Manual Emerson Process Management CSI 9420

148 pages 32.96 mb
Download

Go to site of 148

Summary
  • Emerson Process Management CSI 9420 - page 1

    Reference Manual MHM-97408, Rev 15 January 2015 CSI 9420 Wireless Vibration Transmitter Reference Manual ...

  • Emerson Process Management CSI 9420 - page 2

    Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure to thoroughly understand the contents before installing, using, or maintaining this product. If you need product support, contact: Global Service Center (GSC) Phone: 1-800-833-8314 1-877-812-4036 Email: mhm.custserv@emers ...

  • Emerson Process Management CSI 9420 - page 3

    Copyright © 2015 by Emerson Process Management. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form by any means without the written permission of Emerson Process Management. Disclaimer This manual is provided for informational purpo ...

  • Emerson Process Management CSI 9420 - page 4

    ...

  • Emerson Process Management CSI 9420 - page 5

    Contents Chapter 1 Introduction ...................................................................................................................1 1.1 Safety messages .......................................................................................................................... 1 1.2 Overview ........................................... ...

  • Emerson Process Management CSI 9420 - page 6

    Chapter 4 Operation and maintenance ......................................................................................... 87 4.1 Verify status and operation ........................................................................................................ 87 4.2 Power module maintenance .................................................... ...

  • Emerson Process Management CSI 9420 - page 7

    1 Introduction Topics covered in this chapter: • Safety messages • Overview • Considerations • Return of materials 1.1 Safety messages Instructions in this manual may require special precautions to ensure the safety of the personnel performing the operations. Refer to the following safety messages before performing an operation preceded by ...

  • Emerson Process Management CSI 9420 - page 8

    1.2 Overview The manual This Reference Manual applies to the 2.4 GHz WirelessHART version of the CSI 9420 for use with the Smart Power Module unless otherwise specified. It is optimized for use with the most recent device and software revisions (AMS Suite: Machinery Health Manager v5.61 and AMS Suite: Intelligent Device Manager v12.5). Use this man ...

  • Emerson Process Management CSI 9420 - page 9

    Device revision information Revision Current level Description Universal 7 This is the HART version the transmitter supports. Field device (1) 4 This is the major revision of the transmitter and corresponds with a major interface release. When using AMS Device Manager, this revision can be found on the screen title. Software 6 This is the current s ...

  • Emerson Process Management CSI 9420 - page 10

    Revision numbers in AMS Device Manager Figure 1-2: Introduction 4 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 11

    1.3 Considerations General Electrical vibration sensors, such as accelerometers, produce low-level signals proportional to their sensed vibration. With simple HART configuration, the transmitter converts the low-level sensor signal to a wireless-enabled signal. Commissioning The transmitter can be commissioned before or after installation. You can ...

  • Emerson Process Management CSI 9420 - page 12

    Environmental The transmitter operates within specifications for ambient temperatures between –40°F and 185°F (–40°C and 85°C). Verify that the operating environment of the transmitter is consistent with the appropriate hazardous location certifications. 1.4 Return of materials You may need to ship the CSI 9420 to an Emerson Product Service ...

  • Emerson Process Management CSI 9420 - page 13

    2 Configuration Topics covered in this chapter: • Configuration overview • Configuration with a Field Communicator • Configuration with AMS Device Manager • Configuration with AMS Machinery Manager 2.1 Configuration overview You can configure the CSI 9420 either prior to installation or after the device is installed at the measurement locat ...

  • Emerson Process Management CSI 9420 - page 14

    6. Specify the units (English, metric, or SI) that will be used for each parameter. By default, units are set to English, unless the device is shipped to Japan. 7. Specify which measurements (velocity, temperature, etc.) correspond to the process variables PV, SV, TV, and QV. By default, PV is the Overall Velocity on sensor 1, SV is the PeakVue mea ...

  • Emerson Process Management CSI 9420 - page 15

    2.1.1 Connect to a wired HART interface Unless the CSI 9420 is purchased pre-configured from the factory, you must connect it to a wired HART interface. This is to define device credentials that allow the device to communicate on your wireless network. You can also define other device configurations such as sensor type and alert thresholds at this ...

  • Emerson Process Management CSI 9420 - page 16

    Field Communicator and power module connection Figure 2-2: 3. Configure using a Field Communicator, AMS Device Manager, or any HART-enabled host. Press Send to send configuration changes to the transmitter. The CSI 9420 enters “HART Listen” mode for communication on the wired interface. HART Listen is displayed on the optional LCD, if it is ins ...

  • Emerson Process Management CSI 9420 - page 17

    4. When configuration is complete over the wired HART interface, disconnect the transmitter from the communication wires to re-establish wireless communication. This may take several minutes. 2.1.2 Set the wireless network configuration This enables the transmitter to communicate with the Smart Wireless Gateway and with other systems. This is the w ...

  • Emerson Process Management CSI 9420 - page 18

    2.1.3 Configuration options The CSI 9420 configuration options control the following operations: • How measurement results are reported and how often are they reported • The number and type of sensors installed • How and when alerts are generated Table 2-1 shows the default device configuration. You can change these configurations from AMS De ...

  • Emerson Process Management CSI 9420 - page 19

    2.1.4 Sensor configuration The CSI 9420 can be installed with two accelerometers, or with one accelerometer with an embedded temperature sensor. Table 2-2 shows the possible sensor configurations and variable mappings. Possible sensor configurations and variable mappings Table 2-2: Dynamic process variables Available process variables based on sens ...

  • Emerson Process Management CSI 9420 - page 20

    2.1.5 Measurement parameter units Table 2-3 shows the measurement parameters and available units that can be configured for each parameter. Measurement parameter units Table 2-3: Parameter Units Velocity (Overall 1, Overall 2) mm/s RMS in/s RMS PeakVue maximum value (PeakVue 1, PeakVue 2) m/s 2 g’s Temperature (Temperature 1, Ambient) °C °F Sen ...

  • Emerson Process Management CSI 9420 - page 21

    Default alert thresholds for vibration (continued) Table 2-4: Alert limits Advise Maintenance Failed Default value Report notification Default value Report notification Default value Report notification Sensor temperature 65°C 149°F Yes 75°C 167°F Yes 85°C 185°F Yes Bias (sensor 1, 2) – – – – Above: >3V Below: <2V Yes* Ambient t ...

  • Emerson Process Management CSI 9420 - page 22

    Default levels for configurable device alerts Table 2-6: Parameter Advisory Maintenance Failed Level Enabled Level Enabled Level Enabled Accelerometer Bias N/A N/A N/A N/A < 2 V or > 3 V Yes Supply Voltage < 6.0 V No < 5.7 V Yes < 5.3 V Yes Notes • The supply voltage measurement is made under load conditions. The supply voltage may ...

  • Emerson Process Management CSI 9420 - page 23

    2.1.9 Minimize power consumption The primary way to minimize power consumption is to reduce the publish rate. Two other configuration settings that affect power consumption are: • LCD (Liquid Crystal Display) • PowerSave mode LCD Disable the LCD after installation is complete if it is not required during normal operation. It is neither necessar ...

  • Emerson Process Management CSI 9420 - page 24

    Valid settings for the PowerSave Skip Multiplier range from 1X to 24X. In order to extend power module life, it should only be combined with a long update rate such as 60 minutes (54 minutes may be optimal for older versions of the CSI 9420). When this value is set to 1X, the CSI 9420 acquires a new reading at the update rate. A PowerSave Skip Mult ...

  • Emerson Process Management CSI 9420 - page 25

    2.1.11 Remove the power module The CSI 9420 device is powered whenever the power module is installed. To avoid depleting the power module, remove it when the device is not in use. After you have configured the sensors and network, disconnect the communication leads, remove the power module (if the device is not already installed), and replace the t ...

  • Emerson Process Management CSI 9420 - page 26

    Field Communicator menu tree for CSI 9420, one accelerometer: 1 of 4 Figure 2-4: Configuration 20 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 27

    Field Communicator menu tree for CSI 9420, one accelerometer: 2 of 4 Figure 2-5: Configuration MHM-97408, Rev 15 21 ...

  • Emerson Process Management CSI 9420 - page 28

    Field Communicator menu tree for CSI 9420, one accelerometer: 3 of 4 Figure 2-6: Configuration 22 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 29

    Field Communicator menu tree for CSI 9420, one accelerometer: 4 of 4 Figure 2-7: Configuration MHM-97408, Rev 15 23 ...

  • Emerson Process Management CSI 9420 - page 30

    Field Communicator menu tree for CSI 9420, one accelerometer with temperature: 1 of 4 Figure 2-8: Configuration 24 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 31

    Field Communicator menu tree for CSI 9420, one accelerometer with temperature: 2 of 4 Figure 2-9: Configuration MHM-97408, Rev 15 25 ...

  • Emerson Process Management CSI 9420 - page 32

    Field Communicator menu tree for CSI 9420, one accelerometer with temperature: 3 of 4 Figure 2-10: Configuration 26 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 33

    Field Communicator menu tree for CSI 9420, one accelerometer with temperature: 4 of 4 Figure 2-11: Configuration MHM-97408, Rev 15 27 ...

  • Emerson Process Management CSI 9420 - page 34

    Field Communicator menu tree for CSI 9420, two accelerometers: 1 of 4 Figure 2-12: Configuration 28 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 35

    Field Communicator menu tree for CSI 9420, two accelerometers: 2 of 4 Figure 2-13: Configuration MHM-97408, Rev 15 29 ...

  • Emerson Process Management CSI 9420 - page 36

    Field Communicator menu tree for CSI 9420, two accelerometers: 3 of 4 Figure 2-14: Configuration 30 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 37

    Field Communicator menu tree for CSI 9420, two accelerometers: 4 of 4 Figure 2-15: Configuration MHM-97408, Rev 15 31 ...

  • Emerson Process Management CSI 9420 - page 38

    2.2.1 Field Communicator fast key sequences The following fast key sequences assume that you are using a Rev 4 DD. Press Send to save the changes to the device. CSI 9420 network configuration Table 2-7: Key sequence Menu items 2, 2, 1 (Manual Setup) Network ID Broadcast Info Join Device to Network Configure Publishing Configure Update Rate Transmit ...

  • Emerson Process Management CSI 9420 - page 39

    CSI 9420 common fast key sequences (continued) Table 2-8: Function Key sequence Menu items Power options 2, 2, 3, 2 (Manual Setup) Power Source MHM Access Control 2, 2, 3, 6 (Manual Setup) MHM Access Control Supply power to sensor 2, 1, 5 (Guided Setup) Sensor Power Enable Configure variable mapping 2, 1, 2 (Guided Setup) Configure Variable Mapping ...

  • Emerson Process Management CSI 9420 - page 40

    2.3 Configuration with AMS Device Manager 2.3.1 Configure wireless network credentials in AMS Device Manager Prerequisites Before performing operations in AMS Device Manager, first scan the CSI 9420 with a wired HART modem. Right-click the HART Modem icon in Device Explorer and select Scan All Devices . Note Configuring the wireless network is only ...

  • Emerson Process Management CSI 9420 - page 41

    2.3.2 Right-click menu The right-click menu of the CSI 9420 device in AMS Device Manager provides a quick link to the Configure, Compare, Service Tools, and Overview windows, as well as to other context menus available for the device. This document only discusses the Overview, Configure, and Service Tools windows; for more information on the other ...

  • Emerson Process Management CSI 9420 - page 42

    Overview Overview window Figure 2-17: The Overview window provides a glimpse of the status of the CSI 9420, including the primary purpose variables associated with it. You can also access the following shortcuts from this page: • Device Information • Configure Sensors • Join Device to Network • Acquire New Measurement Configuration 36 MHM-9 ...

  • Emerson Process Management CSI 9420 - page 43

    Device Information From the Overview window, click Device Information to display relevant device information. Device Information window Figure 2-18: Click the Identification tab to display the device tag, long tag, device type, serial number, identifier, and description. Click the Revisions tab to display the universal, field device, software, hard ...

  • Emerson Process Management CSI 9420 - page 44

    Configure Sensors From the Overview window, click Configure Sensors to display installed sensors and current sensor configurations. Sensor Configuration window Figure 2-19: Click the Select Sensor Configuration drop-down to select a sensor configuration to apply to the installed sensors. Configuration 38 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 45

    Join Device to Network From the Overview window, click Join Device to Network to enter network identifiers and join keys that will enable the transmitter to join a wireless network. Join Device to Network window Figure 2-20: Configuration MHM-97408, Rev 15 39 ...

  • Emerson Process Management CSI 9420 - page 46

    Acquire New Measurement From the Overview window, click Acquire New Measurement to display measurement statistics for Velocity, PeakVue, bias, and sensor temperature for installed sensors. This also displays supply voltage and ambient temperature information for the transmitter. Measurement Statistics window Figure 2-21: Configuration 40 MHM-97408, ...

  • Emerson Process Management CSI 9420 - page 47

    Configure Configure window Figure 2-22: The Configure window lets you configure device settings. Important To be able to edit configuration settings, select Current in the Time drop-down menu at the bottom of the screen. Guided Setup Guided Setup lets you configure device settings in a guided step-by-step process. Click Configure Sensors to display ...

  • Emerson Process Management CSI 9420 - page 48

    Note Sensor Power Enable is only available when the device is connected to AMS Device Manager using a USB or serial HART modem and when the device is connected to a Field Communicator. This feature is not available when the device is connected to AMS Device Manager using a WirelessHART connection. Click Join Device to Network to enter network ident ...

  • Emerson Process Management CSI 9420 - page 49

    Click Configure Update Rate to set how often the device acquires and reports new measurements (update rate) and to specify the number of times the transmitter skips data acquisitions between updates to the gateway (PowerSave Skip Multiplier). Click Default Burst Configuration to reset the burst configuration to default values. Click Refresh Effecti ...

  • Emerson Process Management CSI 9420 - page 50

    Click the General Settings tab to display or edit general transmitter settings. General Settings tab Figure 2-25: Click the LCD Mode drop-down to enable or disable the LCD, or to set it to troubleshooting mode. Click the Power Source drop-down to select the transmitter power source. Select the units for measurement variables from the Overall Veloci ...

  • Emerson Process Management CSI 9420 - page 51

    Click the Mapping tab to specify which measurements are reported as the Primary, Secondary, Third, and Fourth variables. Mapping tab Figure 2-26: Configuration MHM-97408, Rev 15 45 ...

  • Emerson Process Management CSI 9420 - page 52

    Click the Device Information tab to display the device tag, long tag, device type, serial number, device identifier, and description, and to display the universal, field device, software, hardware, and DD revision numbers. Device Information tab Figure 2-27: Configuration 46 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 53

    Click the License tab to display installed licensable features such as the Advanced Diagnostics application. License tab Figure 2-28: Click Configure License to configure/change installed licenses. Configuration MHM-97408, Rev 15 47 ...

  • Emerson Process Management CSI 9420 - page 54

    Alert Setup Alert Setup lets you configure the upper and lower range values and alarm limits for Overall Velocity, PeakVue, Bias, Sensor Temperature, Ambient Temperature, and Supply Voltage. Alert Setup Figure 2-29: Click the corresponding sensor/device variable tab and select the Report Advisory , Report Maintenance , or Report Failure check boxes ...

  • Emerson Process Management CSI 9420 - page 55

    Service Tools Service Tools window Figure 2-30: The Service Tools window displays alert conditions. These include hardware and software malfunctions or parameters with values beyond specifications. Alerts Click Alerts to display active alerts for the device. Configuration MHM-97408, Rev 15 49 ...

  • Emerson Process Management CSI 9420 - page 56

    Variables Click Variables to display graphical gauges of sensor and device variables. Variables Figure 2-31: Click the Mapped Variables tab to display graphical gauges of variables and their mappings. Click the Sensor Variables tab to display graphical gauges of the variables for each connected sensor. Click the Device Variables tab to display grap ...

  • Emerson Process Management CSI 9420 - page 57

    Trends Click Trends to display hour-long trends for each of the four measurement variables (PV, SV, TV, and QV). Trends Figure 2-32: Note The trend plots begin when Trends is selected, and continue to build as long as this remains selected. Configuration MHM-97408, Rev 15 51 ...

  • Emerson Process Management CSI 9420 - page 58

    Spectra Click Spectra to display spectral and analysis parameter data and to configure spectral data acquisition settings. You can import spectral data to AMS Machinery Manager for further analysis. Note You must have the Advanced Diagnostics application license to view this feature. For more information on the Advanced Diagnostics application, see ...

  • Emerson Process Management CSI 9420 - page 59

    Click Velocity Spectrum x and PeakVue Spectrum x to display spectral plots of the latest acquired data for Velocity and PeakVue for connected sensors. Velocity spectrum Figure 2-34: Configuration MHM-97408, Rev 15 53 ...

  • Emerson Process Management CSI 9420 - page 60

    PeakVue spectrum Figure 2-35: Configuration 54 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 61

    Click the Energy Bands tab to display calculated energy band values. Energy Bands tab Figure 2-36: Configuration MHM-97408, Rev 15 55 ...

  • Emerson Process Management CSI 9420 - page 62

    Communications Click Communications to display network join status information. Communications Figure 2-37: Click the Join Mode drop-down to select when the transmitter attempts to join a network. Configuration 56 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 63

    Maintenance Click Maintenance to manage the device maintenance and log settings. Maintenance Figure 2-38: Click Routine Maintenance tab > Advertise to New Wireless Devices to enable the gateway to search for new wireless devices on the network. This helps new devices join the network faster. Click the Event History tab to display transmitter eve ...

  • Emerson Process Management CSI 9420 - page 64

    2.4 Configuration with AMS Machinery Manager AMS Machinery Manager can change the data acquisition settings for CSI 9420 devices. If the device is not commissioned in a HART DCS host (DeltaV or Ovation), you can allow AMS Machinery Manager to configure settings to provide easier access. You need to configure MHM Access Control in AMS Device Manager ...

  • Emerson Process Management CSI 9420 - page 65

    Other configurable parameters for the energy band include: • Effective Fmax for the thumbnail spectrum — For the velocity thumbnail spectrum, AMS Machinery Manager uses 100% as the default Fmax. • True Fmax for PeakVue — This allows the monitoring of a slower machine with PeakVue. Choosing 1000 Hz Fmax uses about 1.6 seconds of data to prod ...

  • Emerson Process Management CSI 9420 - page 66

    When using a power module, the maximum recommended time-based acquisition rates are: • Thumbnail spectrum — Once per day • High-resolution spectrum — Once every two weeks • Waveform — Once per month On-demand data collection is not expected to have a significant impact on power module life. If you are using a power module, keep in mind ...

  • Emerson Process Management CSI 9420 - page 67

    Verify device revision Figure 2-39: Note If you have an older device revision, a factory upgrade may be possible in some cases. Contact Product Support for more information. 3. Right-click the CSI 9420 device and select Configure . 4. From the Configure window, select Current from the Time drop-down menu. 5. Click Manual Setup > License tab > ...

  • Emerson Process Management CSI 9420 - page 68

    Enable Advanced Diagnostics application (alternative) If your CSI 9420 is not installed on a wireless network, you can perform the upgrade using either a HART modem or a 375 or 475 Field Communicator. WARNING! The hazardous area rating available with the CSI 9420 does not permit either of the following operations to be performed in a hazardous area ...

  • Emerson Process Management CSI 9420 - page 69

    To make changes to a CSI 9420, AMS Device Manager settings must allow AMS Machinery Manager to make changes. Note In some cases, if the gateway device is connected to a HART host such as DeltaV, any changes made using the AMS Machinery Manager software will be rejected. In such cases, contact your DeltaV administrator or an instrument technician wh ...

  • Emerson Process Management CSI 9420 - page 70

    • You want to limit how often you collect and store data. Consider the following example in which a CSI 9420 is configured for a 60 minute update rate and to request the PeakVue spectrum whenever the PeakVue value exceeds 10 g's. If the measurement stays above 10 g's for an extended period of time, AMS Machinery Manager, without a publi ...

  • Emerson Process Management CSI 9420 - page 71

    How to apply a publishing policy You can apply a publishing policy globally to a Data Import Server or individually to each gateway device. • Apply a publishing policy to a Data Import Server to affect each gateway monitored by that server. • Apply a publishing policy to one gateway device to affect only the CSI 9420 transmitters connected to t ...

  • Emerson Process Management CSI 9420 - page 72

    CSI 9420 publishing policy menu Figure 2-40: Recommended (default) publishing policy settings Table 2-11: Network size Interval (D.HH:MM) Gateway credits Device credits Notes N N/4 days (but never less than 14.00:00) N*8 8 High-resolution data limited only to 4 devices per day with most frequent collection interval of 2 weeks for 1-64 devices. Afte ...

  • Emerson Process Management CSI 9420 - page 73

    Maximum network size when collecting velocity and PeakVue spectra only (no waveforms)* Table 2-12: Network size Interval (D.HH:MM) Gateway credits Device credits 12 1.00:00 48 4 25 3.12:00 100 50 7.00:00 200 100 30.00:00 400 *Set-up for average velocity spectrum and PeakVue spectrum. Maximum network size when collecting velocity spectrum and PeakVu ...

  • Emerson Process Management CSI 9420 - page 74

    2.4.5 Waveform or spectrum time The amount of time required to get a waveform or spectrum varies significantly depending on the network size, network topology, and other installed applications competing for wireless bandwidth. Demand-based acquisitions use a special high-bandwidth mechanism that can transfer a 4096-point waveform in less than 5 min ...

  • Emerson Process Management CSI 9420 - page 75

    3 Setup Topics covered in this chapter: • Power the CSI 9420 • Sensors • Liquid Crystal Display (LCD) • Ground the transmitter 3.1 Power the CSI 9420 Prerequisites Install the Smart Wireless Gateway and ensure it is functioning properly before installing the CSI 9420 and all other wireless devices. Procedure 1. Remove the transmitter back c ...

  • Emerson Process Management CSI 9420 - page 76

    Tip Power up wireless devices in order of proximity to the Smart Wireless Gateway, beginning with the closest device to the gateway. This results in a simpler and faster network installation. 3.2 Sensors Each of the CSI 9420 signal inputs uses accelerometers to make vibration measurements. The term "sensor" applies to both an acceleromete ...

  • Emerson Process Management CSI 9420 - page 77

    CAUTION! Although the integral cable has a built-in strain relief, do not use excessive force when pulling the cable. Do not exert more than 5-lb of force directly on the sensor connection during installation. If possible, secure the cable to the machine near the point of sensor installation. CAUTION! Do not exert more than 5-lb pull force directly ...

  • Emerson Process Management CSI 9420 - page 78

    Spot face or end mill tool Figure 3-1: Attachment tools and supplies • 40-200 inch-lb torque wrench with 1/8 in. hex bit Suggested vendor: Grainger (P/N 4YA74) Description: 3/8" drive inch-lb torque wrench. You can substitute with any torque wrench with a range of 40 to 70 inch-lb and less than 5 inch-lb increments. • 1/4-28" taps and ...

  • Emerson Process Management CSI 9420 - page 79

    3.2.4 Prepare the sensor mount Stud mount (preferred) Stud mount provides increased reliability, improved frequency response, and increased signal sensitivity. Prerequisites The mounting location must provide a flat surface of at least 0.5 in. (12.7 mm) in diameter and a case thickness exceeding 0.4 in. (10.2 mm). If this is not possible, use the e ...

  • Emerson Process Management CSI 9420 - page 80

    3.2.5 Attach the sensors Figure 3-3 shows a typical accelerometer, mounting stud, and mounting pad used with the CSI 9420. The mounting pad is only necessary when doing an epoxy mount. Accelerometer, mounting stud, and optional mounting pad Figure 3-3: A. accelerometer B. mounting stud (included with the accelerometer) C. mounting pad Prerequisites ...

  • Emerson Process Management CSI 9420 - page 81

    Apply thread locker onto mounting location Figure 3-4: 3. Using a 1/8 in. Allen key (English mounting stud) or a 4 mm Hex Allen key (metric mounting stud), loosely screw the mounting stud into the mounting location. The mounting location is the machine surface when using stud mount and the mounting pad when using epoxy mount. 4. Using a torque wren ...

  • Emerson Process Management CSI 9420 - page 82

    For stud mount: If the mounting stud is still not seated against the spot face after you apply the correct torque force, it indicates that the tap hole is not deep enough. Remove the mounting and tap a deeper hole. 5. Apply a thin coat of semi-permanent thread locker to the threads on the sensor housing. 6. Place the sensor onto the mounting stud a ...

  • Emerson Process Management CSI 9420 - page 83

    3.2.6 Secure the sensor cables WARNING! All wiring should be installed by a trained and qualified electrician. Wiring must conform to all applicable local codes and regulations. Follow local codes and regulations regarding wire type, wire size, color codes, insulation voltage ratings, and any other standards. Using an appropriately sized cable clam ...

  • Emerson Process Management CSI 9420 - page 84

    3.2.7 Conduit installation guidelines WARNING! All wiring should be installed by a trained and qualified electrician. Wiring must conform to all applicable local codes and regulations. • Adhere to IEEE 1100 specifications for grounding. • Do not exceed a 40 percent fill for conduits. • Route the conduit away from power trays using these guide ...

  • Emerson Process Management CSI 9420 - page 85

    Connecting one sensor Figure 3-8: A. Connector 1 – red wire B. Connector 2 – white wire C. Connector 3 – blank D. Connector 4 – black wire Setup MHM-97408, Rev 15 79 ...

  • Emerson Process Management CSI 9420 - page 86

    Connecting two sensors Figure 3-9: A. Connector 1 – two red wires, one from each accelerometer B. Connector 2 – white wire from one accelerometer C. Connector 3 – white wire from other accelerometer D. Connector 4 – two black wires, one from each accelerometer Setup 80 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 87

    Connecting one sensor (accelerometer with temperature) Figure 3-10: A. Connector 1 – red wire B. Connector 2 – white wire C. Connector 3 – green wire (temperature wire) D. Connector 4 – black wire 3. Connect the power module or external DC power. 4. Verify the connection through the status on the LCD (if available). 5. Reattach and tighten ...

  • Emerson Process Management CSI 9420 - page 88

    3.3 Liquid Crystal Display (LCD) Note If you purchased the CSI 9420 without the optional LCD, and you want to add an LCD, an upgrade kit is available (P/N A9400LCDM, A9400LCD-SS, or 00753-9004-0002). Contact Product Support for more information. 3.3.1 Install the LCD WARNING! While you can perform this modification for either CSI 9420 devices that ...

  • Emerson Process Management CSI 9420 - page 89

    If the LCD pins are inadvertently removed from the interface board, carefully re- insert the pins before snapping the LCD in place. After installation, you can remove the LCD by squeezing the two tabs and pulling gently. You can then rotate it in 90-degree increments and snap it back in place. 3. Attach the LCD cover. Use a strapping wrench to tigh ...

  • Emerson Process Management CSI 9420 - page 90

    • Periodic Display – Use this setting to show only relevant data. This setting does not extend the wake cycle. • Troubleshooting Display – Use this setting when troubleshooting the transmitter. • Off – Use this setting to disable the LCD. Enable the LCD using AMS Device Manager 1. Launch AMS Device Manager and locate the network where t ...

  • Emerson Process Management CSI 9420 - page 91

    Use a strapping wrench to tighten the cover until it will no longer turn and the black O-ring is no longer visible. Refer to Figure 3-12 for an illustration on how to properly seal the end cap. 3.4 Ground the transmitter The transmitter operates with the housing, either floating or grounded. However, the extra noise in floating systems affects many ...

  • Emerson Process Management CSI 9420 - page 92

    Setup 86 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 93

    4 Operation and maintenance Topics covered in this chapter: • Verify status and operation • Power module maintenance 4.1 Verify status and operation Verify the status and operation of the CSI 9420 through the following: • LCD • Field Communicator • Smart Wireless Gateway LCD If the LCD is installed and enabled, it should display the measu ...

  • Emerson Process Management CSI 9420 - page 94

    For more information on LCD screen messages, refer to Appendix C . Field Communicator You can verify the status of the CSI 9420 and configure it using a Field Communicator. Table Table 4-2 shows the fast key sequences you can use to configure and connect the CSI 9420 to a network. See the Section 2.2 and Section 2.2.1 for more information on the Fi ...

  • Emerson Process Management CSI 9420 - page 95

    The Explorer page displays the transmitter tag name, PV, SV, TV, QV, time of last update, and update rate (burst rate). A green status indicator means that the device is working properly. A red indicator means there is a problem with either the device or its communication path. Note It is normal for the CSI 9420 to have a red “X” on the screen ...

  • Emerson Process Management CSI 9420 - page 96

    4.2 Power module maintenance The Smart Power Module contains two “C” size primary lithium/thionyl chloride cells. Each cell contains approximately 2.5 grams of lithium, for a total of 5 grams in each pack. Actual power module life can vary dramatically based on operating parameters—including whether high-resolution data such as vibration wave ...

  • Emerson Process Management CSI 9420 - page 97

    5 Velocity, PeakVue, and temperature Topics covered in this chapter: • Overall Velocity • PeakVue • Temperature 5.1 Overall Velocity The Overall Velocity measurement provides a summation of the low-frequency vibration energy, which indicates fault conditions such as imbalance, misalignment, looseness, and late-stage bearing problems. The CSI ...

  • Emerson Process Management CSI 9420 - page 98

    Velocity waveform Figure 5-1: PeakVue waveform Figure 5-2: Velocity, PeakVue, and temperature 92 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 99

    While PeakVue is very useful for providing an early indication of impact-related faults in rolling-element bearings, there are many general applications where a lower-frequency measurement is more appropriate. Also, virtually all vibration analysts are very familiar with the Overall Velocity measurement and use it as part of their existing vibratio ...

  • Emerson Process Management CSI 9420 - page 100

    Service factor multiplier (continued) Table 5-1: Machinery type Service factor Turbine, Turbine Generator, Centrifugal Compressor 1.6 Miscellaneous Equipment 2.0 Figure 5-3 shows the Overall Velocity thresholds for root-mean-square (RMS) velocity in units of inches per second. Particularly, in digital acquisition systems, it is customary to measure ...

  • Emerson Process Management CSI 9420 - page 101

    Figure 5-4 shows an example of a typical formula for calculating the advisory alert level for PeakVue. PeakVue advisory levels Figure 5-4: These are the equations that govern this curve: These, however, are generic limits. They are provided as a starting point and these values (for a 3600 RPM machine) are used as the default alert thresholds by the ...

  • Emerson Process Management CSI 9420 - page 102

    Note The appropriate alerts for a given machine will be a function of its design, service, and turning speed. Utilizing the embedded PeakVue technology, the CSI 9420 identified developing problems at a couple of test sites during early field trials. In both cases, the problem was not visible with conventional low-frequency analysis. The following e ...

  • Emerson Process Management CSI 9420 - page 103

    The defective bearing was removed and Figure 5-7 shows the developing problem that was the source of the impacting. After replacing the bearing, the PeakVue vibration is significantly reduced, as shown in Figure 5-8 , indicating that the problem has been resolved. Defective bearing Figure 5-7: Velocity, PeakVue, and temperature MHM-97408, Rev 15 97 ...

  • Emerson Process Management CSI 9420 - page 104

    Motor - OH after the bearing is replaced (PeakVue) Figure 5-8: 5.3 Temperature The levels at which to set temperature alerts depend on a number of factors including the specific process, the operating environment, and the characteristics of the equipment being monitored. This section provides some generic guidelines, given some knowledge of the var ...

  • Emerson Process Management CSI 9420 - page 105

    5.3.1 Relative temperature monitoring The recommended generic guidelines for setting the thresholds based on the relative change are: T Advise = 10°C increase T Maintenance = 15°C increase T Failed = 20°C increase Assuming that the ambient temperature is 25°C, when operating at steady-state, you have determined that the normal temperature at th ...

  • Emerson Process Management CSI 9420 - page 106

    where serv_fact_temp = • 5 for service factor of 1.15 or greater • -5 for either open or totally enclosed fan cooled (TEFC) motors, and service factor of 1.0 • 0 for either totally enclosed non-ventilated (TENV) motors or motors with encapsulated windings, and service factor of 1.0 If elevation > 3300 ft (1000m), then: T rise = T rise {1-[ ...

  • Emerson Process Management CSI 9420 - page 107

    6 Accelerometer EMI and RFI considerations The CSI 9420 uses an accelerometer to measure vibration. The process involves a piezoelectric element, which produces a time-waveform with voltage amplitude proportional to acceleration. The input bandwidth of the measurement is approximately 20 kHz. This waveform is then digitized and analyzed within the ...

  • Emerson Process Management CSI 9420 - page 108

    Accelerometer signal with and without interference Figure 6-1: A. Signal measured with no RFI effect. B. Signal in the presence of interference on a completely unmitigated accelerometer. C. Frequency spectrum representation of the signal with interference. Accelerometer EMI and RFI considerations 102 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 109

    6.1 Mitigate interference The following are four basic things you can do to reduce EMI and RFI on measurements: • Use a shorter cable, if possible. For more details, see Section 6.1.1 . Note The leads on the sensor cables, as delivered, are specially prepared for ease of installation. Before attempting to cut the cables, be aware that cutting cab ...

  • Emerson Process Management CSI 9420 - page 110

    Figure 6-2 shows how to run the accelerometer through a conduit that is grounded on both ends. As a general rule, the transmitter housing itself is grounded through the base where it is mounted. Since the conduit is electrically connected to the transmitter housing, this effectively grounds the conduit at the transmitter end. Grounding the conduit ...

  • Emerson Process Management CSI 9420 - page 111

    6.1.3 Install ferrites Note The accelerometers are shipped with ferrites installed at the accelerometer end. To maintain the optimum performance of the accelerometer, do not remove the ferrites. To meet the stated performance criteria, the standard accelerometer cable has two (2) ferrites installed. These are Steward ferrites (P/N 28B0355-000), wit ...

  • Emerson Process Management CSI 9420 - page 112

    The armor-jacketed accelerometer cable has one ferrite installed. It is a Steward ferrite (P/N 28B0672-000), which provides 245 Ω of reactance at 100 MHz. Armor-jacketed accelerometer cable with ferrite installed (as shipped from the factory) Figure 6-4: If your cables require additional immunity after accelerometer installation is complete and ac ...

  • Emerson Process Management CSI 9420 - page 113

    From a compliance perspective, you do not need to install the ferrites if the cable is in a ferromagnetic conduit (such as galvanized steel) because this type of conduit provides additional shielding. Note that the conduit entry of the device is ½ inch NPT. If you install ferrites with a conduit, you will need a wider conduit ( ¾ inch NPT or M20) ...

  • Emerson Process Management CSI 9420 - page 114

    Armor-jacketed cable and ferrites (pre-installation) Figure 6-6: Install ferrites on a standard cable 1. Make standard connections to the CSI 9420 terminal block and grounding screw. 2. Snap the first of three attenuator ferrites (MHM-94985) at the location on the cable approximately 1 in. from the point where the cable enters the gland. 3. Snap th ...

  • Emerson Process Management CSI 9420 - page 115

    Ferrites installed on a standard cable Figure 6-7: Install ferrites on an armor-jacketed cable 1. Make standard connections to the CSI 9420 terminal block and grounding screw. 2. Slide the first of the three ferrites at the location on the cable approximately 1 in. from the point where the cable enters the gland. 3. Secure the ferrite using a wire ...

  • Emerson Process Management CSI 9420 - page 116

    Ferrites installed on an armor-jacketed cable Figure 6-8: You need an additional ferrite for devices that use external DC supply. This ferrite is included with the transmitter if you order the external power option. Transmitter using an external power option with ferrites installed Figure 6-9: This is a snap-on ferrite. Depending on the size of the ...

  • Emerson Process Management CSI 9420 - page 117

    The ferrite in this example is Fair-Rite P/N 0431164281, which has a reactance that ranges from 28 Ω at 1 MHz to 310 Ω at 100 MHz and 240 Ω at 250 MHz. It supports a maximum cable diameter of 0.260 inch (6.6 mm). Effect of ferrites on interference Figure 6-10 compares two accelerometers in the presence of a high-intensity RF field (10 V/m). The ...

  • Emerson Process Management CSI 9420 - page 118

    Figure 6-10 also shows that ferrites provide a huge amount of RFI suppression and are needed to maintain measurement integrity in the presence of strong electromagnetic interference. Do not remove the ferrites installed on the accelerometer cables that are shipped from the factory, even if you mitigate interference using other methods. 6.1.4 Reduce ...

  • Emerson Process Management CSI 9420 - page 119

    RFI source polarization coincident with long cable run (maximum interference) Figure 6-12: Accelerometer EMI and RFI considerations MHM-97408, Rev 15 113 ...

  • Emerson Process Management CSI 9420 - page 120

    6.1.5 Summary To maximize immunity to EMI/RFI, consider the following when planning the installation of the CSI 9420 and its accelerometers: Required • Use ferrites to attenuate interference that couples into the accelerometer cable. • Ensure the installation conforms with all local codes and regulations. Best practice • Use a shorter cable, ...

  • Emerson Process Management CSI 9420 - page 121

    Appendix A Specifications and reference data Topics covered in this appendix: • Functional specifications • Physical specifications • Performance specifications • Radio specifications • Low-power sensors (special order and standard) • Dimensional drawings • Sensor mounting diagrams A.1 Functional specifications Input Supports 1 or 2 a ...

  • Emerson Process Management CSI 9420 - page 122

    Measurement Range RMS velocity (frequency dependent): 0.008 in/s to >4.35 in/s (0.20 mm/s to >110.5 mm/s) PeakVue: 0.02 g to 80 g (0.2 m/s 2 to 785 m/s 2 ) PeakVue details: 51.2 kHz sampling rate, 4096 samples/block, 1000 Hz high pass filter Accuracy For vibration over stated frequency response (at room temperature) RMS velocity: • +/- 5% f ...

  • Emerson Process Management CSI 9420 - page 123

    A.2 Physical specifications Electrical connections/power module Smart Power Module • Replaceable, non-rechargeable, intrinsically safe lithium-thionyl chloride power module pack with PBT enclosure • 1.5–3-year power module life at reference conditions (1) • 4 screw terminals for sensor connection External DC power • 10-28 VDC, 40 mA, 80 m ...

  • Emerson Process Management CSI 9420 - page 124

    A.3 Performance specifications Temperature Limits The transmitter will operate within specifications for ambient temperatures between –40°F and 185°F (–40°C and 85°C). Temperature limits Table A-1: CSI 9420 Operating limit Storage limit With LCD display –4°F to 175°F –20°C to 80°C –40°F to 185°F –40°C to 85°C Without LCD dis ...

  • Emerson Process Management CSI 9420 - page 125

    A.5 Low-power sensors (special order and standard) Special order models Table A-2: Part number Color code Cable length (ft) Cable type Sensor range Accelerometer A0394RI Green 10 Polyurethane 0.02 g to 80 g from 1 kHz to 20 kHz 0.01 in/s to 4.35 in/s at 1 kHz A0394RI-2 50 A0394RI-3 75 A0394RA 10 Armor A0394RA-2 50 A0394RA-3 75 A0394RAC 10 Armor w/ ...

  • Emerson Process Management CSI 9420 - page 126

    Standard order models Table A-3: Part number Color code Cable length (ft) Cable type Sensor range Accelerometer A0394RI-1 Green 30 Polyurethane 0.02 g to 80 g from 1 kHz to 20 kHz 0.01 in/s to 4.35 in/s at 1 kHz A0394RI-4 100 A0394RA-1 30 Armor A0394RA-4 100 Specifications and reference data 120 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 127

    A.6 Dimensional drawings Sensors are specified separately. Dimensions are in inches (millimeters). CSI 9420 with sensor and mounting brackets Figure A-1: CSI 9420 with long-range and extended antennas Figure A-2: Specifications and reference data MHM-97408, Rev 15 121 ...

  • Emerson Process Management CSI 9420 - page 128

    A.7 Sensor mounting diagrams Milling process Figure A-3: This spot facing should create a uniform seat. Specifications and reference data 122 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 129

    Figure A-3 shows specifications for drilling and spot face grinding when mounting accelerometers using the stud mount method, and Figure A-4 shows the correct and incorrect milling process. Correct and incorrect milling Figure A-4: Note Properly align the drill so that the tapped hole is perpendicular to the mounting surface. Specifications and ref ...

  • Emerson Process Management CSI 9420 - page 130

    Figure A-5 shows the specifications for drilling, tapping a pilot hole, and torqueing the mounting stud when mounting the sensor. Accelerometer mounting Figure A-5: Specifications and reference data 124 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 131

    Appendix B Product certifications Topics covered in this appendix: • Approved manufacturing location • Wireless certifications • Hazardous locations certificates Note For specific device certifications, always refer to the product nameplate and markings on the device. B.1 Approved manufacturing location Emerson Process Management - MHM, Knoxv ...

  • Emerson Process Management CSI 9420 - page 132

    FCC ID: LW2RM2510 IC ID: 2731A-RM2510 Ordinary location certification (CSA) As standard, the transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by CSA, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health ...

  • Emerson Process Management CSI 9420 - page 133

    B.3 Hazardous locations certificates The CSI 9420 carries multiple certificates for operation in hazardous locations. For a complete listing of specific approvals, please reference our website. Note The markings that appear on the transmitter housing determine whether a device is suitable for operation in a specific hazardous location. This further ...

  • Emerson Process Management CSI 9420 - page 134

    Product certifications 128 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 135

    Appendix C LCD screen messages Startup screen sequence These are the screens when the power module is first connected to the CSI 9420. LCD screen Meaning Description All Segments On Used to visually determine if there are any bad segments on the LCD. NIM Startup The device is waiting for the radio to initialize. This takes approximately 15 seconds. ...

  • Emerson Process Management CSI 9420 - page 136

    LCD screen Meaning Description Acquire Preparation The device powers up the DSP and prepares for data acquisition. Acquire Data The device is acquiring and processing data. Device Information Tag 8-character user entered tag. Device Identification Device identifier that makes up the HART long address. The Smart Wireless Gateway may use this to help ...

  • Emerson Process Management CSI 9420 - page 137

    LCD screen Meaning Description Network Identification This ID tells the user what network the device can connect to, assuming the device has the correct Join Key. Version Code Displays the firmware version of the device. Joining and provisioning These are the screens when the CSI 9420 is in the process of joining the network. LCD screen Meaning Des ...

  • Emerson Process Management CSI 9420 - page 138

    LCD screen Meaning Description Set Service The request for network services has been issued to the device. Service Rejected The request for network services has been rejected by the network manager. Sufficient bandwidth may not currently be available. Normal operating sequence These are the screens displayed during normal operation. LCD screen Mean ...

  • Emerson Process Management CSI 9420 - page 139

    LCD screen Meaning Description Acquire Data The device is acquiring and processing data. PV screen Displays the overall velocity, PeakVue, temperature, sensor bias voltage, or power supply voltage depending on how the device is configured. SV screen Displays the overall velocity, PeakVue, temperature, sensor bias voltage, or power supply voltage de ...

  • Emerson Process Management CSI 9420 - page 140

    LCD screen Meaning Description Data Publish The device has started collecting new data and will publish it to the gateway when complete. Sleep Shows how long the device sleeps between times it wakes up and collects/publishes data. Network status screens These screens display the network status of the CSI 9420. LCD screen Meaning Description Network ...

  • Emerson Process Management CSI 9420 - page 141

    LCD screen Meaning Description Network Search The device is searching for a network. Network Negotiation The device has detected a network and is attempting to establish connection. Network Connected The device has joined the network and has established connection with the network manager. Network Operational The device is connected to both the net ...

  • Emerson Process Management CSI 9420 - page 142

    LCD screen Meaning Description Network Disconnected The device is disconnected from the network. Device diagnostic screens These screens show the state of the CSI 9420. LCD screen Meaning Description Device Failure There is critical error which may prevent the device from operating correctly. Alert Present At least one alert is present. Low Supply ...

  • Emerson Process Management CSI 9420 - page 143

    LCD screen Meaning Description Supply Failure The terminal voltage has reached a critical level. If the device is power module operated, the power module should be replaced. If the device is line-powered, the supply voltage should be increased. More Status Available At least one device parameter is on alert. LCD screen messages MHM-97408, Rev 15 13 ...

  • Emerson Process Management CSI 9420 - page 144

    LCD screen messages 138 MHM-97408, Rev 15 ...

  • Emerson Process Management CSI 9420 - page 145

    Index A absolute temperature monitoring 99, 100 accelerometer cable length 103 accelerometer EMI and RFI considerations 101 acquisitions publishing policy 62, 63 store on alert 62, 63 time-based storage 62, 63 Advanced Diagnostics application alternative installation 62 enable using AMS Device Manager 60 enable using AMS Wireless Configurator 60 en ...

  • Emerson Process Management CSI 9420 - page 146

    ferrites, installing 105, 108, 109, 111 field communicator fast key sequences 32 field communicator menu tree 19 field communicator, configuration with 19 functional specifications 115 G grounding 85 H hazardous location certificates 127 I import data CSI 9420 62–65 Smart Wireless Gateway 62–65 installation location 5, 6 installing ferrites 105 ...

  • Emerson Process Management CSI 9420 - page 147

    sensor sensitivity 13 sensors attaching 74 cable length 103 connecting 78 mounting tools 71, 72 operating limit 70 special order 119 standard 119 Smart Power Module removing 19 spectral data 49–52, 56, 57 spectrum time 68 Store on Alert 62, 63 stud mount 73 T temperature absolute monitoring 99, 100 alert thresholds 99 limits 5, 6 relative monitor ...

  • Emerson Process Management CSI 9420 - page 148

    MHM-97408 Rev 15 2015 Emerson Process Management Machinery Health Management 835 Innovation Drive Knoxville, TN 37932 USA T +1 865-675-2400 F +1 865-218-1401 www.EmersonProcess.com © 2015, Emerson Process Management The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their ...

Manufacturer Emerson Process Management Category Home Security System

Documents that we receive from a manufacturer of a Emerson Process Management CSI 9420 can be divided into several groups. They are, among others:
- Emerson Process Management technical drawings
- CSI 9420 manuals
- Emerson Process Management product data sheets
- information booklets
- or energy labels Emerson Process Management CSI 9420
All of them are important, but the most important information from the point of view of use of the device are in the user manual Emerson Process Management CSI 9420.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Emerson Process Management CSI 9420, service manual, brief instructions and user manuals Emerson Process Management CSI 9420. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Emerson Process Management CSI 9420.

A complete manual for the device Emerson Process Management CSI 9420, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Emerson Process Management CSI 9420 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Emerson Process Management CSI 9420.

A complete Emerson Process Management manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Emerson Process Management CSI 9420 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Emerson Process Management CSI 9420, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Emerson Process Management CSI 9420, that we can find in the current document
3. Tips how to use the basic functions of the device Emerson Process Management CSI 9420 - which should help us in our first steps of using Emerson Process Management CSI 9420
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Emerson Process Management CSI 9420
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Emerson Process Management CSI 9420 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Emerson Process Management CSI 9420?

Use the form below

If you did not solve your problem by using a manual Emerson Process Management CSI 9420, ask a question using the form below. If a user had a similar problem with Emerson Process Management CSI 9420 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)