    364861-UIM-H-0712 RESIDENTIAL GAS FURNACE MODELS: TG9S*MP , GG9S*MP (95.5% AFUE Single St age Multi-position) INSTALLATION MANUAL LIST OF SECTIONS SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 FILTERS . . . . . ...

  • Johnson Controls TG9S'MP - page 2

    364861-UIM-H-0712 2 Johnson Controls Unitary Products These high efficiency , compact units employ induced combustion, reli- able hot surface ignition and high hea t transfer aluminized tubular heat exchangers. The units are factory shipped for installation in upflow or horizontal applications and may be converted for downflow ap plica- tions. Thes ...

  • Johnson Controls TG9S'MP - page 3

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 3 • Check the rating plate and power supply to be sure that the elec- trical characteristics match. Al l models use nominal 1 15 V AC, 1 Phase, 60-Hz power supply . DO NOT CONNECT THIS APPL I- ANCE TO A 50-Hz POW ER SUPPL Y OR A VOL T AGE ABOVE 130 VOL TS. • Furnace shall be installed so t he ...

  • Johnson Controls TG9S'MP - page 4

    364861-UIM-H-0712 4 Johnson Controls Unitary Products INSPECTION As soon as a unit is r eceived, it should be inspected for possible dam- age during transit. If damage is evident, th e extent of the damage should be noted on the carrier ’s freight bill. A separate request fo r inspection by the carrier ’s agent shoul d be made in writing. Also, ...

  • Johnson Controls TG9S'MP - page 5

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 5 SECTION II: DUCTWORK DUCTWORK GENERAL INFORMA TION The duct system’s design and installation must: 1. Handle an air volume appropriate for the served space and within the operating parameters of the furnace specifications. 2. Be installed in accordance of Na tional Fire Protection Association ...

  • Johnson Controls TG9S'MP - page 6

    364861-UIM-H-0712 6 Johnson Controls Unitary Products COIL INST ALLA TION COIL/FURNA CE ASSEMBL Y - MC/FC/PC SERIES COILS FURNACE ASSEMBL Y - MC & FC S ERIES COILS These coils are factory shipped for installation in either upflow or down- flow applications with no conversion. Position the coil casing over or under the furnace opening as shown i ...

  • Johnson Controls TG9S'MP - page 7

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 7 Dimension “C” should be at least 2/3 of dimension “D”. See Figure 6. CRITICAL COIL PROJECTION The coil assembly must be located in the duct such that a minimum dis- tance is maintained between the top of the coil and the top of the duct. Refer to T able 2. COIL / FURNACE ASSEMBL Y - HC ...

  • Johnson Controls TG9S'MP - page 8

    364861-UIM-H-0712 8 Johnson Controls Unitary Products A TTIC INST ALLA TION This appliance is certified for line contact when the furnace is installed in the horizontal left or right position. The line contact is only permissible between lines that are formed by the intersection of the top and two sides of the furnace and the building jo ists, stud ...

  • Johnson Controls TG9S'MP - page 9

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 9 SECTION III: FIL TERS FIL TER INST ALLA TION All applications require the use of a field installed filter . All filters and mounting provision must be field supplied. Filters must be installed external to the furnace cabinet. DO NOT attempt to install filters inside the furnace. 1. Air velocity ...

  • Johnson Controls TG9S'MP - page 10

    364861-UIM-H-0712 10 Johnson Controls Unitary Products SIDE RETURN Locate the “L” shaped corner loca tors. These indicate the size of the cut- out to be made in the furnace side panel. Refer to Figure 14. Install the side filter rack followi ng the instructions provided with that accessory . If a filter(s) is provid ed at another location in th ...

  • Johnson Controls TG9S'MP - page 11

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 11 The furnace must be isolated from the gas supply piping system by closing its individual external manua l shutoff valve during any pressure testing of the gas supply piping system at pressures equal to or less than 0.5 psig (3.5 kPa). Gas piping may be connected from eit her side of the furnac ...

  • Johnson Controls TG9S'MP - page 12

    364861-UIM-H-0712 12 Johnson Controls Unitary Products Annual Fuel Utilizat ion Efficiency ( AFUE) numbers are determined in accordance with DOE T est procedures. Wire size and over current protection must comply wi th t he National Electri cal Code (NFP A-70-latest edition) and all local code s. The furnace shall b e installed so that the el ectri ...

  • Johnson Controls TG9S'MP - page 13

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 13 For additional connection diagrams for all UPG equipment refer to “Low V oltage System Wi ring” document available on-line at www .upgnet.com in the Product Catalog Section. FIGURE 18: Thermostat Chart - Single S tage AC with Single S tage PSC Furnaces AC 5D Single Stage Air Conditioner ? ...

  • Johnson Controls TG9S'MP - page 14

    364861-UIM-H-0712 14 Johnson Controls Unitary Products FIGURE 19: Thermostat Chart - Single S tage HP with Single S tage PSC Furnaces HP 2C Single Stage Heat Pump – Single Stage PSC Furnace C 24 – Volt Comm on R 24 – Volt Hot Y1 First Stage Compressor O Reversing Valve Energi zed in Cool L Malfunction Light G Fan *DP32H70124 THERMOSTAT W1 Sec ...

  • Johnson Controls TG9S'MP - page 15

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 15 ACCESSOR Y CONNECTIONS The furnace control will allow power- sw itching control of various acces- sories. ELECTRONIC AIR CLEANER CONNECTION T wo 1/4” (6.4 mm) spade terminals (EAC and NEUTRAL) for electronic air cleaner connections are located on the control board. The te rminals provide 1 1 ...

  • Johnson Controls TG9S'MP - page 16

    364861-UIM-H-0712 16 Johnson Controls Unitary Products T winning Opera tion Heating - On a call for heat (W signal) from the wall ther mostat, both furnaces will start the igniti on sequence and the burners on both fur- naces will light. About thirty seconds after the burners light, the blowers on both furnaces will co me on in heating speed. When ...

  • Johnson Controls TG9S'MP - page 17

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 17 The condensate will flow to the dr ain better if an open stand pipe is installed in the drain line. See Figure 23. If evaporator coil or humidifier drains are combined with the furnace drain, then the open stand pipe could be raised higher , above the 5” minimum. CONDENSA TE DRAIN TERMINA TI ...

  • Johnson Controls TG9S'MP - page 18

    364861-UIM-H-0712 18 Johnson Controls Unitary Products FIGURE 25: Upflow Configuration INDUCER ROT A TED FOR LEFT SIDE VENTING (As required for 130K model) UPFLOW AS RECEIVED (Except for 130K Model) INDUCER ROT A TED FOR RIGHT SIDE VENTING When drain hose routing changes are required, be sure to cap all un-used openings. If rerouting hoses - excess ...

  • Johnson Controls TG9S'MP - page 19

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 19 FIGURE 26: Downflow Configuration AIRFLOW AIRFLOW Move rain gutter hose to this position DOWNFLOW - INDUCER ROT A TED FOR LEFT SIDE VENTING DOWNFLOW - INDUCER ROT A TED FOR RIGHT SIDE VENTING Move pressure switch hose to this position. NOTE: May require the longer hose that is provided with wi ...

  • Johnson Controls TG9S'MP - page 20

    364861-UIM-H-0712 20 Johnson Controls Unitary Products FIGURE 27: Horizontal Left Configuration HORIZONT AL - LEFT INDUCER ROT A TED HORIZONT AL - LEFT INDUCER AS RECEIVED (Except for 130K Model) AIRFLOW AIRFLOW Move pressure switch hose to this position. NOTE: May require the longer hose that is provided with wider cabinets Move rain gutter hose t ...

  • Johnson Controls TG9S'MP - page 21

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 21 FIGURE 28: Horizontal Right Configuration AIRFLOW HORIZONT AL - RIGHT INDUCER ROT A TED HORIZONT AL - RIGHT INDUCER AS RECEIVED (Except for 130K Model) Move rain gutter hose to this position Move pressure switch hose to this position. Change condensate drain connection to the 90° fitting prov ...

  • Johnson Controls TG9S'MP - page 22

    364861-UIM-H-0712 22 Johnson Controls Unitary Products SECTION VIII: COMB USTION AIR AND VENT SY STEM COMBUSTION AIR AND VENT SAFETY This Category IV , dual certified direct vent furnace is designed for resi- dential application. It may be install ed without modification to the con- densate system in a basement, garage, equipment room, alcove , att ...

  • Johnson Controls TG9S'MP - page 23

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 23 Dimensions are those requi red in S tandard AS TM D-33 1 1. Example: An 80,000 BTUH furnace requires 3 2 feet of pipe and five 90º elbows. Using 2" pipe and standard elbows, t he total equivalent length will be: This exceeds the 65 foot maximum equi valent length of 2" pipe allowed ...

  • Johnson Controls TG9S'MP - page 24

    364861-UIM-H-0712 24 Johnson Controls Unitary Products VENT CLEARANCES † A vent shall not terminate directly above a sidewalk or paved driveway that is locate d between two single fa mily dwellings and serves both dwellings. †† 12” (30.5 cm) up from the bottom edge of the str uctur e for T wo- pipe (direct vent) applications per ANSI Z223.1 ...

  • Johnson Controls TG9S'MP - page 25

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 25 VENT SY STEM This furnace is certified to be installed with one of two possible vent configurations. 1. Horizontal vent system. This vent system can be installed com- pletely horizontal or combinations of horizontal, vertical, or offset using elbows. 2. V ertical vent system. Th is vent system ...

  • Johnson Controls TG9S'MP - page 26

    364861-UIM-H-0712 26 Johnson Controls Unitary Products DOWNWA RD VENTING In some applications, it may be neces sary to run the ven t pipe and air intake downwards. If this is to be done, the followin g rules must be fol- lowed. • A condensate trap hose must be connected to both the air intake pipe and the vent pipe at the lowest part of the horiz ...

  • Johnson Controls TG9S'MP - page 27

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 27 Ambient Combustion Air Supply This type installation will draw the air required for combustion from within the space surrounding the a ppliance and from area s or rooms adjacent to the space surrounding the appliance. This may be from within the space in a non-confined location or it may be br ...

  • Johnson Controls TG9S'MP - page 28

    364861-UIM-H-0712 28 Johnson Controls Unitary Products Air Supply Openings and Duct s 1. An opening may be used in lieu of a duct to pr ovide to provide the outside air supply to an appliance unless o therwise permitted by the authority having jurisdiction. The open ing shall be located within 12” (30.5 cm) horizontally from, the burner level of ...

  • Johnson Controls TG9S'MP - page 29

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 29 Specially Engineered Inst allations The above requirements shall be permi tted to be waived whe re special engineering, approved by the authority having jurisdiction, provides an adequate supply of air for combustion and ventilation. VENT BLO WER RO T A TION For ease of venting, the vent blowe ...

  • Johnson Controls TG9S'MP - page 30

    364861-UIM-H-0712 30 Johnson Controls Unitary Products IGNITION SY STEM SEQUENCE 1. T urn the gas supply ON at external valve and main gas valve. 2. Set the thermostat above room temperature to call for heat. 3. System start-up will occur as follows: a. The induced draft blower motor will start and come up to speed. Shortly after inducer start-up, ...

  • Johnson Controls TG9S'MP - page 31

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 31 T able 14: Gas Rate (CU FT/H R) at Full Input Seconds For 1 Revolution Size of T est Dial Seconds For 1 Revolution Size of T est Dial 1 Cu Ft 2 Cu Ft 5 Cu Ft 1 Cu Ft 2 Cu Ft 5 Cu Ft 10 360 720 1800 55 65 131 327 1 1 327 655 1636 56 64 129 321 12 300 600 1500 57 63 126 316 13 277 555 1385 58 62 ...

  • Johnson Controls TG9S'MP - page 32

    364861-UIM-H-0712 32 Johnson Controls Unitary Products ADJUSTMENT OF MANIFO LD GAS PRESSURE & INPUT RA TE Inlet and manifold gas pressure may be measured by connecting the “U” tube manometer to the gas valve with a piece of tubing. Follow the appropriate section in the instructions below. Refer to Figure 40 for a drawing of the locations of ...

  • Johnson Controls TG9S'MP - page 33

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 33 ADJUSTMENT OF TEMPERA TURE RISE After about 5 minutes of operation, determine the furnace temperature rise. T ake readings of both the return air and the heated air in the ducts, about six feet (1.8 m) from the furnace where they will not be affected by radiant heat. Increase the blower speed ...

  • Johnson Controls TG9S'MP - page 34

    364861-UIM-H-0712 34 Johnson Controls Unitary Products NOTES: 1.Airflow expressed in st andard cubic feet per minute (CFM). 2.Motor voltage at 1 15 V . T able 17: Blower Performance CFM - Any Positio n (without filter) - Bottom Return Models Input/Airflow/Cabinet Sp eed Bottom Airflow Dat a (SCFM) Ext. Static Pressure (in. H2O) 0.1 0.2 0.3 0. 4 0.5 ...

  • Johnson Controls TG9S'MP - page 35

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 35 NOTES: 1.Airflow expressed in st andard cubic feet per minute (CFM). 2.Return air is through side opposite motor (lef t side). 3.Motor voltage at 1 15 V . 4.Airflow through motor side (rig ht side) may be slightly less than the data shown above. T able 18: Blower Performance CFM - Any Positio ...

  • Johnson Controls TG9S'MP - page 36

    364861-UIM-H-0712 36 Johnson Controls Unitary Products SECTION X: SAFETY CONTROLS CONTROL CIR CUIT FUSE A 3-amp fuse is provided on the control circuit board to protect the 24- volt transformer from overload caus ed by control circ uit wiring errors. This is an A TO 3, automotive type fuse and is located on th e control board. BLO WER DOOR SAFETY S ...

  • Johnson Controls TG9S'MP - page 37

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 37 FURNA CE CONTROL DIA GNOSTICS The furnace has built-in, self-diagnos tic capability . A blinking LED light on the control board can flash red, green or amber to indicate various conditions. The control con tinuou sly monitors its own operation and the operation of the system. If a failur e occ ...

  • Johnson Controls TG9S'MP - page 38

    364861-UIM-H-0712 38 Johnson Controls Unitary Products DIAGNOSTIC F A UL T CODE ST ORAGE AND RETRIEV AL The control in this furnace is equipped with memory that will store up to five error codes to allow a serv ice technician to diagnose problems more easily . This memory will be retained even if power to the furnace is lost. This feature sho uld o ...

  • Johnson Controls TG9S'MP - page 39

    364861-UIM-H-0712 Johnson Controls Unitary Produ cts 39 SECTION XIII: WIRING DIAGRAM FIGURE 44: Wiring Diagram Wiring Diagram - 95% Single-Stage Furnace MOT IDM EAC HUM COOL HEAT EAC HUM HSI HUM DS TST GND GND GV LS PS1 EAC R G Y W EAC HUM BRN ROS ROS W Y G C R BLU BLU - MED HI BLK DS GRN BRN BRN GND HSI IDM BLK - HI YEL - MED LOW RED - LOW WHT MOT ...

  • Johnson Controls TG9S'MP - page 40

    Subject to change without not ice. Published in U.S.A. 364861-UIM-H-0712 Copyright © 2012 by Johnson Controls, Inc. All rights reserved. Supersedes: 364861-UIM-G-1211 Y ork International Corp. 5005 Y ork Drive Norman, OK 73069 NOTES ...

Manufacturer Johnson Controls Category Furnace

Documents that we receive from a manufacturer of a Johnson Controls TG9S'MP can be divided into several groups. They are, among others:
- Johnson Controls technical drawings
- TG9S'MP manuals
- Johnson Controls product data sheets
- information booklets
- or energy labels Johnson Controls TG9S'MP
All of them are important, but the most important information from the point of view of use of the device are in the user manual Johnson Controls TG9S'MP.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Johnson Controls TG9S'MP, service manual, brief instructions and user manuals Johnson Controls TG9S'MP. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Johnson Controls TG9S'MP.

A complete manual for the device Johnson Controls TG9S'MP, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Johnson Controls TG9S'MP by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Johnson Controls TG9S'MP.

A complete Johnson Controls manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Johnson Controls TG9S'MP - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Johnson Controls TG9S'MP, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Johnson Controls TG9S'MP, that we can find in the current document
3. Tips how to use the basic functions of the device Johnson Controls TG9S'MP - which should help us in our first steps of using Johnson Controls TG9S'MP
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Johnson Controls TG9S'MP
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Johnson Controls TG9S'MP in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Johnson Controls TG9S'MP?

Use the form below

If you did not solve your problem by using a manual Johnson Controls TG9S'MP, ask a question using the form below. If a user had a similar problem with Johnson Controls TG9S'MP it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)