    Quick Start Guide 00825-0100-4774, Rev FA June 2014 Note Bef ore installing the transmitte r , con firm the correct device drive r is loaded on the host systems. See “Syste m readiness ” on page 3 . R osemount ® 3051 Pressure T ransmitt er R osemount 3051CF Series Flo wmeter T ransmitter with F OUNDATION ™ fieldbus prot ocol 00825-0100-4774_ ...

  • Emerson Rosemount 3051CF - page 2

    June 2014 2 Quick Start Guide NO TICE This installation guide provides basic guidelines for R osemount 3051 transmitters. It does no t provide instructions f or confi guration, di agnostics, main tenance , ser vice , troubleshoo ting, Explosion-Proof , Flame-Proof, or intrinsically saf e (I.S.) installa tions. Ref er to the 3051 ref ere nce manual ...

  • Emerson Rosemount 3051CF - page 3

    Quick Start Guide 3 June 2014 System re adiness Confirm correct device driv er  V erif y the correct device drive r (DD/DTM ™ ) is loaded on your syst ems to ens ur e p ro p er co mmu n ic at io ns .  Download the correc t device driver a t your host ve ndor download site, www .eme rsonprocess.c om or www .fieldbus.org . R ose mount 3051 de ...

  • Emerson Rosemount 3051CF - page 4

    June 2014 4 Quick Start Guide Figure 1. Installation Flowchart Start 1. T ransmitter installation 2 . Commissioning tag 6 . Configuration Done Locate device 7 . Zero tri m th e transmitter 5. Grounding, wiring and power up 3 . Housing rot at io n 4 . Set switches and softwar e write lock 00825-0100-4774_RevFA.fm Pag e 4 Friday, June 6, 2014 2:21 PM ...

  • Emerson Rosemount 3051CF - page 5

    Quick Start Guide 5 June 2014 T ransmitter installation St ep 1: Mount the transmitter Liquid applications Coplanar In-Line 1. Place taps to the side of the line. 2. Mount be side or be low the tap s. 3. Mount the trans mitte r so that the drain/ven t valves are oriented up ward. Ga s applications Coplanar In-Line 1. Plac e taps in t he top or side ...

  • Emerson Rosemount 3051CF - page 6

    June 2014 6 Quick Start Guide Figure 2. Panel and Pipe Mounting Bolting consider ations If the transmi tter installat ion requires assem bly of the proce ss flanges, man ifolds, or flange adapters, fo llow the assembly guideline s to ensure a tight seal for optimal performa nce charact eristics of the t ransmitters. Us e only bolts suppl ied with t ...

  • Emerson Rosemount 3051CF - page 7

    Quick Start Guide 7 June 2014 Figure 3. Common T ransmitte r Assemblies A. T ransmitter with C oplanar Flange B. T ransmitter with Coplanar Flan ge and Optional Flange Adapters C. T ransmitter with T raditional Flange and Optional Flange Adap ters D. T ransmi tter with Coplan ar Flange and Option al Manifold and Fl ange Adapt ers Bolts are typica l ...

  • Emerson Rosemount 3051CF - page 8

    June 2014 8 Quick Start Guide T able 2. T orque V alues for the Flange and Flange Ad apter Bolts O-rings with fl ange adapte rs Bolt materi al Head markings Initial torque Final torque Carbon Steel (CS) 300 in.-lbs. 650 in.-lbs. Sta in le ss St eel (S ST ) 150 in.-lbs. 300 in.-lbs. F ailure to instal l proper flange adapter O-rings may cause proces ...

  • Emerson Rosemount 3051CF - page 9

    Quick Start Guide 9 June 2014 Whenever the fl anges or adapte rs are removed, visually inspe ct the o-rings. Replace them if t here are any signs of d amage, such as nic ks or cuts. If you replace the o-rings, re-torque t he flange bolts an d alignment scre ws after installa tion to compensate for seating of the PTFE o-ring. Inline gage transmitte ...

  • Emerson Rosemount 3051CF - page 10

    June 2014 10 Quick Start Guide Figure 6. Commissioning T ag A. Device revision Note The device de scription loaded in the host system mu st be at the same re vision as this device. The devic e description can be downloaded from the host system we bsite or www .rosemo unt.c om by se lecting Download Devic e Drive r s under Product Quick Links. Y ou ...

  • Emerson Rosemount 3051CF - page 11

    Quick Start Guide 11 June 2014 Step 4: Set the switc hes Set Simulate an d Security switch configuration be fore installat ion as shown in Figure 8 .  The simulate switch en ables or disables simulated ale r ts and simulated AI Block status and values. The default simulate switch position is enabled.  The Securit y s witch allows (unlocked sy ...

  • Emerson Rosemount 3051CF - page 12

    June 2014 12 Quick Start Guide St ep 5: Wire, ground, and power up Use of copper wire of sufficient size to ensure th at the voltage across the transmitter power t erminals does not drop below 9 vdc. P ower supply volta ge can be varia ble, especi ally under ab normal conditions suc h as when ope rating on battery backup. A minimum of 12 vdc under ...

  • Emerson Rosemount 3051CF - page 13

    Quick Start Guide 13 June 2014 a. T rim the cable shie ld as short as practical and insu lat e from to uching the transmitter housing. Note Do NO T ground the cable shield a t the transmitter; if the cable shie ld touches the transmitte r housing, it can cre ate gro und loops and int erfere with c ommunica tions. b. C ontinuously c onnect th e cabl ...

  • Emerson Rosemount 3051CF - page 14

    June 2014 14 Quick Start Guide When the user exits the “Locate Device” meth od, the device LCD d isplay automatically ret urns to normal ope ration. Note Some hosts do not support “Locate De vice” in the DD . Step 6: Configure Each F OUNDATION fieldbus host or config uration tool has a different way of displaying an d performing configu rat ...

  • Emerson Rosemount 3051CF - page 15

    Quick Start Guide 15 June 2014 Figure 11. Basic Configur ation Menu T ree Before y ou begin See Figu re 10 to graphically view th e step by step process for basic device configuration. Be fore beginning configurat ion you may need to v erify the Device Tag or deactivat e hardware and softwa re write prote ction on the transm itter. To do this follo ...

  • Emerson Rosemount 3051CF - page 16

    June 2014 16 Quick Start Guide a. Navig ation : from the ove r view scree n, select “Devic e Inf orma tion ” and the n se lect the “Security and Simul ation” tab . b. P erform “Write Lock Setup ” to disable Soft ware Write Lock. Note Place the c ontrol loop in “Manual” mode bef o re beginning Analog Input Block configuration. AI blo ...

  • Emerson Rosemount 3051CF - page 17

    Quick Start Guide 17 June 2014 Note If the L_TYPE selected in Step 3 is “Direc t”, Step 4 , St ep 5 and Step 6 are not needed. If the L_T YPE selected is “Indi rect”, Step 6 is not needed. If guided setup is used any unneeded steps will aut omatically be skipped. 3. T o select the Signal Conditioning “L_T YPE” from the drop down menu: a ...

  • Emerson Rosemount 3051CF - page 18

    June 2014 18 Quick Start Guide 8. Configure optional L CD di splay (if installed). a. T o use guided setup :  Naviga te to Con figure, Guided Setup , and select “Local Display Setup”. Note Guided setup will automatically go through each step in the proper orde r .  Check the box nex t to each parameter to be displayed to a maximum of fou ...

  • Emerson Rosemount 3051CF - page 19

    Quick Start Guide 19 June 2014 AI block conf igur ation pa ramet ers Use the Pressure, DP Fl ow, and DP Level examples for guides. Pressure example DP Flow example Param ete rs Enter data Channe l 1=Pressure, 2=Se nsor T emp, 12=S PM mean, 13=S PM standard de viati on L-T y pe Dir ect, I ndi re ct, or Sq u ar e Ro ot XD_Scale Scale and Enginee ring ...

  • Emerson Rosemount 3051CF - page 20

    June 2014 20 Quick Start Guide DP Leve l example Displ ay pre ssure on the L CD displ ay Select the 'pre ssure' check bo x on the display con figuration sc reen. St ep 7: Zero trim the transmitt er Note T ransmitters are shipped fully calibrated per request or by the factor y default of full scale (s pan = uppe r range limit). A zero trim ...

  • Emerson Rosemount 3051CF - page 21

    March 2014 Quick Start Guide   3051 Product Certifications Rev 1.0 European Directive Information A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at www.rosemount.com . Ordinary Location Certifi cation from FM Approvals As st ...

  • Emerson Rosemount 3051CF - page 22

    Quick Start Gui de March 2014  Markings: Explosionproof for Class I, Division 1, Groups B, C and D; Suitable for Class I, Zone 1, Group IIB+H2, T5; Dust-I gnitionproof Class II, Division 1, Groups E, F, G; Class III Division 1; Intrinsically Safe Cl ass I, Division 1 Groups A, B, C, D when connected in accordance with Rosemount drawing 03031-102 ...

  • Emerson Rosemount 3051CF - page 23

    March 2014 Quick Start Guide Special Conditions for Safe Us e (X): 1. The apparatus is not capable of withstanding the 500 V insulation test required by EN60079-11. This must be taken into account when installing the apparatus. 2. The enclosure may be made of aluminum allo y and given a protective polyuretha ne paint finish; how ever care should be ...

  • Emerson Rosemount 3051CF - page 24

    Quick Start Gui de March 2014 2. For information on the dimensions of t he flameproo f joints the manufacturer shall be contacted. 3. The capacitance of the wrap around label, bei ng 1. 6 nF, exceeds th e limit in Table 9 of EN60079-0. The user shall determine suit ability for the specific applic ation. 4. Some variants of the equipment have reduce ...

  • Emerson Rosemount 3051CF - page 25

    March 2014 Quick Start Guide Brazil E2 INMETRO Flameproof Certificate: UL-BR 13.0643X Standards: ABNT NBR IEC60079-0:2008 + Errat a 1:2011, ABNT NBR IEC60079- 1:2009 + Errata 1:2011, ABNT NBR IEC60 079-26:2008 + Errata 1:2008 Markings: Ex d IIC T6/T5 Ga/Gb, T6(-50°C ≤ Ta ≤ +65°C), T5 (-50°C ≤ Ta ≤ +80°C) Special Conditions for Safe Us e ...

  • Emerson Rosemount 3051CF - page 26

    Quick Start Gui de March 2014 China E3 China Flameproof Certificate: GYJ14.1041X; GYJ10.1313X [Flowmeters] Standards: GB3836.1-2000, GB38 36.2-2010, GB12476-2000 Markings: Ex d IIC T6/T5, T6(-50°C ≤ Ta ≤ +65°C), T5(-50° C ≤ Ta ≤ +80°C) Special Conditions of Us e (X): 1. The relation between ambient temperature ar range and temperature c ...

  • Emerson Rosemount 3051CF - page 27

    March 2014 Quick Start Guide Power P i 0.9 W 1.3 W 5.32 W Capacitance C i 0.012 µF 0 µF <5 nF Inductance L i 0 mH 0mH <10 µH Note 1: FISCO paramete rs apply to both Group IIC and IIB. Note 2: [For Flowmeters] When 644 te mperature tra nsmitter is used, the 644 temperature transmitter should be used with E x-certified associated apparatus t ...

  • Emerson Rosemount 3051CF - page 28

    Quick Start Gui de March 2014 GB3836.15-2000 “Electrical apparatus for explos ive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)” GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines)” GB50257-1996 “Code f ...

  • Emerson Rosemount 3051CF - page 29

    Quick Start Guide June 2014 00825-0100-4774_RevFA.fm Pag e 21 Friday, June 6, 2014 2:21 PM ...

  • Emerson Rosemount 3051CF - page 30

    June 2014 Quick Start Guide 00825-0100-4774_RevFA.fm Pag e 22 Friday, June 6, 2014 2:21 PM ...

  • Emerson Rosemount 3051CF - page 31

    Quick Start Guide June 2014 00825-0100-4774_RevFA.fm Pag e 23 Friday, June 6, 2014 2:21 PM ...

  • Emerson Rosemount 3051CF - page 32

    June 2014 Quick Start Guide 00825-0100-4774_RevFA.fm Pag e 24 Friday, June 6, 2014 2:21 PM ...

  • Emerson Rosemount 3051CF - page 33

    Quick Start Guide June 2014 00825-0100-4774_RevFA.fm Pag e 25 Friday, June 6, 2014 2:21 PM ...

  • Emerson Rosemount 3051CF - page 34

    Device revision (1) 1. 1. F OUNDATION fieldbus devic e revision can be read using a F OUNDATION fieldbus capable con figuration tool. Host De vice d rive r (DD) (2) 2.Device driver file names u se device and DD revision. T o access functional ity , the correct devi ce driv er mu st be insta lled on your control and asset ma nagement hos ts, and o n ...

Manufacturer Emerson Category Marine Instruments

Documents that we receive from a manufacturer of a Emerson Rosemount 3051CF can be divided into several groups. They are, among others:
- Emerson technical drawings
- Rosemount 3051CF manuals
- Emerson product data sheets
- information booklets
- or energy labels Emerson Rosemount 3051CF
All of them are important, but the most important information from the point of view of use of the device are in the user manual Emerson Rosemount 3051CF.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Emerson Rosemount 3051CF, service manual, brief instructions and user manuals Emerson Rosemount 3051CF. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Emerson Rosemount 3051CF.

Similar manuals

A complete manual for the device Emerson Rosemount 3051CF, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Emerson Rosemount 3051CF by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Emerson Rosemount 3051CF.

A complete Emerson manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Emerson Rosemount 3051CF - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Emerson Rosemount 3051CF, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Emerson Rosemount 3051CF, that we can find in the current document
3. Tips how to use the basic functions of the device Emerson Rosemount 3051CF - which should help us in our first steps of using Emerson Rosemount 3051CF
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Emerson Rosemount 3051CF
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Emerson Rosemount 3051CF in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Emerson Rosemount 3051CF?

Use the form below

If you did not solve your problem by using a manual Emerson Rosemount 3051CF, ask a question using the form below. If a user had a similar problem with Emerson Rosemount 3051CF it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)