    © Panasonic HA Air-Conditi oning (M) Sdn. Bhd. 2009. Unauthorized copy ing and distributi on is a violation of law . Order No. PHAAM0905053C2 Air Conditioner Indoor Unit Out door Unit CS-CE9JKE CU-CE9JKE CS-CE12JKE CU-CE12JKE T ABLE OF CONTENTS PA G E PA G E 1 Safety Precautions ----------------------------------------------- 3 2 Specifications -- ...

  • Panasonic CS-CE9JKE - page 2

    2 12.7. Indication Panel------------------------------------------- 33 13 Protection Control ---------------------------------------------- 34 13.1. Protection Control For All Operations --------------- 34 13.2. Protection Control For Cooling & Soft Dry Operation --------------------------------------------------- 36 13.3. Protection Control Fo ...

  • Panasonic CS-CE9JKE - page 3

    3 1 Safety Precautions • Read the following “SAFETY PRECAUTIONS” carefully before perfo rm any servicing. • Electrical work must be installed or serviced by a licensed elec trician. Be sure to use the correct rating of the power plug a nd main circuit for the model installed. • The caution items stated here must be followed because these ...

  • Panasonic CS-CE9JKE - page 4

    4 18. For R410A models, when connecting the pi ping, do not use any existing (R22) pipes and flare nuts. Using such same may cause abnormally high pressure in the refriger ation cycle (piping), and possibly result in explosion and inju ry . Use only R410A materials. Thickness of copper pipes used with R410A must be more than 0.8mm. Never use copper ...

  • Panasonic CS-CE9JKE - page 5

    5 2 S pecifications MODEL INDOOR CS-CE9JKE OUTDOOR CU-CE9JKE Performance T est Condition EUROVENT Power Supply Phase, Hz Single, 50 V 230 Min. Mid. Max. Cooling Capacity kW 0.60 2.60 3.00 BTU/h — — — Kcal/h 520 2240 2580 Running Current A — 2.8 — Input Power W 125 590 750 Annual Consumption kWh — 295 — EER W/W 4.80 4.41 4.00 Kcal/hW 4 ...

  • Panasonic CS-CE9JKE - page 6

    6 Outdoor Fan Ty p e Propeller Fan Material PP Motor T ype DC T ype (8-poles) Input Power W — Output Power W 40 S peed Hi Cool rpm 800 Heat rpm 790 Moisture Removal L/h (Pt/h) 1.6 (3.4) Indoor Airflow Lo Cool/Fan m 3 /min (ft 3 /min) 5.4 (190) Heat m 3 /min (ft 3 /min) 6.4 (230) Me Cool/Fan m 3 /min (ft 3 /min) 8.0 (280) Heat m 3 /min (ft 3 /min) ...

  • Panasonic CS-CE9JKE - page 7

    7 1. Coo ling capacities are based on indoor tempera ture of 27 ° C Dry Bulb (80.6 ° F Dry Bulb), 19.0 ° C Wet Bulb (66.2 ° F We t Bulb) and outdoor air temperature of 35 ° C Dry Bulb (95 ° F Dry Bulb), 24 ° C Wet Bulb (75.2 ° F Wet Bulb) 2. Heating capacities are based on indoor temp erature of 20 ° C Dry Bulb (68 ° F Dry Bulb) and outdo ...

  • Panasonic CS-CE9JKE - page 8

    8 MODEL INDOOR CS-CE12JKE OUTDOOR CU-CE12JKE Performance T est Condition EUROVENT Power Supply Phase, Hz Single, 50 V 230 Min. Mid. Max. Cooling Capacity kW 0.60 3.50 4.00 BTU/h — — — Kcal/h 520 3010 3440 Running Current A — 4.4 — Input Power W 125 915 1.18k Annual Consumption kWh — 458 — EER W/W 4.80 3.83 3.39 Kcal/hW 4.16 3.29 2.92 ...

  • Panasonic CS-CE9JKE - page 9

    9 Outdoor Fan Ty p e Propeller Fan Mater ial PP Motor T ype DC T ype (8-poles) Input Power W — Output Power W 40 S peed Hi Cool rpm 840 Heat rpm 820 Moisture Removal L/h (Pt/h) 2.0 (4.2) Indoor Airflow Lo Cool/Fan m 3 /min (ft 3 /min) 6.3 (220) Heat m 3 /min (ft 3 /min) 9.4 (332) Me Cool/Fan m 3 /min (ft 3 /min) 8.5 (300) Heat m 3 /min (ft 3 /min ...

  • Panasonic CS-CE9JKE - page 10

    10 1. Cooling ca pacities are based on indoor temperature of 27 ° C Dry Bulb (80.6 ° F Dry Bulb), 19.0 ° C Wet Bulb (66.2 ° F Wet Bulb) and outdoor air tempera ture of 35 ° C Dry Bulb (95 ° F Dry Bulb), 24 ° C Wet Bulb (75.2 ° F Wet Bulb) 2. Heating capacities a re based on in door temperature of 20 ° C Dry Bulb (68 ° F Dry Bulb) and out ...

  • Panasonic CS-CE9JKE - page 11

    11 3 Features • Inverter T ech nology - Wider output po wer range - Energy saving - More precise temperature control • Environment Protection - Non-ozone depl etion substances refrigerant (R410A) • Long Installation Piping - Long piping up to 15 meters during single split connection only • Easy to use remote contr ol • Quality Improvement ...

  • Panasonic CS-CE9JKE - page 12

    12 4 Location of Controls and Component s 4.1. Indoor Unit 4.2. Out door Unit 4.3. Remote Control ...

  • Panasonic CS-CE9JKE - page 13

    13 5 Dimensions 5.1. Indoor Unit ...

  • Panasonic CS-CE9JKE - page 14

    14 5.2. Out door Unit ...

  • Panasonic CS-CE9JKE - page 15

    15 6 Refrigeration Cycle Diagram ...

  • Panasonic CS-CE9JKE - page 16

    16 7 Block Diagram ...

  • Panasonic CS-CE9JKE - page 17

    17 8 Wiring Connection Diagram 8.1. Indoor Unit ...

  • Panasonic CS-CE9JKE - page 18

    18 8.2. Out door Unit ...

  • Panasonic CS-CE9JKE - page 19

    19 9 Electronic Circuit Diagram 9.1. Indoor Unit ...

  • Panasonic CS-CE9JKE - page 20

    20 9.2. Out door Unit ...

  • Panasonic CS-CE9JKE - page 21

    21 10 Printed Circuit Board 10.1. Indoor Unit 10.1.1. Main Printed Circuit Board ...

  • Panasonic CS-CE9JKE - page 22

    22 10.1.2. Power Printed Circuit Board 10.1.3. Indicator Printed Circuit Board ...

  • Panasonic CS-CE9JKE - page 23

    23 10.2. Out door Unit ...

  • Panasonic CS-CE9JKE - page 24

    24 1 1 Inst allation Instruction 1 1.1. Select the Best Location 1 1.1.1. Indoor Unit • Do not install the unit in excessive oil fume area such as kitchen, workshop and etc. • There should not be an y heat source or steam near the unit. • There should not be any ob stacles blocking the air circulation. • A place where air circulation in the ...

  • Panasonic CS-CE9JKE - page 25

    25 1 1.2. Indoor Unit 1 1.2.1. How to Fix Inst allation Plate The mounting wall is strong and solid enough to prevent it from the vibration. The centre of installation plate should be at more th an at right and left of the wa ll. The distance from installation plate edge to ceiling should more than . From installation plate left edge to unit’s le ...

  • Panasonic CS-CE9JKE - page 26

    26 1. For the right rear pip ing 2. For the right and right bottom piping 3. For the embedded piping (This can be used for left rear piping and bottom piping also. ) ...

  • Panasonic CS-CE9JKE - page 27

    27 1 1.2.4. Connect the Cable to the Indoor Unit 1. The inside and outside connecting cable can be connected without removing the front grille. 2. Connecting c able between indoor uni t and outdoor unit shall be approved polychloroprene sheathed 4 x 1.5 mm 2 flexible cord, type designation 245 IEC 57 or he avier cord. • Secure the connecting cabl ...

  • Panasonic CS-CE9JKE - page 28

    28 1 1.3. Out door Unit 1 1.3.1. Inst all the Out door Unit • After selecting the best location, start installation according to Indoor/Outdoor Unit Installation Diagram. 1. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). 2. When installing at roof, p lease consider strong wind and e arthquake. Please fasten ...

  • Panasonic CS-CE9JKE - page 29

    29 4. Close the Low side valve of the charging set and turn o ff the vacuum pump. Make sure that the needle in the gaug e does not move after approximately five minutes. Note: BE SURE TO T AKE THIS PROCEDURE IN ORDER T O A VOID REFRIGERANT GAS LEAKAGE. 5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve ...

  • Panasonic CS-CE9JKE - page 30

    30 12 Operation and Control 12.1. Basic Function Inverter control, which equipped wi th a microcomputer in determining the most suitable operating mo de as time passes, automatically ad justs output power for maximum comfort always. In order to achieve the su itable operating mode, the microcomputer maintains the set temperat ure by measuring the t ...

  • Panasonic CS-CE9JKE - page 31

    31 12.1.5. Automatic Operation • This mode can be set using remote control and the operation is decided by remote control setting temperature, remote control operation mode, indoor intake air temperature and outdoor air temperature. • During operation mo de judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are ru nning for 30 ...

  • Panasonic CS-CE9JKE - page 32

    32 [Heating] • According to indo or pipe temperature, automatic he ating fan speed is determined as follows. B. Feedbac k control • Immediately after the fan motor started, feedback control is performed once every secon d. • During fan motor on, if fan mo tor feedback 2550 rpm or < 50 rpm continue for 10 seconds, then fan motor error count ...

  • Panasonic CS-CE9JKE - page 33

    33 12.4.2. Horizontal Airflow • The horizontal airflow direction louve rs can be adjusted manually by hand. 12.5. T imer Control 12.5.1. ON Timer Control • ON timer can be set using remote control, the unit with timer set will start operate earlier than the setting time. This is to provide a comfortable environment when reaching the set ON time ...

  • Panasonic CS-CE9JKE - page 34

    34 13 Protection Control 13.1. Protection Control For All Operations 13.1.1. Rest art Control (Time Delay Safety Control) • The Compressor will no t turn on within 3 minutes from the moment operation stops, although the unit is turned on again by pressing OFF/ON button at remote control within this period . • This control is not applicable if t ...

  • Panasonic CS-CE9JKE - page 35

    35 13.1.5. Compressor Overheating Prevention Control • Instructed frequency for compressor operati on will be regulated by compressor di scharge temperature. The changes of frequency ar e as below . • If compressor discharge temperatu re exceeds 1 12 ° C, compressor will be stopped, occurs 4 times per 20 minutes, timer LED will be blinking. (? ...

  • Panasonic CS-CE9JKE - page 36

    36 13.2. Protection Control For Cooling & Sof t Dry Operation 13.2.1. Outdoor Air T emperature Control • The compressor operating frequency is regulate d in accordance to the outdoor air temperature as shown in the diagram below . • This control will begin 1 mi nute after the compressor st arts. • Compressor frequency will adjust base on ...

  • Panasonic CS-CE9JKE - page 37

    37 13.2.6. Dew Prevention Control 2 • T o prevent dew formation at indoor unit discharge area . • This control starts if all conditions continue for 20 minutes: - Operated with Cooli ng or Soft Dry Mode. - Indoor intake temperature is between 25 ° C and 29 ° C. - Outdoor air temperature is less than 30 ° C. • This control stopped if: - Whe ...

  • Panasonic CS-CE9JKE - page 38

    38 14 Servicing Mode 14.1. Auto OFF/ON Button 1. AUTO OPERA TION MODE The Auto operation wil l be activated immediately once the Auto OFF/ON button is pressed. This operatio n can be used to operate air conditioner with limi ted function if remote control is mi splaced or malfunction. 2. TEST RUN OPERA TION (FOR PUMP DOWN/SERVICING PURPOSE) The T e ...

  • Panasonic CS-CE9JKE - page 39

    39 4. REMOTE CONTROL RECEIVING SOUND OFF/ON MODE The Remote Control R eceiving Sound OFF/ON Mode will be activa ted if the Auto OFF/ON button is pressed continuously for more than 16 seconds (4 “beep” sounds will occur a t 16th seconds to identify the R emote Control Receiving Sound Off/On Mode is in standby condition) a nd press “AC Reset” ...

  • Panasonic CS-CE9JKE - page 40

    40 15 T r oubleshooting Guide 15.1. Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insu fficient insulation, problem with the power source, malfunction of a compressor and a fan. The normal outlet a ir temperature and pres ...

  • Panasonic CS-CE9JKE - page 41

    41 15.1.1. Relationship between the condition of the air conditioner and pressure and electric current • Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started. Cooling Mode Heating Mode Low Pressure High Pressure Electric current during operating Low Pressure High Pressure Electric ...

  • Panasonic CS-CE9JKE - page 42

    42 15.2. Breakdown Self Diagnosis Function 15.2.1. Self Diagnosis Function (Three Digit s Alphanumeric Code) • Once abnormality h as occurred during operation, th e unit will stop its operation, and T imer LED blinks. • Although Timer LED goes off when power supply is turned off, if the unit is operated under a breakdown condition, the LED will ...

  • Panasonic CS-CE9JKE - page 43

    43 15.3. Error Codes T able Abnormality / Protection contro l Abnormality Judgement Protection operation Problem Check location Diagnosis display H00 No memory of failure — Normal operation — — H1 1 Indoor/out door abnormal communication After operation for 1 minute Indoor fan only operation can start by entering into force cooling operation ...

  • Panasonic CS-CE9JKE - page 44

    44 F97 Compressor overheating protection 3 times happen within 30 minutes — Compressor overheat • Insufficient refrigerant F98 T otal running current protection 3 times happen within 20 minutes — T otal current protection • Check refrigeration system • Power source or compressor lock F99 Out door dir ect current (DC) peak detection Contin ...

  • Panasonic CS-CE9JKE - page 45

    45 15.4. Self-diagnosis Method 15.4.1. H1 1 (Indoor/Outdoor Abnormal Communication) Malfunction Decis ion Conditions During startup and ope ration of cooling and hea ting, the data received from outdoor unit in in door unit signal transmission is checked whether it is normal. Malfunction Cause d • Faulty indoor unit PCB. • Faulty outdoor unit P ...

  • Panasonic CS-CE9JKE - page 46

    46 15.4.2. H14 (Indoor Intake Air T emperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling an d heating, the temp eratures detected by the indoor intake air temperature sensor are used to determine sensor er rors. Malfunction Caused • Faulty connecto r connection. • Faulty sensor . • Faulty PCB. ...

  • Panasonic CS-CE9JKE - page 47

    47 15.4.3. H15 (Compressor T emper ature Sensor Abnormality) Malfunction Decis ion Conditions During startup and operation o f cooling and heati ng, the temperatures detected by the outdoor compressor temperature sensor are used to determine sen sor errors. Malfunction Cause d • Faulty connector connection. • Faulty sensor . •F a u l t y P C ...

  • Panasonic CS-CE9JKE - page 48

    48 15.4.4. H16 (Outdoor Current T ransformer Open Circuit) Malfunction Decision Conditions A current transformer (CT) is detected by checking the compressor running frequency ( rated frequency) and CT detected input current (less than 0.65A) for con tinuously 20 seconds. Malfunction Caused • CT defective • Outdoor PCB defective • Compressor d ...

  • Panasonic CS-CE9JKE - page 49

    49 15.4.5. H19 (Indoor Fan Motor - DC Motor Mechanism Locked) Malfunction Decis ion Conditions The rotation speed detected by the Hall IC duri ng fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550rpm or < 50 rpm) Malfunction Cause d • Operation stops due to short circuit inside the fan motor winding. ? ...

  • Panasonic CS-CE9JKE - page 50

    50 15.4.6. H23 (Indoor Pipe T emperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of coolin g and heating, the tempe ratures detected by the indoo r heat exchanger temperature sensor are used to determine sensor errors. Malfunction Caused • Faulty connecto r connection. • Faulty sensor . • Faulty PCB. T ...

  • Panasonic CS-CE9JKE - page 51

    51 15.4.7. H27 (Out door Air T emperature Sensor Abnormality) Malfunction Decis ion Conditions During startup and operati on of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors. Malfunction Cause d • Faulty connector connection. • Faulty sensor . •F a u l t y P C B . T ro ...

  • Panasonic CS-CE9JKE - page 52

    52 15.4.8. H28 (Outdoor Pipe T emp erature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating , the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor er rors. Malfunction Caused • Faulty connecto r connection. • Faulty sensor . • Faulty PCB. T r ouble ...

  • Panasonic CS-CE9JKE - page 53

    53 15.4.9. H30 (Compressor Di scharge T emperature Sensor Abnormality) Malfunction Decis ion Conditions During startup and operation of cooling and hea ting, the temperatures detected by the outdoor discharge pipe temp erature sen- sor are used to determine sensor errors. Malfunction Cause d • Faulty connector connection. • Faulty sensor . •F ...

  • Panasonic CS-CE9JKE - page 54

    54 15.4.10. H33 (Unspecified V olt age between Indoor and Outdoor) Malfunction Decision Conditions The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused • Wrong models interconnected. • Wrong indoor unit and outdoor u nit PCBs used. • Indoor unit or outdoor unit PCB defective. T r oubleshooti ...

  • Panasonic CS-CE9JKE - page 55

    55 15.4.1 1. H97 (Out door Fan Moto r - DC Motor Mechanism Locked) Malfunction Decis ion Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor . Malfunction Cause d • Operation stops due to short circuit inside the fan motor winding. • Operation stops due to breaking of wire ins ...

  • Panasonic CS-CE9JKE - page 56

    56 15.4.12. H98 (Indoor High Pressure Protection) Error Code will not display (no Timer LED bli nking) but store in EEPROM Malfunction Decision Conditions During heating operation, the tem perature detected by the indoor pipe te mperature sensor is above 60 ° C. Malfunction Caused • Clogged air filter of the indoor uni t • Dust accumulati on o ...

  • Panasonic CS-CE9JKE - page 57

    57 15.4.13. H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) Error code will not display (no TIMER LED blinking) but store in EEPROM Malfunction Decis ion Conditions Freeze prevention control takes place (when indoor pipe temp erature is lower than 2 ° C) Malfunction Cause d • Clogged air filter of the indo or unit • Dust accumul ...

  • Panasonic CS-CE9JKE - page 58

    58 15.4.14. F1 1 (4-way valve Abnormality) Malfunction Decision Conditions • When heating operation , when indoor pipe temperature is below 10 ° C • When cooling operation, wh en indoor pipe temperature is above 45 ° C Malfunction Caused • Connector in poor contact • Faulty sensor • Faulty outdoor unit PCB • 4-way valve defective T r ...

  • Panasonic CS-CE9JKE - page 59

    59 15.4.15. F90 (Power Factor Correction Protection) Malfunction Decis ion Conditions During startup and operation of cooling and heating, when Pow er Factor Correction (PFC) pro tection circuitry at the outdoor uni t main PCB senses a bnormal high DC voltage level. Malfunction Cause d • DC voltage peak due to power supply surge. • DC voltage p ...

  • Panasonic CS-CE9JKE - page 60

    60 15.4.16. F91 (Refrigeration Cycle Abnormality) Malfunction Decision Conditions • During cooling, compressor frequency = Fcmax. • During heating, compressor freq uency > Fhrated. • During cooling and hea ting operation, running current: 0.65A < I < 1.65A. • During cooling, ind oor intake - indoor pipe < 4 ° C • During heati ...

  • Panasonic CS-CE9JKE - page 61

    61 15.4.17. F93 (Compressor Rot ation Failure) Malfunction Decis ion Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Cause d • Compressor terminal disconnect • Outdoor PCB malfunction T roubleshooting ...

  • Panasonic CS-CE9JKE - page 62

    62 15.4.18. F95 (Cooling High Pressure Abnormality) Malfunction Decision Conditions During operation of coo ling, when outdoor unit heat excha nger high temperature data (61 ° C) is dete cted by the outdoor pipe temperature sensor . Malfunction Caused • Outdoor pipe temperature rise due to short circuit of hot discha rge air flow . • Outdoor p ...

  • Panasonic CS-CE9JKE - page 63

    63 15.4.19. F96 (IPM Overheating) Malfunction Decis ion Conditions During operating of cooling and heating, when IPM temp erature data (100 ° C) is detected by the IPM temperature sensor . Multi Models Only • Compressor Overheating: During op eration of cooling and heating, whe n the compressor OL is activated. • Heat Sink Overheating: During ...

  • Panasonic CS-CE9JKE - page 64

    64 15.4.20. F97 (Compressor Overheating) Malfunction Decision Conditions During operation of co oling and heating, wh en compressor tank temperature data (1 12 ° C) is detected by the comp ressor tank temperature sensor . Malfunction Caused • Refrigerant shortage (refrigerant leakage). • 2/3 way valve closed. • Detection error due to faul ty ...

  • Panasonic CS-CE9JKE - page 65

    65 15.4.21. F98 (Input Over Current Detection) Malfunction Decision Conditions During operation of cooling an d heati ng, when an input over-curren t (14.98A) is detected by checking the input current value being detected by current transformer (CT) with th e compressor running. Malfunction Caused • Over-current due to compressor failure. • Ove ...

  • Panasonic CS-CE9JKE - page 66

    66 15.4.22. F99 (Output Over Current Detection) Malfunction Decision Conditions During operation of cooling and heating, when an ou tput over-current (20.2A) is detected by checking the current that flows in the inverter DC peak sensing circuitry . Malfunction Caused • DC peak due to compressor failure. • DC peak due to defective power transist ...

  • Panasonic CS-CE9JKE - page 67

    67 16 Disassembly and Assembly Instructions 16.1. Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures 16.1.1. T o remove front grille 16.1.2. T o remove power electronic controller High voltages are generated in the electrical parts area by the cap acitor . Ensure that the capacitor has discharged sufficientl y bef ...

  • Panasonic CS-CE9JKE - page 68

    68 16.1.3. T o remove discharge grille ...

  • Panasonic CS-CE9JKE - page 69

    69 16.1.4. T o remove control board 16.1.5. T o remove cross flow fan and indoor fan motor ...

  • Panasonic CS-CE9JKE - page 70

    70 ...

  • Panasonic CS-CE9JKE - page 71

    71 16.2. Out door Electronic Controller Removal Procedure Caution! When handling ele ctronic controller , be careful of electrostatic discharge. 1. Remove the 3 screws of the T op Panel. Fig. 1 2. Remove the 6 screws of the Front Panel. Fig. 2 3. Remove the screw of the T erminal Board Cover . 4. Remove the T op Cover o f the Control Board by 4 hoo ...

  • Panasonic CS-CE9JKE - page 72

    72 17 T echnical Dat a 17.1. Operation Characteristics 17.1.1. CU-CE9JKE ...

  • Panasonic CS-CE9JKE - page 73

    73 ...

  • Panasonic CS-CE9JKE - page 74

    74 ...

  • Panasonic CS-CE9JKE - page 75

    75 ...

  • Panasonic CS-CE9JKE - page 76

    76 17.1.2. CU-CE12JKE ...

  • Panasonic CS-CE9JKE - page 77

    77 ...

  • Panasonic CS-CE9JKE - page 78

    78 ...

  • Panasonic CS-CE9JKE - page 79

    79 ...

  • Panasonic CS-CE9JKE - page 80

    80 17.2. Sensible Cap acity Chart O CU-CE9JKE O CU-CE12JKE 230V Outdoor T emp. ( ° C) Indoor wet bulb temp. 30 35 40 46 T C S H C I PT C S H C I PT C S H C I PT C S H C I P 17.0 ° C 2.58 1.96 0.54 2.41 1.88 0.58 2.24 1.80 0.62 2.04 1.71 0.67 19.0 ° C 2.60 0.59 19.5 ° C 2.83 2.05 0.55 2.65 1.97 0.59 2.46 1.89 0.63 2.24 1.80 0.68 22.0 ° C 3.09 2 ...

  • Panasonic CS-CE9JKE - page 81

    81 18 Exploded V iew and Replacement Part s List 18.1. Indoor Unit Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts. ...

  • Panasonic CS-CE9JKE - page 82

    82 (NOTE) • All parts are supplied from PHAAM, Malaysia (V endor Code: 0002 9488). • “O” marked parts are recommended to be kept in stock. REF . NO. P ART NAME & DESCRIPTION QTY . CS-CE9JKE CS-CE12JKE REMARKS 1 CHASSY COMP LETE 1 CWD50C1599 ← 2 F AN MOTOR 1 ARW6101CB ← O 3 CROSS FLOW F AN COMPLETE 1 CWH02C1076 ← 4 BEARING ASS’Y ...

  • Panasonic CS-CE9JKE - page 83

    83 18.2. Out door Unit Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts. ...

  • Panasonic CS-CE9JKE - page 84

    84 (NOTE) • All parts are supplied from PHAAM, Malaysia (V endor Code: 0002 9488). • “O” marked parts are recommended to be kept in stock. [PHAAM] Printed in Malaysia SFYW0905-00 REF . NO. P ART NAME & DESCRIPT ION QTY . CU-CE9JKE CU-C E12JKE REMARKS 1 CHASSY ASS’Y 1 CWD50K2202 ← 2 ANTI-VIBRA T ION BUSHING 3 CWH50077 ← 3 COMPRESSO ...

Manufacturer Panasonic Category Air Conditioner

Documents that we receive from a manufacturer of a Panasonic CS-CE9JKE can be divided into several groups. They are, among others:
- Panasonic technical drawings
- CS-CE9JKE manuals
- Panasonic product data sheets
- information booklets
- or energy labels Panasonic CS-CE9JKE
All of them are important, but the most important information from the point of view of use of the device are in the user manual Panasonic CS-CE9JKE.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Panasonic CS-CE9JKE, service manual, brief instructions and user manuals Panasonic CS-CE9JKE. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Panasonic CS-CE9JKE.

A complete manual for the device Panasonic CS-CE9JKE, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Panasonic CS-CE9JKE by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Panasonic CS-CE9JKE.

A complete Panasonic manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Panasonic CS-CE9JKE - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Panasonic CS-CE9JKE, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Panasonic CS-CE9JKE, that we can find in the current document
3. Tips how to use the basic functions of the device Panasonic CS-CE9JKE - which should help us in our first steps of using Panasonic CS-CE9JKE
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Panasonic CS-CE9JKE
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Panasonic CS-CE9JKE in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Panasonic CS-CE9JKE?

Use the form below

If you did not solve your problem by using a manual Panasonic CS-CE9JKE, ask a question using the form below. If a user had a similar problem with Panasonic CS-CE9JKE it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)