    TECHNICAL GUIDE AFFINITY R-22 SPLIT -SYSTEM HEA T PUMPS 12 SEER MODELS: YMA024 THRU 060 (2 THRU 5 NOMINAL TONS) Due to continuous pr od uct improvement, sp eci fications are subject to change without n otice. Visit us on the web at www .yor k.com for the most up-to-date technical information. Additional rating informa tion can be foun d at www .ari ...

  • York YMA024 - page 2

    036-21570-002 Rev. D (0605) 2 Unitary Products Group All dimensions are in inches. They a re subject to change without notice. Ce rtif ied dimensio ns will be provide d upon request. * Expander fitti ng req uired for 1-1/8” line set. Physical and Electrical Dat a MODEL YMA0241 1 YMA0301 1 YMA0361 1 YMA0421 1 YMA0481 1 YMA0601 1 Unit Supply V olta ...

  • York YMA024 - page 3

    036-21570-002 Rev. D (0605) Unitary Products Group 3 PROCEDURES: 1. Unit factory charge listed on the unit nameplate inclu des refr igerant for the co ndenser , the smallest evaporator and 15 feet of inter- connecting line tubing. 2. V erify the TXV and additional charge requ ired for specific evaporator coil in th e system using the above table. 3 ...

  • York YMA024 - page 4

    036-21570-002 Rev. D (0605) 4 Unitary Products Group ** Refer to Quick Selection Chart for specific furnace mat ch-up. COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL ELECTRIC 2 HEA T KW W RA TED CFM TOT AL CAP ACITY SENSIBLE CAP ACITY SEER W/O TXV SEER W/ TXV EER 1 PH 12 SEER HP WITH N1AH / G2FD YMA0241 ...

  • York YMA024 - page 5

    036-21570-002 Rev. D (0605) Unitary Products Group 5 COOLING CAP ACITY - Upflow , Downflow & Horizontal Furnaces and Coils UNIT MODEL FURNACE** COI L MODEL COOLING CFM RANGE (MIN.-MAX.) WR A T E D C F M TOT AL CAP ACITY SENSIBLE CAP ACITY SEER W/O TXV + T DR 1,2 SEER W/TXV + TDR EER YMA0241 1 600 1000 14 G1F A036S1 4 800 24.2 19.1 12.00 12.00 1 ...

  • York YMA024 - page 6

    036-21570-002 Rev. D (0605) 6 Unitary Products Group COOLING CAP ACITY - With V a riable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COI L MODEL 1 W COOLING RA TED CFM TOTAL CAP ACITY SENSIBLE CAP ACITY SEER W/O TXV +TDR SEER/ W/TXV +TDR 2 EER 1 PH 12 SEER HP / P1DU / P1XD / P1XU - V ARIABLE SPEED 3 YMA0241 1 P*DUA12V G1F A036S14 14 7 5 ...

  • York YMA024 - page 7

    036-21570-002 Rev. D (0605) Unitary Products Group 7 UNIT MODEL V ARIABLE SPEED FURNACE MODEL COI L MODEL 4 W COOLING RA TED CFM TOT AL CAP ACITY SENSIBLE CAP ACITY SEER W/O TXV +TDR SEER/ W/TXV +TDR 5 EER 1 PH 12 SEER HP / P1DU / P1XD / P1XU - V ARIABLE SPEED 6 YMA0481 1 P*DUC20V G1F A060S21(T) 21 1610 46.0 35.8 - 12.10 10.40 P*DUC20V G2FD060(S,H) ...

  • York YMA024 - page 8

    036-21570-002 Rev. D (0605) 8 Unitary Products Group COP equals MBH output divided by (t ot al KW input x 3.412). HSPF (Heating Seasonal Performa nce Factor) is the tot al heatin g output during a norma l annua l usage period for heating divided by the to t al electric power input during the same period. — = Not Applicable. HEA TING PER FORMANCE ...

  • York YMA024 - page 9

    036-21570-002 Rev. D (0605) Unitary Products Group 9 COP equals MBH output divided by (tot al KW inp ut x 3.412). HSPF (Heating Seasonal Performa nce Factor) is the total heat i ng output during a norma l annual usage period for heating divide d by the total electric power input during the same period. — = Not Applicable. HEA TING P ERFORMANCE - ...

  • York YMA024 - page 10

    036-21570-002 Rev. D (0605) 10 Unitary Products Group ACCESSORIES* Hard St art Kit (024-31994-000, 024-31995-000) - Provides increased starting torque for areas with low voltage. TXV Kit s - 1 TV07 seri es thermal expansion valves precisely meter refrigerant for optimum pe rforman ce. Dehumidistat (2HU16700124) - Provides increased dehu- midificati ...

  • York YMA024 - page 11

    036-21570-002 Rev. D (0605) Unitary Products Group 11 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible cap acity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York YMA024 - page 12

    036-21570-002 Rev. D (0605) 12 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increase s by 1060 BTUH per 100 0 CFM per degree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM pe ...

  • York YMA024 - page 13

    036-21570-002 Rev. D (0605) Unitary Products Group 13 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible cap acity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York YMA024 - page 14

    036-21570-002 Rev. D (0605) 14 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increase s by 1060 BTUH per 100 0 CFM per degree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM pe ...

  • York YMA024 - page 15

    036-21570-002 Rev. D (0605) Unitary Products Group 15 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible cap acity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York YMA024 - page 16

    036-21570-002 Rev. D (0605) 16 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increase s by 1060 BTUH per 100 0 CFM per degree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM pe ...

  • York YMA024 - page 17

    036-21570-002 Rev. D (0605) Unitary Products Group 17 Multipliers for determini ng the performance with other indoor section. HEA TING P ERFORMANCE DA T A OUTDOOR UNIT MODEL NO. YMA024 1 1 INDOOR COIL MODEL NO. G2FD030S17 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 600 800 1000 MBTUH KW C.O.P . MBTU H KW C.O.P . MBTUH KW ...

  • York YMA024 - page 18

    036-21570-002 Rev. D (0605) 18 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A OUTDOOR UNIT MODEL NO. YMA030 1 1 INDOOR COIL MODEL NO. G2FD030S17 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 800 1000 1200 MBTUH KW C.O.P . M BTUH KW C.O.P . MBTU ...

  • York YMA024 - page 19

    036-21570-002 Rev. D (0605) Unitary Products Group 19 Multipliers for determining the performance with other indoor sections . HEA TING P ERFORMANCE DA T A OUTDOOR UNIT MODEL NO. YMA036 1 1 INDOOR COIL MODEL NO. G2FD036S17 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1000 1200 1400 MBTUH KW C.O.P . MBTU H KW C.O.P . MBTUH ...

  • York YMA024 - page 20

    036-21570-002 Rev. D (0605) 20 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A OUTDOOR UNIT MODEL NO. YMA042 1 1 INDOOR COIL MODEL NO. G2FD048S21 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1200 1400 1600 MBTUH KW C.O.P . M BTUH KW C.O.P . MBT ...

  • York YMA024 - page 21

    036-21570-002 Rev. D (0605) Unitary Products Group 21 Multipliers for determining the performance with other indoor sections . HEA TING P ERFORMANCE DA T A OUTDOOR UNIT MODEL NO. YMA048 1 1 INDOOR COIL MODEL NO. G1F A06 0S24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1400 1600 1800 MBTUH KW C.O.P . MBTU H KW C.O.P . MBT ...

  • York YMA024 - page 22

    036-21570-002 Rev. D (0605) 22 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A OUTDOOR UNIT MODEL NO. YMA060 1 1 INDOOR COIL MODEL NO. G1F A06 0S24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1600 1800 2000 MBTUH KW C.O.P . M BTUH KW C.O.P . M ...

  • York YMA024 - page 23

    036-21570-002 Rev. D (0605) Unitary Products Group 23 MA TCHING INDOOR COMPONENTS G1UA 1/2 CASED UPFLOW G1HD HORIZONT AL DUCT G2FD* MUL TI-POSITION (UPFLOW , HORIZONT AL AND DOWNFLOW) * A vailable with factor y installed horizontal drain p an. ADD-ON COILS - FOR FURNACE APPLICA TIONS G1F A FULL CASED UPFLOW G1HA FULL CASED HORIZONT AL AIR HANDLERS ...

  • York YMA024 - page 24

    Subject to change without notice. Printe d in U.S.A. 036-21570-002 Rev. D (0605) Copyright © by York International Corp. 2005. All right s reserved. Supersedes: 036-21570-002 Rev. C (040 5) Unitary 5005 Norman Product s Y ork O K Group Drive 73069 NOTES ...

Manufacturer York Category Heat Pump

Documents that we receive from a manufacturer of a York YMA024 can be divided into several groups. They are, among others:
- York technical drawings
- YMA024 manuals
- York product data sheets
- information booklets
- or energy labels York YMA024
All of them are important, but the most important information from the point of view of use of the device are in the user manual York YMA024.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals York YMA024, service manual, brief instructions and user manuals York YMA024. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product York YMA024.

Similar manuals

A complete manual for the device York YMA024, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use York YMA024 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of York YMA024.

A complete York manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual York YMA024 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the York YMA024, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the York YMA024, that we can find in the current document
3. Tips how to use the basic functions of the device York YMA024 - which should help us in our first steps of using York YMA024
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with York YMA024
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of York YMA024 in a specific country, if it was not possible to solve the problem on our own.