Summary
  • Minuteman E1000RM1U - page 1

    User's Manual Enterprise 1U Rackmount Series ...

  • Minuteman E1000RM1U - page 2

    1 © Copyright Para Systems, Inc., 2005 Enterprise 1U Rackmount Series User's Manual 1 . Introduction 2 2 . Controls and Indicators 6 3. Installation 8 4 . Operation 12 5 . T roubleshooting 15 6 . Replacing the Battery 16 7 . Obtaining Service 19 8 . Specifications 20 9 . Configurable Parameters & Settings 22 10 . Limited Product W arranty ...

  • Minuteman E1000RM1U - page 3

    2 IMPORT ANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS ! English Thank you for purchasing a MINUTEMAN power protection product. It has been designed and manufactured to provide many years of trouble free service. Please read this manual before installing your Enterprise 1U Rackmount Se- ries UPS, models E700RM1U, E1000RM1U, E1500RM1U, as it prov ...

  • Minuteman E1000RM1U - page 4

    3 W ARNING: Risk of Electrical Shock. Hazardous live p arts inside these power supplies are energized from the battery even when the AC input is disconnected. CAUTION! T o de-energize the outputs of the UPS: 1. If the UPS is on press and release the On/Of f/T est button. 2. Disconnect the UPS from the AC wall outlet. 3. T o de-energize the UPS comp ...

  • Minuteman E1000RM1U - page 5

    4 English After removing your MINUTEMAN UPS from its carton, it should be inspected for damage that may have occurred in shipping. Immediately notify the carrier and place of purchase if any damage is found. Warranty claims for damage caused by the carrier will not be honored. The packing materials that your UPS was shipped in are carefully designe ...

  • Minuteman E1000RM1U - page 6

    5 English Para Systems Life Support Policy As a general policy , Para Systems Inc. (Para Systems) does not recommend the use of any of its products in life support applications where failure or mal- function of the Para Systems product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or ef ...

  • Minuteman E1000RM1U - page 7

    6 English The AC normal (green) LED illuminates in a steady st ate when the UPS is on and operating in the AC normal mode. The AC normal LED will extinguish when operating in the Battery mode. The On-Battery (green) LED illuminates in a steady state when the UPS is operating in the Battery mode. The On-Battery LED will extinguish when operating in ...

  • Minuteman E1000RM1U - page 8

    7 English The Load Level Bar Graph operates as follows: LED #10: >10% load (green/red/yellow) LED will be green and illu- minated when there is at least 10% of the rated capacity . LED #30: >30% load (green/yellow) LED will be green and illumi- nated when there is at least 30% of the rated capacity . LED #50: >50% load (green/yellow) LED w ...

  • Minuteman E1000RM1U - page 9

    8 English INST ALLA TION PLACEMENT The Enterprise 1U Rackmount Series is intended to be install in a temperature controlled environment that is free of conductive contaminants. Select a loca- tion which will provide good air circulation for the UPS at all times. A void loca- tions near heating devices, water or excessive humidity , or where the UPS ...

  • Minuteman E1000RM1U - page 10

    9 English INST ALLA TION Be sure to read the installation placement and all the cautions before installing the UPS. Place the UPS in the final desired location and complete the rest of the installation procedure. These UPSs are shipped with the internal batteries disconnected. The batteries must be connected before putting these UPSs into service. ...

  • Minuteman E1000RM1U - page 11

    10 English Installing the UPS in a 4-post rack USE CAUTION: The UPS is heavy . Use the appropriate number of personnel when installing the UPS. 1. Install the rails in the 4-post rack. (FIG . 1) 2. Install the rack ears on the UPS. (FIG . 2) 3. Align the cleat s with the rails and slide the UPS into the rails. (FIG . 3) NOTE: The cleats are pre-mou ...

  • Minuteman E1000RM1U - page 12

    11 English CHARGING THE BA TTER Y The Enterprise 1U Rackmount Series UPS will charge the internal batteries whenever the UPS is connected to an AC source. It is recommended that the UPS's batteries be charged for a minimum of 4 hours before use. The UPS may be used immediately , however , the “On-Battery” runtime may be less than normally ...

  • Minuteman E1000RM1U - page 13

    12 English SYSTEM OVERVIEW This Line-Interactive 1U Rackmount model UPS protects internetworking and telecommunications equipment from blackouts, brownouts, overvoltages, and surges. The A VR function continuously corrects the voltages, in-between the brownout and overvoltage transfer points (85 - 150V AC), to a safe usable level. When the UPS is o ...

  • Minuteman E1000RM1U - page 14

    13 English ALARMS ON BA TTER Y When the UPS is operating on the batteries, the On-Battery LED will illuminate and the audible alarm will sound once every ten-seconds. The alarm will stop once the UPS returns to the AC normal mode. LOW BA TTER Y W ARNING The UPS will sound two beeps every five-seconds when the battery reserve runs low . This conditi ...

  • Minuteman E1000RM1U - page 15

    14 English COMMUNICA TIONS PORTS (RS232 and USB) The RS232 communication port is a standard DB9 female with both RS232 and simulated cont act closure capability . The Enterprise 1U Rackmount Series UPS will poll the port and activate the port for RS232 or contact closure in accordance with the type of cable it finds connected to the port. T o chang ...

  • Minuteman E1000RM1U - page 16

    15 English Possible Cause Symptom What T o Do Press and release the On/Off/ T est button to start UPS On/Off/T est button not pushed UPS will not turn on Reset circuit breaker by pressing the plunger back in. If the AC circuit breaker trips after UPS starts up, reduce the load on the UPS UPS operates in battery mode only , even though there is norm ...

  • Minuteman E1000RM1U - page 17

    16 English REPLACING THE BA TTER Y W ARNING! This Uninterruptible Power Supply contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement procedure. This UPS contains no user serviceable parts. Repairs and Battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONL Y . Do not open or m ...

  • Minuteman E1000RM1U - page 18

    17 English BA TTER Y REPLACEMENT PROCEDURE PLEASE READ THE CAUTIONS AND W ARNINGS BEFORE A TTEMPTING TO REPLACE THE BA TTERIES Hot-swappable batteries mean that the batteries can be replaced without powering down the whole UPS system. NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will ...

  • Minuteman E1000RM1U - page 19

    18 English 8. Remove the four ret aining screws for the battery retaining bracket. (FIG . 3) 9. Remove the battery retaining bracket. (FIG . 3) 10. Grasp the battery tray and gently pull the battery tray out far enough to get to the battery connectors (red and black). (FIG . 4) 1 1. Disconnect the battery connectors (red and black). (FIG . 5) 12. G ...

  • Minuteman E1000RM1U - page 20

    19 English IF THE UPS REQUIRES SERVICE 1.Use the TROUBLESHOOTING section to eliminate obvious causes. 2.V erify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem. 3.Call your dealer for assistance. If you cannot reach your dealer , or if they cannot resolve the problem call or fax MINUTEMAN T echnical Suppo ...

  • Minuteman E1000RM1U - page 21

    20 English Default 120V AC User selectable 120/127V AC 700V A 490W 1500V A 900W 1000V A 700W Protection W aveform T ype Over-Current, Short-Circuit Protected and Latching Shutdown Sine Wave Frequency 50/60Hz, +/-0.1Hz (unless synchronized to utility) Nominal V olt age Maximum Power Capacity 2-6 mS T ypical >93% (Full Load) Resettable Circuit Bre ...

  • Minuteman E1000RM1U - page 22

    21 English BA TTER Y SYSTEM T ypical Recharge T ime T ypical Battery Life Battery Quantity/Rating 3-5 years, depending on discharge cycles and ambient temp 4-6V9Ah 4-6V9Ah 8 hours from total discharge 4-6V9Ah Battery T ype Sealed, Non-S pillable, Maintenance Free, V alue Regulated Lead Acid System V oltage 24VDC 24VDC 24VDC Runtime: Full Load Runti ...

  • Minuteman E1000RM1U - page 23

    22 English (These items may require optional software or hardware) Function Factory Default Description User Choices Set inverter output voltage Shut- down T ype Set audible alarm state Enable/ Disable auto restart Battery life in days Battery install date UPS ID Enterprise 1U RM Series Date of manufacture 1826 Enabled Enabled Entire UPS 120V AC Up ...

  • Minuteman E1000RM1U - page 24

    23 English Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase. For equip- ment sites within the United S tates and Canada, this warranty covers repair or replacement of defective equipm ...

  • Minuteman E1000RM1U - page 25

    24 English EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL P ARA SYSTEMS BE LIABLE FOR DIRECT , INDIRECT , SPECIAL, INCIDENT AL, OR CONSEQUEN- TIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT , EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. S pecifically , Para Sys- tems is not liable for any costs, such as lost profits or revenue, loss of equip- ...

  • Minuteman E1000RM1U - page 26

    25 English DECLARA TION OF CONFORMITY Application of Council Directive(s): 89/336/EEC, 73/23/EEC S tandard(s) to which Conformity is declared: Manufacturer’s Name: Para Systems, Inc. (MINUTEMAN UPS) Manufacturer ’s Address: 1455 LeMay Drive Carrollton, T exas 75007 USA T ype of Equipment: Uninterruptible Power Supplies (UPS) Model No: E700RM1U ...

  • Minuteman E1000RM1U - page 27

    26 English Notes: ...

  • Minuteman E1000RM1U - page 28

    Para Systems, Inc. 1455 Lemay Dr . Carrollton, TX 75007 Phone: 1-972-446-7363 Fax: 1-972-446-901 1 Internet: minutemanups.com UPS Sizing: sizemyups.com PN - 34000256 Rev .1 ...

Manufacturer Minuteman Category Power Supply

Documents that we receive from a manufacturer of a Minuteman E1000RM1U can be divided into several groups. They are, among others:
- Minuteman technical drawings
- E1000RM1U manuals
- Minuteman product data sheets
- information booklets
- or energy labels Minuteman E1000RM1U
All of them are important, but the most important information from the point of view of use of the device are in the user manual Minuteman E1000RM1U.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Minuteman E1000RM1U, service manual, brief instructions and user manuals Minuteman E1000RM1U. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Minuteman E1000RM1U.

Similar manuals

A complete manual for the device Minuteman E1000RM1U, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Minuteman E1000RM1U by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Minuteman E1000RM1U.

A complete Minuteman manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Minuteman E1000RM1U - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Minuteman E1000RM1U, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Minuteman E1000RM1U, that we can find in the current document
3. Tips how to use the basic functions of the device Minuteman E1000RM1U - which should help us in our first steps of using Minuteman E1000RM1U
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Minuteman E1000RM1U
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Minuteman E1000RM1U in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Minuteman E1000RM1U?

Use the form below

If you did not solve your problem by using a manual Minuteman E1000RM1U, ask a question using the form below. If a user had a similar problem with Minuteman E1000RM1U it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)