy labels A.O. Smith DB/DW-720-1810
All of them are important, but the most important information from the point of view of use of the device are in the user manual A.O. Smith DB/DW-720-1810.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals A.O. Smith DB/DW-720-1810, service manual, brief instructions and user manuals A.O. Smith DB/DW-720-1810. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product A.O. Smith DB/DW-720-1810.

A complete manual for the device A.O. Smith DB/DW-720-1810, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use A.O. Smith DB/DW-720-1810 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of A.O. Smith DB/DW-720-1810.

A complete A.O. Smith manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual A.O. Smith DB/DW-720-1810 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the A.O. Smith DB/DW-720-1810, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the A.O. Smith DB/DW-720-1810, that we can find in the current document
3. Tips how to use the basic functions of the device A.O. Smith DB/DW-720-1810 - which should help us in our first steps of using A.O. Smith DB/DW-720-1810
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with A.O. Smith DB/DW-720-1810
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of A.O. Smith DB/DW-720-1810 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning A.O. Smith DB/DW-720-1810?

Use the form below

If you did not solve your problem by using a manual A.O. Smith DB/DW-720-1810, ask a question using the form below. If a user had a similar problem with A.O. Smith DB/DW-720-1810 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)