    POINT I/O EtherNet/IP Adapter Module 1734-AENT User Manual ...

  • Bradley Smoker 1734-AENT - page 2

    Important User Information Solid state equipment has operational ch aracteristics dif fer ing from those of electromechanical equipment. Safety G uidelines for the Applicati on, Installati on and Mainten ance of Solid State Controls (Publication SGI -1.1 available from your local Rockwell Automation sales o ffice or online at http://literature.rock ...

  • Bradley Smoker 1734-AENT - page 3

    1 Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Summary of Changes This publication contains new and revise d in for mation not in the last release. New and Revised Information See the table for a summary of the major changes in this manual. Change Bars Change bars (as shown with this paragraph) show the areas in this manual that are different fro ...

  • Bradley Smoker 1734-AENT - page 4

    Publication 1734-U M011C-EN-P - Ja nu ary 2006 2 Summary of Changes Notes: ...

  • Bradley Smoker 1734-AENT - page 5

    i Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 T able of Contents Preface What This Preface Contains . . . . . . . . . . . . . . . . . . . . . . . . P-1 Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . P-1 Common Techniques Used in This Manual. . . . . . . . . . . . . P-1 How To Use This Manual . . . . . . . . . . . . . . . ...

  • Bradley Smoker 1734-AENT - page 6

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 T able of Conten ts ii Chapter 3 Configure the Adapter for Your EtherNet/IP Network What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . 3-1 Configuration Requirements . . . . . . . . . . . . . . . . . . . . . . . 3-2 IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Bradley Smoker 1734-AENT - page 7

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 T able of Contents iii Chapter 6 LED Status Indicators What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . 6-1 Interpret the Status Indicators . . . . . . . . . . . . . . . . . . . . . . 6-1 Appendix A Adapter Web Pa ge s What This Appendix Contains . . . . . . . . . . . . . . . . ...

  • Bradley Smoker 1734-AENT - page 8

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 T able of Conten ts iv Appendix D Quick Start What This Appendix Contains . . . . . . . . . . . . . . . . . . . . . . D-1 Necessary Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . D-1 Configure the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-2 Enter Adapter Propertie ...

  • Bradley Smoker 1734-AENT - page 9

    1 Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Preface What This Preface Contains This preface describes how to use this manu al. See the table for a list of where to find specific in formation within this chapter . Who Should Use This Manual W e wrote this manual f or control engineers and technicians who are installing, configuring, and maintai ...

  • Bradley Smoker 1734-AENT - page 10

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 2 Preface How T o Use This Manual This manual contains an overview of th e 1734-AENT adapter . It describes how to i nstall and conf igure the adapte r and provides examples showing how to use th e adapter to communicate with POINT I/O modules over an EtherNet/IP network. About the Exampl e Application ...

  • Bradley Smoker 1734-AENT - page 11

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Preface 3 Sy stem Components W e used th e following components for the example applications. Y ou need the same or similar compon ents to set up y our own control system using POINT I/O mo du les on an EtherNet/IP network. Quantity Product Name Catalog Number Hardware 1 POINT I/O EtherNet/IP adapter 1 ...

  • Bradley Smoker 1734-AENT - page 12

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 4 Preface Where to Find More Information Refer to the following Rockwell publ ications as needed for additional help when setting up and using your EtherNe t/IP network. For Information About See This Publicati on Publication Number Using EtherNet/IP for industrial control EtherNet/IP Performance and A ...

  • Bradley Smoker 1734-AENT - page 13

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Preface 5 T erminology Refer to the table for the meaning of common ter m s . POINT I/O protected sink output module POINT I/O Protected Sink Output Module Installation Instructions 1734-IN585 POINT I/O 2 relay output module POINT I/O 2 Relay Output Module In stallation Instructions (OX2) 1734-IN587 PO ...

  • Bradley Smoker 1734-AENT - page 14

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 6 Preface consumer A destination device in the CIP networking model. See CIP . CSMA/CD Carrier sense multiple access/collision detection is the access method used in Ethernet. When a device wants to gain access to the network, it checks to see if the network is quiet (senses the carrier). If it is not, ...

  • Bradley Smoker 1734-AENT - page 15

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Preface 7 Gateway A module or set of modules that allows communications between nodes on dissimilar networks. Hardware address Each Ethernet dev ice has a unique hardware address (sometimes called a MAC address) that is 48 bits. The address appears as six digits separated by colons (such as, xx:xx:xx:x ...

  • Bradley Smoker 1734-AENT - page 16

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 8 Preface TCP/IP The transmission control protocol/internet protocol is a transport-layer protocol (TCP) and a network-layer protocol (IP) commonly used for communication within networks and across internetworks. T ransaction An exchange of request and data and response and data . UDP The user datagram ...

  • Bradley Smoker 1734-AENT - page 17

    1 Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Chapter 1 About the Adapter What This Chapter Contains This chapter provides an overview of th e 173 4-AENT POINT I/O EtherNet/IP adapter , its primary features, and how to use it. Y ou need to understand the concepts di scussed in this chapter to configure your adapter and use it in an EtherNet/IP c ...

  • Bradley Smoker 1734-AENT - page 18

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 1-2 About the Adapter Y ou must set the chassis size to a number equaling 1 slot for the adapter plus 1 slot for each I/O module present in the adapter’s backplane. For example, the adapter plus 4 I/O modules uses a chassis size of 5. The adapter stores this chassis size setting in non-volatile stora ...

  • Bradley Smoker 1734-AENT - page 19

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 About the Adapter 1-3 • A correct POINT I/O system does not have any empty ter minal bases. • After you cycl e power , the adapter will not run an y I/O until the number of modu les comprising th e chassis equal s the stored chassis size. – Because the adapter cannot detect empty terminal bases, ...

  • Bradley Smoker 1734-AENT - page 20

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 1-4 About the Adapter Cycle Power T o a Sy stem For the First T ime When you power POI NT I/O for the fi rst time, the adap ter must assign addresses to every module in the backplane. POINT I /O modules all ship configu red at the same address. When you first apply power , we expect that all but one mo ...

  • Bradley Smoker 1734-AENT - page 21

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 About the Adapter 1-5 Hardware/Software Compatibility The 1734-AENT adapter and the applic ations described in this manual are compatible with the following firmware revisions and software releases. Contact Rockwell Auto mation if yo u need software o r firmware upgrades to use this equipment. What the ...

  • Bradley Smoker 1734-AENT - page 22

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 1-6 About the Adapter This has the following significant benefits. • Y ou do not need to configure ro uting tables in th e bridging modules, which greatly simplifies main tenance and modul e replacement . • Y ou maintain full control over the route taken by each message, which enables you to se lec ...

  • Bradley Smoker 1734-AENT - page 23

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 About the Adapter 1-7 Support of Rack-optimized and Direct Connections The 1734-AENT adapter supports bo th direct and rack-optimized connections. A direct connection is a real-time d ata transfer link between the contro ller and whatever mo dule occupies the slot that the configur ation data reference ...

  • Bradley Smoker 1734-AENT - page 24

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 1-8 About the Adapter Before Y ou Begin T o effectively use yo ur adapter , note the follow in g considerations. Determine Compatibility If using the adapter with a 1756 -ENBT module or 1788-ENBT module, use the following req uired firmware revisions for these bridge modules: • 1756-ENBT firmware rev ...

  • Bradley Smoker 1734-AENT - page 25

    1 Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Chapter 2 Install the Adapter What This Chapter Contains This chapter describes how to phys ical ly install the adapter on the DIN rail and connect it to the EtherNet/IP network. Th e fol lowing table lists whe re to find specific in formation. Identify Adapter Components Use the figure to iden tify ...

  • Bradley Smoker 1734-AENT - page 26

    Publication 1734-U M011C-EN-P - Decemb er 2006 2-2 Install the Adapter Mount the Adapter on a DIN Rail Before Installing Modules Use the following procedur e to mo unt the adapter on a new system before you install any I/O mo dules. 1. Position the adapter vertic a lly above the DIN rail. 2. Press down firmly to install the adapte r on the DIN rail ...

  • Bradley Smoker 1734-AENT - page 27

    Publication 1734-UM0 11C-EN-P - December 20 06 Install the Adapter 2-3 Mount (or Replace) the Adapter to an Existing Sy stem Follow these steps to mou n t (or replace) an adapter . 1. Remove the existing adapter (if there is one) from the DIN rail as follows: a. Pull up on the RTB removal ha ndle to remove the terminal block. b. Disconnect the Ethe ...

  • Bradley Smoker 1734-AENT - page 28

    Publication 1734-U M011C-EN-P - Decemb er 2006 2-4 Install the Adapter Wiring Refer to the illu s tr a t io n to wire the adapter . WARNIN G If you connect or discon nect wiring while the field-side power is on, an electrical arc can occur . This could cause an explosion in hazardous location installations. Be sure that power is removed or the area ...

  • Bradley Smoker 1734-AENT - page 29

    Publication 1734-UM0 11C-EN-P - December 20 06 Install the Adapter 2-5 Mounting Dimensions Refer to the figu re for mounting dimensions. millimeters (inches) A = DIN rail B = Secure DIN ra il approximate ly every 200 mm (7.8 in.) A B 133.4 (5.25) 76.5 (3.0) 43520 36.51 (1.44) 54.9 (2.16) 1734-AENT 76.2H x 54.9W x 133.4D (3.0H x 2. 16W x 5.25D) ...

  • Bradley Smoker 1734-AENT - page 30

    Publication 1734-U M011C-EN-P - Decemb er 2006 2-6 Install the Adapter Notes: ...

  • Bradley Smoker 1734-AENT - page 31

    1 Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Chapter 3 Configure the Adapter for Y our EtherNet/IP Network What This Chapter Contains Before using your adapter in an Ethe rNe t/IP ne two rk, configure it with an IP address, su bnet mask, and optional Gateway address. This chapter descr ibes these configu ration requir ements and th e procedure ...

  • Bradley Smoker 1734-AENT - page 32

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 3-2 Configure the Adapte r fo r Y our EtherNet/IP Network Configuration Requirements Before you can use y our ad apter , you must con figur e its IP address, its subnet mask, and, option ally, gateway address. Y ou can us e the Rockwell BootP util ity, version 2.3 or later , to perform the configuratio ...

  • Bradley Smoker 1734-AENT - page 33

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Configure the Adapter for Y o ur EtherNet /IP Network 3-3 IP Address The IP address identifies each node on the IP netwo rk (or syste m of connected networks). Each TCP/IP node on a network (including th e 1734-AENT adapter) must ha ve a unique IP address. The IP address is 32 bits long and has a ne t ...

  • Bradley Smoker 1734-AENT - page 34

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 3-4 Configure the Adapte r fo r Y our EtherNet/IP Network IP addresses are written as four deci mal integers (0 to 255) separated by periods where each integer gives the value of one by te of the IP address. Gateway Address This section applies to multi-network systems. If yo u have a single network sy ...

  • Bradley Smoker 1734-AENT - page 35

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Configure the Adapter for Y o ur EtherNet /IP Network 3-5 The gateway has two IP addresses (1 28.1.0.2 and 128.2.0 .3). The fi rst must be used by ho sts on Network 1 and th e second must be us ed by hosts on Network 2. T o be usable, a host’s gateway must be addressed us in g a net ID matching its o ...

  • Bradley Smoker 1734-AENT - page 36

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 3-6 Configure the Adapte r fo r Y our EtherNet/IP Network The new configuration is: A second network with Hosts D and E was added. Gateway G2 connects Network 2.1 with Network 2.2. Hosts D and E will use G ateway G2 to communicate with ho sts not on Network 2.2. Hosts B and C will use Gatew ay G to com ...

  • Bradley Smoker 1734-AENT - page 37

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Configure the Adapter for Y o ur EtherNet /IP Network 3-7 Set the Network Address The adapter ships with th e thumbwheel switches set to 999 an d DHCP enabled. Y ou can set the network Internet Protocol (IP) address in these ways: • Use the thumbwhe el swit ches located on the mod ule . • Use a Dyn ...

  • Bradley Smoker 1734-AENT - page 38

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 3-8 Configure the Adapte r fo r Y our EtherNet/IP Network Use the Rockwell BootP/DHCP Utility The Rockwell BootP/DHC P util ity is a stand alone program that incorporates the funct ionality of standard BootP software with a user friendly graph ic al interf ace . It is located in the Uti ls directory on ...

  • Bradley Smoker 1734-AENT - page 39

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Configure the Adapter for Y o ur EtherNet /IP Network 3-9 3. Enter the IP Addres s you want to assign to the device, and click OK. The device is added to the Relati on List, displaying the Ethernet Address (MAC) and cor responding IP Addres s, Hostname, and Description (if applicable). When the addres ...

  • Bradley Smoker 1734-AENT - page 40

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 3-10 Configure the Adapt er for Y our EtherNet/IP Network 5. T o e nable DHCP for a device wi th DHCP disabled, highlight the device in the Relation List, an d click the Enable DHCP button. Y ou must have an entry for the device in the Relation List panel to re-enable DHCP . Save the Relation List Y ou ...

  • Bradley Smoker 1734-AENT - page 41

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Configure the Ada pter for Y our EtherNet/IP Network 3-11 Y ou see the Save As dial og. 2. Select the folder yo u want to Save in. 3. Enter a File name for the Relati on List (for example, co ntrol system configuration), and clickclick Save. Y ou can leave the Save as type at the default setting: Bootp ...

  • Bradley Smoker 1734-AENT - page 42

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 3-12 Configure the Adapt er for Y our EtherNet/IP Network Refer to the section Configure the 1734- AENT Adapter with Fixed IP Address in this manual to config ure the adapter with a fixed IP address. ATTENTION T o avoid unintended control, the 17 34-AENT adapter must be assigned a fixed IP address. The ...

  • Bradley Smoker 1734-AENT - page 43

    1 Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software What This Chapter Contains In this example, a ControlLogix controller communica tes with POINT I/O modules via the 1734-AENT adapter using a direct connection. The adapter makes a direct connection to each of the modu le s ...

  • Bradley Smoker 1734-AENT - page 44

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 4-2 Configur e the Adapter for Direct Co nnection in RSL ogix 5000 Sof tware W e moun ted the 1734-AENT adapter on a DIN rail in slot 0, with a 1734-OW2/C rela y output module in slo t 1, a 1734- OV4E/C sink output module in slot 2, and a power supply (n ot shown). To w or k al o n g w i t h t h i s e ...

  • Bradley Smoker 1734-AENT - page 45

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure the A dapter for Direct Connectio n in RSLogix 5000 Software 4-3 2. From the File menu, sele ct Ne w. The New Controller dialog opens. 3. Enter an appropriate Name for the Controller , for example, POINT_IO_Contr oller . 4. Select the correct V ersion, Chassis Type, and Slot n umber of th ...

  • Bradley Smoker 1734-AENT - page 46

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 4-4 Configur e the Adapter for Direct Co nnection in RSL ogix 5000 Sof tware Configure the I/O Y ou now add the POINT I/O mo dules to the controlle r’s I/O configuratio n pe rfor ming these proc edures. • Add the local 1756-E NBT mo du le to the I/O configuration . • Add the 173 4-AENT adapter a ...

  • Bradley Smoker 1734-AENT - page 47

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure the A dapter for Direct Connectio n in RSLogix 5000 Software 4-5 The Select Module dialog op ens. 3. Click + next to Communication s to ex pand, as in the followin g dialog. 4. Select the 1756-ENBT Eth erNet/IP Bridge, and click OK. The Select Major Revision dialog opens. 5. Select the num ...

  • Bradley Smoker 1734-AENT - page 48

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 4-6 Configur e the Adapter for Direct Co nnection in RSL ogix 5000 Sof tware The New Module dialog open s. 6. Enter values for Name, IP Address, Slot, Electro nic Key ing, and Revision, noting that we used the following values: 7. Click OK to accept the configuration. The Module Properties dialo g ope ...

  • Bradley Smoker 1734-AENT - page 49

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure the A dapter for Direct Connectio n in RSLogix 5000 Software 4-7 Add the POINT I/O Adapter to the I/O Configuration Next, you must add th e 1734-AENT adapter as a child of the local 1756-ENBT module. 1. In the Project dialog, right-cl ick the local 1756-ENBT mo dule under the I/ O Configur ...

  • Bradley Smoker 1734-AENT - page 50

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 4-8 Configur e the Adapter for Direct Co nnection in RSL ogix 5000 Sof tware 2. Click + next to Communications to expand . 3. Select the 1734-AENT/A Ethernet adapter from the list, and click OK, noting that we used these values. Name POINT_IO_Adapter IP Address 10.88.70.2 Comm Format None Chassis Size ...

  • Bradley Smoker 1734-AENT - page 51

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure the A dapter for Direct Connectio n in RSLogix 5000 Software 4-9 The New Module dialo g open s. Comm Format choices are the foll owing. • None = the adapter makes a direct connection to each of the modules referenced by the data. • Rack optimization = digital I/O data is collected into ...

  • Bradley Smoker 1734-AENT - page 52

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 4-10 Configure the Adapt er fo r Direct Connection in RSLogix 50 00 Software Add the POINT I/O Modules to the I/O Configuration Y ou now add POINT I/O modu les to the I/O C onfiguration List und er the 1734-AENT adapter . In this example, yo u add a 1734 -OW2 relay ou tput and a 1734-OV4E sink output ...

  • Bradley Smoker 1734-AENT - page 53

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure the Adap te r for Direct Connection in RSLogix 5000 Software 4-11 The Select Module dialog op ens. 2. Click the + next to Digital to expand. 3. Select the 1734-OW2 relay outpu t module from the list, and click OK. ...

  • Bradley Smoker 1734-AENT - page 54

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 4-12 Configure the Adapt er fo r Direct Connection in RSLogix 50 00 Software The New Module dialog open s. 4. Enter values for Name and Slot, noting that we used th e following values. 5. Choose Connection . The RPI is selectable sin ce it is a direct con nection. Name POINT_Relay_Output Slot 1 ...

  • Bradley Smoker 1734-AENT - page 55

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure the Adap te r for Direct Connection in RSLogix 5000 Software 4-13 6. Enter 50 for requ ested packet interval (RP I ) to set ho w often you exchange data with the 17 34-AENT adapter . 7. Click OK save the configuration. The relay o utput module appe ars under Etherne t. Add the Digital Outp ...

  • Bradley Smoker 1734-AENT - page 56

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 4-14 Configure the Adapt er fo r Direct Connection in RSLogix 50 00 Software The Select Module dialo g opens. 2. Click + next to Digital to expand . 3. Select the 1734-OV4E digital output module from the list. 4. Click OK. ...

  • Bradley Smoker 1734-AENT - page 57

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure the Adap te r for Direct Connection in RSLogix 5000 Software 4-15 The New Module dialog opens. 5. Enter values for Name and Slo t, noting we used the following. 6. Click Connection at th e top of the scr een. 7. Enter 10 ms as the RPI for the 1734-OV4E module . 8. Click OK. Name POINT_Digi ...

  • Bradley Smoker 1734-AENT - page 58

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 4-16 Configure the Adapt er fo r Direct Connection in RSLogix 50 00 Software The I/O Configuration in the Proj ect dialog should look similar to the following. Edit the Controller T ags When you add modules to t he I/O configurat ion the syste m creates tags for those modules to use in the application ...

  • Bradley Smoker 1734-AENT - page 59

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure the Adap te r for Direct Connection in RSLogix 5000 Software 4-17 The Controller T ags dialog opens. Y ou see the tags created for the 1734-AENT adapte r and digital I/O module s. 2. Click the Edit T ags tab at the bottom of the Controller T ags dialog. 3. Create the following tag : 4. Clo ...

  • Bradley Smoker 1734-AENT - page 60

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 4-18 Configure the Adapt er fo r Direct Connection in RSLogix 50 00 Software Create the Ladder Program Next create the example ladder program to test the I/O. 1. Double-click Main Routine under the Main Progra m fold e r. 2. Enter the follo wing ladder program usin g the tags pr eviously created. 3. S ...

  • Bradley Smoker 1734-AENT - page 61

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure the Adap te r for Direct Connection in RSLogix 5000 Software 4-19 1. From the main menu, choo se Communic ations>Who -Active. Y ou see the Who Active dialog. 2. Navigate to select the sl ot where the contro ller is located i n the chassis. 3. Choose Set Project Path. 4. Choose Down load ...

  • Bradley Smoker 1734-AENT - page 62

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 4-20 Configure the Adapt er fo r Direct Connection in RSLogix 50 00 Software 5. From the Downl oad dialog, choose D ownload to see the RSLogix5000 software dialog. 6. Notice that the 1756-ENB T Bridge is now onli ne . If yellow triangles are pr esent, see the following section . V erify the Module Cha ...

  • Bradley Smoker 1734-AENT - page 63

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure the Adap te r for Direct Connection in RSLogix 5000 Software 4-21 Y ou see the Module Fault error code. 5. Click the Chassis Size tab. 6. Click Set Chassis Size in Module . 7. Read and acknowledge the warning dialog. V alue from RSLogix 5000 software V alue sto red in 1734-AENT adapter ...

  • Bradley Smoker 1734-AENT - page 64

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 4-22 Configure the Adapt er fo r Direct Connection in RSLogix 50 00 Software 8. Click OK to co ntinue. Notice the chassis size in th e module is modifie d to 3. 9. Click OK. At this point, your POINTBus st atus LED should be solid green. All the yellow tri a ng les in your I/O configuration shou ld be ...

  • Bradley Smoker 1734-AENT - page 65

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure the Adap te r for Direct Connection in RSLogix 5000 Software 4-23 2. Click the Enable DHCP box so th at there is not a checkmark in the box. 3. Click the Set button. 4. Read and acknowledge the warning. 5. Click OK. 6. Click the Refresh button to ve rify th e changes. ...

  • Bradley Smoker 1734-AENT - page 66

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 4-24 Configure the Adapt er fo r Direct Connection in RSLogix 50 00 Software Recover From an Overloaded Adapter Each POINT I/O connection established with the 1734-A ENT adapter consumes a portion of the micropro ce sso r’s bandwidth. The amount of bandwidt h used by a connection depend s on a numb ...

  • Bradley Smoker 1734-AENT - page 67

    1 Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software What This Chapter Contains This chapter guides you through the ste ps req ui red to confi g ure your 1734 POINT I/O Ethernet adapter for both direct connection and rack optimization using RSLogix 5000 ...

  • Bradley Smoker 1734-AENT - page 68

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 5-2 Configur e the Adapter f or Direct Conn ection and Rack Optimization in RSLogix 5000 Soft ware Set Up the Hardware In this example, a Co ntrolLogix chassis contains the Logix 5555 controller in slot 1 and a 17 56-ENBT bridge module in slot 3. W e mounted th e 1734-AENT adapter on a DIN rail in slo ...

  • Bradley Smoker 1734-AENT - page 69

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure th e Adapter fo r Direct Connec tion and Rack Opt imization in RSLo gix 5000 Software 5-3 Create the Example Application Perform the following steps to create the example application: 1. Start RSLogix 50 00 Enterprise Serie s software. Y ou see the RSLogix 5000 main dialog. 2. From the Fil ...

  • Bradley Smoker 1734-AENT - page 70

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 5-4 Configur e the Adapter f or Direct Conn ection and Rack Optimization in RSLogix 5000 Soft ware 5. Complete the Create In entry by selecting the folder whe re yo u want to save the RSLogi x 5000 file. 6. T o use redundancy in your sy stem, check the Redun dancy Enabled checkbox so th at a checkmark ...

  • Bradley Smoker 1734-AENT - page 71

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure th e Adapter fo r Direct Connec tion and Rack Opt imization in RSLo gix 5000 Software 5-5 2. Click New Module. The Select Module dialog op ens. 3. Click + next to Communication s to ex pand, as in the followin g dialog. 4. Select the 1756-ENBT Eth erNet/IP Bridge, and click OK. ...

  • Bradley Smoker 1734-AENT - page 72

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 5-6 Configur e the Adapter f or Direct Conn ection and Rack Optimization in RSLogix 5000 Soft ware The Select Majo r Revision dialog o pens. 5. Select the value for Major Re vision, and click OK. The Module Propertie s dialo g opens. 6. Enter value for Name, IP Addr ess, Slot, Electron ic Keying, and ...

  • Bradley Smoker 1734-AENT - page 73

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure th e Adapter fo r Direct Connec tion and Rack Opt imization in RSLo gix 5000 Software 5-7 Add the POINT I/O Adapter to the I/O Configuration Next, you must add th e 1734-AENT adapter as a child of the local 1756-ENBT module. 1. In the Project dialog, right-cl ick the local 1756-ENBT mo dul ...

  • Bradley Smoker 1734-AENT - page 74

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 5-8 Configur e the Adapter f or Direct Conn ection and Rack Optimization in RSLogix 5000 Soft ware 2. Click + next to Communications to expand . 3. Select the 1734-AENT/A Ethernet adapter from the list, and click OK. The New Module dialog open s. ...

  • Bradley Smoker 1734-AENT - page 75

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure th e Adapter fo r Direct Connec tion and Rack Opt imization in RSLo gix 5000 Software 5-9 4. Enter values for Name, IP Address, Comm F ormat, Chassis Size, Electronic Keying, an d Revision, noting we used the following values. Comm Format choices include: • None = the adapter makes a dir ...

  • Bradley Smoker 1734-AENT - page 76

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 5-10 Configure the Ada pt er for Direct Connec tion an d Ra ck Optimization in RSLogix 5000 So ft ware The Module Properties dialo g opens. 7. V erify that the requested packet interval (RPI) is appropriate for your system. Y ou use this value for the rack -optimized connecti on to the I/O modules. 8. ...

  • Bradley Smoker 1734-AENT - page 77

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure th e A dapter for Direct Co nn ection and Rack Optimization in RSLo gix 5000 Software 5-11 Add the POINT I/O Module and Configure for Direction Connection 1. Highlight the 1734-AENT adapte r unde r th e I/O Configuratio n folder , and se lect New Module. The Select Module dialog op ens. 2. ...

  • Bradley Smoker 1734-AENT - page 78

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 5-12 Configure the Ada pt er for Direct Connec tion an d Ra ck Optimization in RSLogix 5000 So ft ware The New Module dialog opens. 4. Enter values for Name and Slot,noting we u sed the follow ing values. 5. Choose Connection . The RPI is selectable, since it is a direct connection. Name POINT_Relay_O ...

  • Bradley Smoker 1734-AENT - page 79

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure th e A dapter for Direct Co nn ection and Rack Optimization in RSLo gix 5000 Software 5-13 6. V erify that the requested packe t in te rval (RPI) is appropriate for your system (10 ms for this example). Y ou use this value for the rack-optimized conn ection to the I/O module s. 7. Click OK ...

  • Bradley Smoker 1734-AENT - page 80

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 5-14 Configure the Ada pt er for Direct Connec tion an d Ra ck Optimization in RSLogix 5000 So ft ware Add the POINT I/O Module and C onfigure For Rack Optimization 1. Right-click the 1734-AENT adapter under the I/O Configuration folder , and select New Module. . The Select Module dialo g opens. IMPOR ...

  • Bradley Smoker 1734-AENT - page 81

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure th e A dapter for Direct Co nn ection and Rack Optimization in RSLo gix 5000 Software 5-15 2. Click the + next to Digital to expand. 3. Choose the 1734 - OV 4E/C module, and click OK. The New Module dialo g open s. 4. From the New Module di alo g , complete the following. • Enter a value ...

  • Bradley Smoker 1734-AENT - page 82

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 5-16 Configure the Ada pt er for Direct Connec tion an d Ra ck Optimization in RSLogix 5000 So ft ware Y ou see the Mo dule Definit io n screen. 5. From the Module Definition dialog, for Con necti on, select Rack Optimizatio n. 6. From the Module Definitio n dialog, click OK. Y ou see the New Modu le ...

  • Bradley Smoker 1734-AENT - page 83

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure th e A dapter for Direct Co nn ection and Rack Optimization in RSLo gix 5000 Software 5-17 9. Keep the following unchecked . • Inhibit Module • Major Fault on Controller If Con nectio n fail s While in Run Mode 10. Click OK. 11. Choose File> Save and ente r th e name and location of ...

  • Bradley Smoker 1734-AENT - page 84

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 5-18 Configure the Ada pt er for Direct Connec tion an d Ra ck Optimization in RSLogix 5000 So ft ware Y ou see the Download dialog. 5. From the Download di alog, cli ck Download. Y ou see this RSLogix 5000 dialog. 6. Notice that the 1756-ENB T Bridge is now onli ne . 7. If yellow triangles are pr ese ...

  • Bradley Smoker 1734-AENT - page 85

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure th e A dapter for Direct Co nn ection and Rack Optimization in RSLo gix 5000 Software 5-19 Y ou see the Module Fault error code. 5. Click the Chassis Size tab. 6. Click Set Chassis Size in Module. 7. Read and acknowledge the warning dialog. V alue from RSLogix 5000 software V alue stored i ...

  • Bradley Smoker 1734-AENT - page 86

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 5-20 Configure the Ada pt er for Direct Connec tion an d Ra ck Optimization in RSLogix 5000 So ft ware 8. Click OK to co ntinue. 9. Notice the chassis size in th e module is modifie d to 3. 10. Click OK. At this point, your POINTBus st atus LED should be solid green. All the yellow tri a ng les in you ...

  • Bradley Smoker 1734-AENT - page 87

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Configure th e A dapter for Direct Co nn ection and Rack Optimization in RSLo gix 5000 Software 5-21 Access Module Data Use the following i nformation to use the 1734 POINT I/O Ethe rnet adapter data in the ladder logic program. • POINT_IO_Ad a pte r = the name you gave to you r Ethern e t adapter ...

  • Bradley Smoker 1734-AENT - page 88

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 5-22 Configure the Ada pt er for Direct Connec tion an d Ra ck Optimization in RSLogix 5000 So ft ware Use the controller tags in your ladder pro gram to read input data or write output data. • For RSLogix 5000 programming instruc tions, refer to RSLogix 5000 Getting Resu lts, publication 93 99-RLD3 ...

  • Bradley Smoker 1734-AENT - page 89

    1 Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Chapter 6 LED Status Indicators What This Chapter Contains Read this chapter for informatio n about LED status indicators. Interpret the Status Indicators ATTENTION Y ou must use series C POINT I/O modules with the 1734-AENT adapter . Series A or B POINT I/O modules will not work with this adapter . ...

  • Bradley Smoker 1734-AENT - page 90

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 6-2 LED Status Indicators Indication Probable Cause Recommended Action Network Activity Off No link established. V erify network cabling, and correct, as needed. Flashing Green/Off T ransmit or receive activity present. None Steady Green Link established. None Network St atus Off Device not initialize ...

  • Bradley Smoker 1734-AENT - page 91

    1 Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Appendix A Adapter W eb Pages What This Appendix Contains Read this appendix for informat ion about the adapter W eb page diagnostics that offer extensive internal and network diagnostics. W ork with the Home Page Use the adapter diagnostics Home page to access other ad apte r diagnostics W eb pages ...

  • Bradley Smoker 1734-AENT - page 92

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 A-2 Adapter Web Pages 1. From a browser s uch as Netscape or M icrosoft Inter net Explo rer , enter the adapter IP addre ss to see the Home page. 2. From the Home page, click Expa nd to expand options, as in the figure, or Mi ni mize to see Di agnostics, Configuration, and Browse Chassis options witho ...

  • Bradley Smoker 1734-AENT - page 93

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Adapter W eb Pages A-3 3. From the Home page , complete one o f these, as desired. • Click one of these to go to http://www.ab.com/. – Allen-Bradley logo at the top of the page – Visit AB.com for additional infor m ation stateme nt under Resour ces • Click Rockwell Automati on at the top rig ...

  • Bradley Smoker 1734-AENT - page 94

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 A-4 Adapter Web Pages Use the Diagnosti c Overview Page T o use the Diagnostic Overvi ew page to view general diagnostic s inform ation, follow this proced ure. 1. From the W eb page, click Diagnostic Overview from the tab at the top of the page or panel on the left. Y ou see the Diagnostic Ov erview ...

  • Bradley Smoker 1734-AENT - page 95

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Adapter W eb Pages A-5 – Open Errors – Conn Closes – Close Errors – Conn Timeout – Status • Module Settings – Chassis Size – Switches Use the Network Settings Page T o use the Network Settings pa ge to view network related information, follow this procedure. 1. From the W eb page, cl ...

  • Bradley Smoker 1734-AENT - page 96

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 A-6 Adapter Web Pages 2. From the Network Settings page, view the following. • Network Interface – Ethernet Address (MAC) – IP Addres s – Subnet Mask – Default Gateway – Primary Name Server – Secondary Name Server – Default Domain Nam e – Host Name – Name Resolution • Ethernet In ...

  • Bradley Smoker 1734-AENT - page 97

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Adapter W eb Pages A-7 Y ou see the Ethernet Statistics page. 2. From the Ethernet Statistics page, view the foll owi ng. • Ethernet Link – Media Speed, H alf or Full Duplex, Autonegotiate Status • Interface Counters – In Octets, In UCast Pack ets, In NUcast Packe ts, In Discards, In E rrors ...

  • Bradley Smoker 1734-AENT - page 98

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 A-8 Adapter Web Pages Use the I/O Connections Page T o use the I/O Connections page to view CI P I/O (Class 1) connection information, foll ow this procedure. 1. From the W eb page, click I/O Connectio ns from the tab at the top of the page or panel on the left. Y ou see the I/ O Connections page. 2. ...

  • Bradley Smoker 1734-AENT - page 99

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Adapter W eb Pages A-9 Use the Diagnostic Messaging Page T o use the Diagnostic Messag in g page to execute explicit, unconnecte d me ssage services, use th is procedur e . 1. From the W eb page, click Diag n ost ic Messaging from the tab at the top of the page or panel on the left. Y ou see the Dia ...

  • Bradley Smoker 1734-AENT - page 100

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 A-10 Adapter Web Pages 3. From the Diagnostic Messaging pa ge, click Submit to see values similar to that in the figure. W ork with the Configuration Pages T o work with the Configuration pages, follow these procedures, noting that values on these pages are stored in and retrieved from non-volatile me ...

  • Bradley Smoker 1734-AENT - page 101

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Adapter Web Pages A-11 1. From the Home page, click Config uration or Expand to see the Configuratio n options, if nee ded. 2. From the Configurat ion page, clic k one of these. • Identity • Network • Services Y ou see a dialog pr ompting you for a user name and password, as shown in the figur ...

  • Bradley Smoker 1734-AENT - page 102

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 A-12 Adapter Web Pages Y ou see the Id en tity page. 2. From the Identity page, comple te entries for the following, noting that the description and location help you identify wher e modules are in the facility. • Host Name - the name a Domain Name Server uses to resolve this adapter’s IP address ...

  • Bradley Smoker 1734-AENT - page 103

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Adapter Web Pages A-13 Y ou see the Network Configuratio n page. 2. From the Network Conf ig uration page, co mplet e these entries, noting that val ues for Network Interface are d isabled when DHCP is Dynamic DHCP and port spe ed and du plex mode are disabled when Autonegotiate Spee d and Duplex is ...

  • Bradley Smoker 1734-AENT - page 104

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 A-14 Adapter Web Pages Use the Services Page T o use the Services page to change the C onfiguration web page’s password or disable the W e b se rv er , complete the se procedures. 1. From the W eb page, click Services from the tab at the t op of the page or panel on the left. Y ou see the Services p ...

  • Bradley Smoker 1734-AENT - page 105

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Adapter Web Pages A-15 W ork with the Browse Chassis Page Use the Browse Chassis page for th e following. • See what modules are present on the system. • Run a query from slot 1 to slot 63. • Display the modules fou nd based on the query. • Provide an easy way to see what mo du le s the adap ...

  • Bradley Smoker 1734-AENT - page 106

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 A-16 Adapter Web Pages 4. From the Browse Chassis page, click Start to ru n the query, noting that you see a page such as the one in the the figure , which shows that modu le hyperlinks are disab led while browsing before the qu ery completes or is ca nce lled. Before the query completes, this note ab ...

  • Bradley Smoker 1734-AENT - page 107

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 Adapter Web Pages A-17 After completion of a query, he re is how a typica l Browse Chassis page looks with the modu le hyper links ac tive and the Display compact check box unchecked. Here is how a typical Browse Chassis page looks with the Display compact check box checked. Click a module hyperlink ...

  • Bradley Smoker 1734-AENT - page 108

    Publication 1734 -U M011C-EN-P - Ja nu ary 2006 A-18 Adapter Web Pages 5. From the Browse Chassis page, to view information about a particular module, click the module’s Module Description hyperlink. Y ou see a page showing this infor mation about the module: • Product Name • V endor • Product T ype • Product C ode • Module Revision • ...

  • Bradley Smoker 1734-AENT - page 109

    1 Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Appendix B Configure the RSLinx Ethernet Communication Driver What This Appendix Contains T o communicate with your 1734-AENT ad apter over your network you must confi gure the RSLinx Ethernet communication drive r (AB_ETH) or the EtherNe t /I P driv er (AB-ETHIP). Y ou can co nfigure the AB_ETH driv ...

  • Bradley Smoker 1734-AENT - page 110

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 B-2 Configure t he RSLinx Ether net Communication Dr iver 4. Click OK. Y ou see the progress bar , followed by the welcome screen . Configure the AB_ETH Driver T o configure th e AB-ET H Ethe rnet communic ation driver perform the following steps: 1. Start RSLinx software. 2. From the Communic ations m ...

  • Bradley Smoker 1734-AENT - page 111

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Configure th e RSLinx Ethernet Co mmunication Drive r B-3 Y ou are prompted to name the dri ver . 5. Select the default driv er n ame (fo r example, AB_ETH-1) or type in a name and click OK. The Configure driver dialog appears with the Station Mapping page ope n. 6. Click Add New and enter the IP addre ...

  • Bradley Smoker 1734-AENT - page 112

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 B-4 Configure t he RSLinx Ether net Communication Dr iver The new driver appears in the list of configured drivers. (Y our list displays the drivers you configured on your workstati on .) 10. Close RSLinx so ftware . Configure the AB_ETH/IP Driver T o configure the AB-ETHI P Ethe rnet communicati on dr ...

  • Bradley Smoker 1734-AENT - page 113

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Configure th e RSLinx Ethernet Co mmunication Drive r B-5 4. Select EtherNet/IP Devices an d click Add/New. Y ou see this window. 5. Make sure the Brow se Local S ubnet button is selected. ...

  • Bradley Smoker 1734-AENT - page 114

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 B-6 Configure t he RSLinx Ether net Communication Dr iver RSLinx software brow ses your local sub net and automaticall y reads the IP address. 6. Click OK. The AB-ETHIP driver is now confi gured and appears in the configured drive rs window. 7. Close RSLinx software . ...

  • Bradley Smoker 1734-AENT - page 115

    1 Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Appendix C 1734 POINT I/O Module/RSLogix 5000 Controller T ag Reference What This Appendix Contains Read this appendix for info rmation about tag references. 1734 POINT I/O Catalog Numbers ATTENTION Y ou must use series C POINT I/O modules with the 1734-AENT adapter . Series A or B POINT I/O modules ...

  • Bradley Smoker 1734-AENT - page 116

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-2 1734 POINT I/O Module/ RSLogix 5000 Controller T a g Reference Note that all POINT I/O module s must be series C or above for RSLogix 5000 software, ve rsion 11, compatibility. The 1734-232ASC/A (ser ies A) is pres en tl y the only exception to the series C requiremen t. With RSLogix 5000 software ...

  • Bradley Smoker 1734-AENT - page 117

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I/O Module /RSLogix 5000 Controlle r T ag Reference C-3 Digital 2 POINT Input 1734-IA2 2 POINT 120V ac Input 1734-IB2 2 POINT 10V…28V dc Input, Sink 1734-IM2 2 POINT 240V ac Input 1734-IV2 2 POINT 10V…28V dc Input, Source Configuration Data Data T ype Default Va l u e V alid Data V alues ...

  • Bradley Smoker 1734-AENT - page 118

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-4 1734 POINT I/O Module/ RSLogix 5000 Controller T a g Reference Digital 4 POINT Input 1734-IB4 4 POINT 10…28V dc Input, Sink 1734-IV4 4 POINT 10…28V dc Input, Source Configuration Data Data T ype Default Va l u e V alid Dat a V alues Filter Off On T ime - POINT 0 INT 1,000 -32,768…32,767 µ s ...

  • Bradley Smoker 1734-AENT - page 119

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I/O Module /RSLogix 5000 Controlle r T ag Reference C-5 Digital 2 POINT Output – Without Diagnostic Status 1734-OA2 2 POINT 120V ac Output 1734-OW2 2 POINT ac/dc Relay Output 1734-OX2 2 POINT Relay Output N.O./N.C. Configuration Da ta Data T ype Defa ult Va l u e V alid Data Values Fault M ...

  • Bradley Smoker 1734-AENT - page 120

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-6 1734 POINT I/O Module/ RSLogix 5000 Controller T a g Reference Digital 2 POINT Output – With Over Load and Open Load Diagnostic Status 1734-OB2E 2 POINT 10V…28V dc Electronically Fused Output, Source 1734-OB2EP 2 POINT 10V…28V dc Electronically Fused Protected Output, Sourc e Configuration Da ...

  • Bradley Smoker 1734-AENT - page 121

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I/O Module /RSLogix 5000 Controlle r T ag Reference C-7 Digital 2 POINT Output – With Over Load Diagnostic Status 1734-OV2E 2 POINT 10V…28V dc Electronically Fused Output, Sink Configuration Data Data T ype Default Va l u e V alid Data V alues Fault Mode - POINT 0, 1 SINT , BIT 0 0=Fault ...

  • Bradley Smoker 1734-AENT - page 122

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-8 1734 POINT I/O Module/ RSLogix 5000 Controller T a g Reference Digital 4 POINT Output – With Over Load and Open Load Diagnostic Status 1734-OB4E 4 POINT 10V…28V dc Electronically Fused Output, Source Configuration Data Data T ype Defau lt Va l u e V alid Data V alues Fault Mode - POINT 0, 1, 2, ...

  • Bradley Smoker 1734-AENT - page 123

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I/O Module /RSLogix 5000 Controlle r T ag Reference C-9 Digital 4 POINT Output – With Over Load Diagnostic Status 1734-OV4E 4 POINT 10V…28V dc Electronically Fused Output, Sink Configuration Data Data T ype Default Va l u e V alid Data Values Fault Mode - POINT 0, 1, 2, 3 SINT , BIT 0 0= ...

  • Bradley Smoker 1734-AENT - page 124

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-10 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference Analog 2 Channel Input 1734-IE2C 2 Channel Analog Current Input Configuration Data Data T ype Default Va l u e V ali d Data Values Low Engineering Channel 0 INT 3,277 -32,768…32,767 High Engineering Channel 0 INT 16,383 -32,768…32,7 ...

  • Bradley Smoker 1734-AENT - page 125

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I /O Module/RSLogix 50 00 Controller T ag Referenc e C-11 1734-IE2C 2 Channel Analog Current Input Input Data Data T ype Default Va l u e V ali d Data V alues Data Channel 0 INT 0 -32,768…32,767 Data Channel 1 INT 0 -32,768…32,767 Status Byte Channel 0 SINT 0 Bit 0 Fault Bit 1 Calibratio ...

  • Bradley Smoker 1734-AENT - page 126

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-12 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference 1734-IE2V 2 Channel Analog V oltage Input Configuration Data Data T ype Defau lt Va l u e V al id Data V alues Low Engineering Channel 0 INT 0 -32,768…32,767 High Engineering Channel 0 INT 10,0 00 -32,768…32,767 Digital Filter Chann ...

  • Bradley Smoker 1734-AENT - page 127

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I /O Module/RSLogix 50 00 Controller T ag Referenc e C-13 1734-IE2V 2 Channel Analog V oltage Input Input Data Data T ype Default Va l u e V ali d Data V alues Data Channel 0 INT 0 -32,768…32,767 Data Channel 1 INT 0 -32,768…32,767 Status Byte Channel 0 SINT 0 Bit 0 Fault Bit 1 Calibrati ...

  • Bradley Smoker 1734-AENT - page 128

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-14 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference 1734-IR2 2 Channel RTD Input Configuration Data Data T ype Default Value V alid Data V alues Low Engineering Channel 0 INT 1,000 -32,768…32,767 High Engineering Channel 0 INT 5,000 -32,768…32,767 Digital Filter Channel 0 INT 0 0…1 ...

  • Bradley Smoker 1734-AENT - page 129

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I /O Module/RSLogix 50 00 Controller T ag Referenc e C-15 1734-IR2 2 Channel RTD Inpu t Configuratio n Data Data T ype Default Value V alid Data V alues Sensor T ype Channel 1 SINT 1 0=Ohms 1=100 Ω Pt α 385 2=200 Ω Pt α 385 5=100 Ω JPt α 3916 6=200 Ω JPt α 3916 9=10 Ω Cu α 427 ...

  • Bradley Smoker 1734-AENT - page 130

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-16 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference 1734-IT2 2 Channel Thermocouple Input, Isol. Configuration Data Dat a T y p e Default Va l u e V al id Data V alues Cold Junction Notch Filter SINT 1 0=50 Hz 1=60 Hz Cold Junction Mode SINT 1 0=None 1=Channel 0 2=Channel 1 3=Average Bot ...

  • Bradley Smoker 1734-AENT - page 131

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I /O Module/RSLogix 50 00 Controller T ag Referenc e C-17 1734-IT2 2 Channel Thermocouple Input, Isol. Configuration Data Data T ype Default Va l u e V ali d Data V alues T emperature Mode Channel 0 SINT 1 0=mV/Custom Scale 1=°C 2=°F 3=°K 4=°R Cold Junction Enable Channel 0 SINT 1 0=Disa ...

  • Bradley Smoker 1734-AENT - page 132

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-18 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference 1734-IT2 2 Channel Thermocouple Input, Isol. Configuration Data Dat a T y p e Default Va l u e V al id Data V alues T emperature Mode Channel 1 S INT 1 0=mV/Custom Scale 1=°C 2=°F 3=°K 4=°R Cold Junction Enable Channel 1 SINT 1 0=Di ...

  • Bradley Smoker 1734-AENT - page 133

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I /O Module/RSLogix 50 00 Controller T ag Referenc e C-19 Analog 2 Channel Output 1734-OE2C 2 Channel Analog Current Output Configuration Data Dat a T ype Defau lt Va l u e V alid Data V alues Fault V alue Channel 0 INT 0 -32,768…32,767 Program V alue Channel 0 INT 0 -32,768…32,767 Low E ...

  • Bradley Smoker 1734-AENT - page 134

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-20 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference 1734-OE2C 2 Channel Analog Current Output Configuration Data Data T ype Defa ult Va l u e V alid Data Values Idle Mode Channel 1 SINT 1 0=Hold Last State 1=Go to Low Clamp 2=Go to High Clamp 3=Go to Fault V alue Limit Alarm Latch Channe ...

  • Bradley Smoker 1734-AENT - page 135

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I /O Module/RSLogix 50 00 Controller T ag Referenc e C-21 1734-OE2V 2 Channel Analog V oltage Output Configuration Data Data T ype Default Va l u e V ali d Data V alues Fault V alue Channel 0 INT 0 -32,768…32,767 Program V alue Channel 0 INT 0 -32,768…32,767 Low Engineering Channel 0 INT ...

  • Bradley Smoker 1734-AENT - page 136

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-22 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference 1734-OE2V 2 Channel Analog V oltage Output Configuration Data Dat a T y p e Default Va l u e V al id Data V alues Limit Alarm Latch Channel 1 SINT 0 0=No Latchi ng 1=Alarms Latch Alarm Disable Channel 1 S INT 0 0=Alarms Ena bled 1=Alarm ...

  • Bradley Smoker 1734-AENT - page 137

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I /O Module/RSLogix 50 00 Controller T ag Referenc e C-23 Specialty I/O 1734-VHSC24 1 Channel 15…24V dc V ery High-speed Counter 1734-VHSC5 1 Channel 5V dc V ery High-speed Counter Configuration Data Data T ype Default Va l u e V alid Data V alues Counter Config Config_0 Config_1 Config_2 ...

  • Bradley Smoker 1734-AENT - page 138

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-24 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference 1734-VHSC24 1 Channel 15…24V dc V ery High-speed Counter 1734-VHSC5 1 Channel 5V dc V ery High-speed Counter Configuration Data Data T ype Default Va l u e V ali d Data V alues Scalar SINT 0 Counter Config 5, 6, 8 only: -128…+127 (0 ...

  • Bradley Smoker 1734-AENT - page 139

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I /O Module/RSLogix 50 00 Controller T ag Referenc e C-25 T o enter values from +128 to +255 , us e these convers io n for mulas: Desired Decimal Po sition V alue - 256 = Entere d Decimal Position V alue. As an example, for a d ivisor of 200, 200 - 256 = -56 Desired Gate In terval V alue - 2 ...

  • Bradley Smoker 1734-AENT - page 140

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-26 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference Stored Data T o interpret values from -2,147,483,648 to -1, use this conversi on formula: Stored Data T ag V alue + 4,294,967,296 = Actual Stored Data T ag Va l u e . As an example, for a read value of - 1,794,967,296: -1,794,967,2 96 + ...

  • Bradley Smoker 1734-AENT - page 141

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I /O Module/RSLogix 50 00 Controller T ag Referenc e C-27 Program Fault Programming Fault Error bit - If an incomplete, incorrect, or conflicting set of config uration paramete rs is se nt to the module, the Program Fault bit will be asserted and an error code will be placed in the Programmi ...

  • Bradley Smoker 1734-AENT - page 142

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-28 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference 1734-VHSC24 1 Channel 15…24V dc V ery High-speed Counter 1734-VHSC5 1 Channel 5V dc V ery High-speed Counter Output Data Data T ype Default Va l u e V alid Data V alues PWM V alue INT 0 0 …9500 ( 0.00 …95.00%) Counter Control Coun ...

  • Bradley Smoker 1734-AENT - page 143

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I /O Module/RSLogix 50 00 Controller T ag Referenc e C-29 1734-IJ 1 Channel 5V dc Encoder / Counter 1734-IK 1 Channel 15…24V dc Encoder / Counter Configuration Data Data T ype Default Va l u e V alid Da ta V alues Counter Config Config_0 Config_1 Config_2 Config_3 Mode_4 Mode_5 Mode_6 Z In ...

  • Bradley Smoker 1734-AENT - page 144

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-30 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference T o enter values from +128 to +2 55, use these co nv ersion for mulas: Decimal Positi on Desired Decimal Po sition V alue - 256 = Entered D ecimal Position V alue. As an example, for a divisor of 200, 200 - 256 = -56 Gate Interval Desir ...

  • Bradley Smoker 1734-AENT - page 145

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I /O Module/RSLogix 50 00 Controller T ag Referenc e C-31 Stored Data T o interpret values fr om -2,147,483 ,648 to -1, use this conver sion formula: Stored Data T ag V alue + 4,294,967,296 = Actual Stored Data T ag Va l u e . As an example, for a read val ue of -1,794,967 ,296:-1,794, 967,2 ...

  • Bradley Smoker 1734-AENT - page 146

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-32 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference Program Fault Note Programming Fault Error bit - If an i ncomplete, incorrect, or conflicting se t of configuration para meters is sent to the module, the Program Fault bit is asserted and an error cod e placed in the Programming Error ...

  • Bradley Smoker 1734-AENT - page 147

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I /O Module/RSLogix 50 00 Controller T ag Referenc e C-33 1734-SSI 1 Channel Synchronous Serial Interface Configuration Data Data T ype Defa ult Va l u e V alid Data Values Run SINT 1 0=Module Not Running 1=Module Is Running Gray Binary SINT 1 0=Binary Code 1=Gray Code Word Length SINT 13 2? ...

  • Bradley Smoker 1734-AENT - page 148

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-34 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference SSI W ord Delay Time T o enter De lay values fro m +32,768 to + 65,535 µ s, use this conv ersion formula: Desired De lay V alue (in µ s) - 6553 6 = Entered Dela y V alue (in µ s). As an example, for a 40 ms d elay time, 40000 - 65536 ...

  • Bradley Smoker 1734-AENT - page 149

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I /O Module/RSLogix 50 00 Controller T ag Referenc e C-35 Present / Latched Data T o interpret values fr om -2,147,483 ,648 to -1, use this conver sion formula: Stored Data T ag V alue + 4,294,967,296 = Actual Stored Data T ag Va l u e . As an example, for a read value of -1,7 94,967,296: -1 ...

  • Bradley Smoker 1734-AENT - page 150

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-36 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference 1734-SSI 1 Channel Synchronous Serial Interface Output Data Data T ype Default Va l u e V ali d Data V alues Control Latch Acknowledge Compare 0 Acknowledge Compare 1 Acknowledge Compare 0 Select Compare 1 Select SINT BIT 0 BIT 1 BIT 2 ...

  • Bradley Smoker 1734-AENT - page 151

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I /O Module/RSLogix 50 00 Controller T ag Referenc e C-37 1734-232ASC 1 Channel ASCII Interface Module Configuration Data Data T ype Default Va l u e V alid Data Values Serial Character Format (ASCII Format: Data Bits / Parity / Stop) SINT 0 0=7N2 1=7E1 2=7O1 3=8N1 4=8N2 5=8E1 6=8O1 7=7E2 8= ...

  • Bradley Smoker 1734-AENT - page 152

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-38 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference T ransmit Data / Receive Data / Delimiter / Pad Character Note that 7 data bits allows ASCII Character data values of 0 to 127, which RSLogix 5000 software does su pport in the sign ed Short Integer data type SINT (-128 to +127 range). ...

  • Bradley Smoker 1734-AENT - page 153

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 1734 POINT I /O Module/RSLogix 50 00 Controller T ag Referenc e C-39 1734-232ASC 1 Channel ASCII Interface Module Input Data Data T y pe Defa ult Va l u e V alid Data V alues Receive Record Number SINT 0 -128…+127 (0…255) Status TX FIFO Overflow RX FIFO Overflow RX Parity Error Handshake Error New ...

  • Bradley Smoker 1734-AENT - page 154

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 C-40 1734 POINT I/O Module/RSL ogix 5000 Controller T ag Reference T ransmit Rec or d Numbe r/ Recei ve Record Number / Length _Lo Note that 7 data bits allows T ran smit / Receive record Number of Length_Lo values of 0 to 127, w hich RSLogix 5000 software d oes support in the signed Short Intege r dat ...

  • Bradley Smoker 1734-AENT - page 155

    1 Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Appendix D Quick Start What This Appendix Contains In this quick start, you learn how to use the 1734-AENT adapter with a ControlLogix contro ller for EtherNet/IP sy stems. Necessary Prerequisites Before you begin this quick start, make sure the foll owing conditions are in place. • The ControlLogi ...

  • Bradley Smoker 1734-AENT - page 156

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 D-2 Quick Start Configure the Adapter In the 1734-AENT Modul e Properties dialog, perform the following steps. 1. Complete th e Na me field. 2. Enter the following add ress into the IP Address field: 192.168.1.42 Y ou are setting the last digit, beca use the first three digits are set for you as set by ...

  • Bradley Smoker 1734-AENT - page 157

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Quick Start D-3 Enter Adapter Properties Use this procedure to en ter adapter properties. 1. Right-click the 1734-AENT adap ter and select Properties. The Module Prope rties dialog appears. 2. Click the Chassis Size tab. Notice that the data under this ta b is dimmed while offline. Use the Chassi s Siz ...

  • Bradley Smoker 1734-AENT - page 158

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 D-4 Quick Start 4. Select the module from the list and click OK. 5. In the Module Prop erties dialog, enter the following information. a. Name b. Slot c. Comm Format d. Electronic Keying, choose Comp atible Module to verify the major revis io n C, becaus e on ly series C modules support EtherNet/IP . e ...

  • Bradley Smoker 1734-AENT - page 159

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Quick Start D-5 Configure 1734 POINT I/O Modules For RSLogix 5000 software version 13 and ea rlier , configure your 1734 POINT I/O modules vi a the Control ler T ags database, using the following ste ps. For RSLogix 5000 softw are, versions 15 or later , the preferred method for module configuration is ...

  • Bradley Smoker 1734-AENT - page 160

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 D-6 Quick Start It is set to 2, which is the default value. There are two settings that this module supports: • 2 = 0 to 10V dc • 0 = -10 to +10V dc 5. Click the value 2 and chan ge it to 0, which changes the volt age range to -10 to +10V dc for chan ne l 0. Note the following: • The controller s ...

  • Bradley Smoker 1734-AENT - page 161

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Quick Start D-7 – If you downloaded the of fline configurat ion into t he module and then realize that you must modify any of the modu le ’s configuration parameters, then the preferred way to make these changes onli ne is to go to th e Module Conne ction tab and inhibit the mod ule, apply th e cha ...

  • Bradley Smoker 1734-AENT - page 162

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 D-8 Quick Start Remember to inhib it and unhibit the module for this to take effect. Now you can put your cont roller in Run mode, and the connection should be successful. Configure an Ethernet Driver in RSLinx Software T o configure a n Ethernet driver in RSLinx software, launch RSLinx software. Launc ...

  • Bradley Smoker 1734-AENT - page 163

    Publicati on 1734-UM011 C-EN-P - Ja nuary 2006 Quick Start D-9 The Rockwell Software RSLi nx Gateway - [RSWho - 1] screen appears. TIP The RSWho screen is actu ally RSLinx’s ne twor k browser inter face, which lets you view all of your active network conn ec tions. The left pane of this disp lay is the T ree Control, which shows networks and devi ...

  • Bradley Smoker 1734-AENT - page 164

    Publication 1734 -U M011C-EN-P - Ja nuary 2006 D-10 Quick Start Add the AB_ETHIP-1 (EtherNet/IP) Driver 1. From the Communic ations menu, choose Con figure Drive rs. The Configure Drivers dialog appears. 2. From the Available Driver Types pull-down menu , choose EtherNet/IP Driv er . 3. Click the Add New butto n . 4. Click OK to accept the default ...

  • Bradley Smoker 1734-AENT - page 165

    Publication 1734-UM0 11C-EN-P - Januar y 2006 Index Numerics 1734-POINT I/O catalog numbers C-1 A AB_ETH driver B-1 AB-ETHIP driver B-1 access module data 5-21 adapter features 1-4 replacing on system 2-3 wiring 2-4 auto negotiate 3-2 autobaud 1-8 B bandwidth, insufficient 4-24 BootP/DHCP utility 3-8 browse chas sis page A-15 C catalog numbers C-1 ...

  • Bradley Smoker 1734-AENT - page 166

    Publicatio n 17 34 -U M011C-EN-P - Ja nu ary 2006 2 Index mounting dimensions 2-5 mounting modules on DIN rail before modules installed 2-2 N network address 2-3, 3-7 O overloaded a dapter 4-24 P power up system for the first time 1-4 producer/consu mer model understanding 1-6 program fault note C-27, C-32 publications related P-4 Q quick start D-1 ...

  • Bradley Smoker 1734-AENT - page 167

    Publication CIG-CO52 1C- EN-P- May 2003 PN957782-91 How Are W e Doing? Y our comments on our technical publications will help us serve you better in the future. Thank you for taking the time to provide us feedback. Y ou can complete this form and mail (or fax) it back to us or email us at RADocumentComments@ra.rockwell.com Please complete the s ect ...

  • Bradley Smoker 1734-AENT - page 168

    Other Comments PLEASE FOLD HERE NO POST AGE NECESSARY IF MAILED IN THE UNITED ST A TES BUSINESS REPL Y MAIL FIRST -CLASS MAIL PERMIT NO. 18235 CLEVELAND OH POST AGE WILL BE P AID BY THE ADDRESSEE PLEASE FASTEN HERE (DO NOT ST APLE) PLEASE RE MOVE ...

  • Bradley Smoker 1734-AENT - page 169

    ...

  • Bradley Smoker 1734-AENT - page 170

    Publication 1734 -UM011C-EN-P - Ja nuary 2006 1 PN 957988-75 Supersedes Publ ication 1734-UM011B-E N-P -August 200 5 Copyright © 200 6 Rockwell Automat ion, Inc. All rights reserved. Printed i n the U.S.A. Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using its products. At http://suppor ...

Manufacturer Bradley Smoker Category Network Card

Documents that we receive from a manufacturer of a Bradley Smoker 1734-AENT can be divided into several groups. They are, among others:
- Bradley Smoker technical drawings
- 1734-AENT manuals
- Bradley Smoker product data sheets
- information booklets
- or energy labels Bradley Smoker 1734-AENT
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bradley Smoker 1734-AENT.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bradley Smoker 1734-AENT, service manual, brief instructions and user manuals Bradley Smoker 1734-AENT. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bradley Smoker 1734-AENT.

A complete manual for the device Bradley Smoker 1734-AENT, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bradley Smoker 1734-AENT by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bradley Smoker 1734-AENT.

A complete Bradley Smoker manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bradley Smoker 1734-AENT - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bradley Smoker 1734-AENT, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bradley Smoker 1734-AENT, that we can find in the current document
3. Tips how to use the basic functions of the device Bradley Smoker 1734-AENT - which should help us in our first steps of using Bradley Smoker 1734-AENT
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bradley Smoker 1734-AENT
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bradley Smoker 1734-AENT in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bradley Smoker 1734-AENT?

Use the form below

If you did not solve your problem by using a manual Bradley Smoker 1734-AENT, ask a question using the form below. If a user had a similar problem with Bradley Smoker 1734-AENT it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)