Spectrum Brands 72A-190BQREM Series - page 1
72A-196BAREM Series 72A-190BQREM Series Installation and Operation Manual 3-Phase Power Monitoring and Distribution Unit June 2, 2008 Rev-01 27-0027-01 1 1 ...
-
Spectrum Brands 72A-190BQREM Series - page 2
Installation and Operation Manual SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Date: 6/02/2008 2 27-0027-01 1 1 Contents I ntroduction & Safety Information .............................................. 3 T echnical Specications .............................................................. 4 Declaration of Conformity ................... ...
-
Spectrum Brands 72A-190BQREM Series - page 3
Installation and Operation Manual Date: 6/02/2008 3 27-0027-01 1 1 SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Introduction & Safety Information The Spectrum Control PDU is an AC power distribution unit designed to distribute power for up to eighteen (18) AC loads. The PDU distributes 3 phase power to six individual, over current protected ...
-
Spectrum Brands 72A-190BQREM Series - page 4
Installation and Operation Manual SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Date: 6/02/2008 4 27-0027-01 1 1 T echnicalSpecications Global Domestic Power Entry Connector IEC 309, 4pole, 5 wire, 32A, WYE connected NEMA L21-30P 5 pin, Delta connected Nominal Input V oltage 3 ∅ 400/230V AC ±10% 3 ∅ 208/208V AC ±10% Input Frequency 5 ...
-
Spectrum Brands 72A-190BQREM Series - page 5
Installation and Operation Manual Date: 6/02/2008 5 27-0027-01 1 1 SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Declaration of Conformity Manufacturer ’ s Name: Manufacturer ’ s Address: Declares that the product: EMC: Safety: ConformstothefollowingProductSpecications: Model Number: Product Name: Spectrum Power Management ...
-
Spectrum Brands 72A-190BQREM Series - page 6
Installation and Operation Manual SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Date: 6/02/2008 6 27-0027-01 1 1 Connections and Installation Operating Environment • Locate PDU in dry area. • Rack Mount in equipment rack using mounting brackets. • Restricted Access Location not required. • This PDU relies on protective devices in the bui ...
-
Spectrum Brands 72A-190BQREM Series - page 7
Installation and Operation Manual Date: 6/02/2008 7 27-0027-01 1 1 SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Electrical Connections • Depress rocker handle of all circuit breakers to “off” position. Example: Breaker Off Example: Breaker On • Connect input supply cord to a grounded power source rated for the input voltage and current ...
-
Spectrum Brands 72A-190BQREM Series - page 8
Installation and Operation Manual SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Date: 6/02/2008 8 27-0027-01 1 1 LAN Module and Communications RJ45 LAN Connection LAN Module Interface The LAN Module provides an interface between a computer network and the power distribution unit using the front RJ-45 jack. Communications between the PDU and a co ...
-
Spectrum Brands 72A-190BQREM Series - page 9
Installation and Operation Manual Date: 6/02/2008 9 27-0027-01 1 1 SCI P/N: 72A-196BAREM Series 72A-190BQREM Series The LAN module consists of integrated hardware and a network agent softwareprogram.Thesecomponentsprovidetheabilitytocongure, control, and monitor aspects of multiple units using a standard web browser ...
-
Spectrum Brands 72A-190BQREM Series - page 10
Installation and Operation Manual SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Date: 6/02/2008 10 27-0027-01 1 1 Connections and Installation The discovery tool “digi_dev_disc.exe” has the following: 1.“CongureNetworkSettings”istoconguretheIP/Subnet/Gateway . 2. “Restart Device” is to reboot the PDU ...
-
Spectrum Brands 72A-190BQREM Series - page 11
Installation and Operation Manual Date: 6/02/2008 1 1 27-0027-01 1 1 SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Connections and Installation T elnet Conguration Password SettingtheT elnetcongurationpasswordpreventsunauthorizedaccess of the setup menu via a T elnet connection to port 9999. The password is limited ...
-
Spectrum Brands 72A-190BQREM Series - page 12
Installation and Operation Manual SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Date: 6/02/2008 12 27-0027-01 1 1 Connections and Installation Set PDU and LAN Module to Factory Defaults Menu option 8 restores all PDU and LAN module defaults back to the factory settings. This command will ensure that both the LAN module and internal PDU microproc ...
-
Spectrum Brands 72A-190BQREM Series - page 13
Installation and Operation Manual Date: 6/02/2008 13 27-0027-01 1 1 SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Connections and Installation Exit Conguration Mode Select9toexitthecongurationmodewithoutsavinganychanges,or select 10 to exit and save all changes. All values are stored in nonvolatile RAM. ...
-
Spectrum Brands 72A-190BQREM Series - page 14
Installation and Operation Manual SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Date: 6/02/2008 14 27-0027-01 1 1 Operational Control of PDU Front Panel Menu Theunit’sLCDisusedtomonitorincomingpowerandcongurethe software. The LCD has two modes of operation: Monitor or Menu. The system menu is organized in ...
-
Spectrum Brands 72A-190BQREM Series - page 15
Installation and Operation Manual Date: 6/02/2008 15 27-0027-01 1 1 SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Operational Control of PDU PEAKS - MAX, MIN, RESET Selecting PEAKS in the menu system allows the user to view the maximum and minimum values that have been recorded for both voltage and current for each distribution bank. This featur ...
-
Spectrum Brands 72A-190BQREM Series - page 16
Installation and Operation Manual SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Date: 6/02/2008 16 27-0027-01 1 1 CONFIG - CYCLE TIME The CYCLE TIME parameter sets the amount of time to wait before displaying the next bank measurement. The parameter can be set to F AST , MEDIUM, or SLOW . CONFIG - NUMBER OF CHANNELS Theunitcanbecon? ...
-
Spectrum Brands 72A-190BQREM Series - page 17
Installation and Operation Manual Date: 6/02/2008 17 27-0027-01 1 1 SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Networking Functions The PDU LAN Port supports the T elnet and SNMP networking functions, which allow remote monitoring through the network environment. T able 1 lists the available T elnet commands. T able 2 lists the content of SNM ...
-
Spectrum Brands 72A-190BQREM Series - page 18
Installation and Operation Manual SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Date: 6/02/2008 18 27-0027-01 1 1 telnet <IP Address> 10001 [space before and after address] T able 1 List of Commands: Command Description Response @AACK Alarm Acknowledgement #AACK @SYSF Save settings to EEPROM #SYSF OK @BNKV A,? V oltage Bank A #BNKV 120.2 @ ...
-
Spectrum Brands 72A-190BQREM Series - page 19
Installation and Operation Manual Date: 6/02/2008 19 27-0027-01 1 1 SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Networking Functions @BULC B,? Read High Threshold Current Bank B #BULC 22.5 @BULC C,? Read High Threshold Current Bank C #BULC 22.5 @BULC T ,? Read High Threshold Current Bank T #BULC 77.5 @BLL V A,? Read Low Threshold V oltage Bank ...
-
Spectrum Brands 72A-190BQREM Series - page 20
Installation and Operation Manual SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Date: 6/02/2008 20 27-0027-01 1 1 Networking Functions Simple Network Management Protocol (SNMP) An SNMP-managed network consists of three key components: 1. Managed devices 2. Agents 3. Network Management Systems (NMSs) A managed device is a network node that contai ...
-
Spectrum Brands 72A-190BQREM Series - page 21
Installation and Operation Manual Date: 6/02/2008 21 27-0027-01 1 1 SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Networking Functions Interactions between the NMS and managed devices can be any of four different types of commands: reads, writes, traversal operations, and traps. Reads - T o monitor managed devices, NMSs read variables main- tain ...
-
Spectrum Brands 72A-190BQREM Series - page 22
Installation and Operation Manual SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Date: 6/02/2008 22 27-0027-01 1 1 MAXandMINdataeldsarecalculatedbythePDU. T oresetaMAXeld,writea“0”(zero)tothedatalocation. T oresetaMINeld,write“999”tothedata? ...
-
Spectrum Brands 72A-190BQREM Series - page 23
Installation and Operation Manual Date: 6/02/2008 23 27-0027-01 1 1 SCI P/N: 72A-196BAREM Series 72A-190BQREM Series SNMP v2 Functions SNMP v2 Functions V ariables SNMP v2 MIB V oltage Bank A READ & TRAP V oltage Bank B READ & TRAP V oltage Bank C READ & TRAP Current Bank A READ & TRAP Current Bank B READ & TRAP Current Bank C R ...
-
Spectrum Brands 72A-190BQREM Series - page 24
Installation and Operation Manual SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Date: 6/02/2008 24 27-0027-01 1 1 Networking Functions This section addresses the loading and compiling of MIBS into Network Management Systems (NMS). Alternatively , you can consult the docu- mentation of other NMS on MIB loading and compilation. Below are the instr ...
-
Spectrum Brands 72A-190BQREM Series - page 25
Installation and Operation Manual Date: 6/02/2008 25 27-0027-01 1 1 SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Maintenance & W arranty Maintenance and Replacement parts There are no user serviceable parts inside the PDU. In the event there is an electronic problem with the unit, please contact the factory . W arranty Undernormaluse? ...
-
Spectrum Brands 72A-190BQREM Series - page 26
Installation and Operation Manual SCI P/N: 72A-196BAREM Series 72A-190BQREM Series Date: 6/02/2008 26 27-0027-01 1 1 PDU Front Panel IEC C13 Outlets 20A Circuit Breakers ...
Do you have a question concerning Spectrum Brands 72A-190BQREM Series?
Use the form below
If you did not solve your problem by using a manual Spectrum Brands 72A-190BQREM Series, ask a question using the form below. If a user had a similar problem with Spectrum Brands 72A-190BQREM Series it is likely that he will want to share the way to solve it.