Manual York YHJD18 thru 60

44 pages 0.66 mb
Download

Go to site of 44

Summary
  • York YHJD18 thru 60 - page 1

    TECHNICAL GUIDE LX SERIES SPLIT-SYSTEM HEAT PUMPS 13 SEER – R-410A – 1 PHASE 1.5 THRU 5 NOMINAL TONS MODELS: YHJD18 THRU 60 Due to continuou s pro duc t impro vement, speci fic a tio ns are subject to chan ge without notice. Visit us on the web at www .upgnet.com an d www.york.com Additional rating informa tion can be found at www.ahridirectory ...

  • York YHJD18 thru 60 - page 2

    571209-YTG-C-1012 2 Johnson Controls Unitary Products * Adapter fi tting required for 1-1/8" lin e set. All dimensions are in inches an d are subject to change without notice. Overall height is from bottom of base pan to top of fan guar d. Overall length and widt h includ e screw heads. Physical and Electrica l Data MODEL YHJD18 S41S2 YHJD24 S ...

  • York YHJD18 thru 60 - page 3

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 3 PROCEDURES: 1. Unit factory charge listed on the unit nameplat e includes refrigerant f or th e outdoor unit, the smallest matched indoor unit, and 15 fe et of interconnecting line tubin g. 2. V erify the TXV or orifice and addit ional charge required for s pecific matched ind oor unit in the ...

  • York YHJD18 thru 60 - page 4

    571209-YTG-C-1012 4 Johnson Controls Unitary Products COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL WIDTH RA TED CFM NET MBH SEER EER TOT AL SENS. 13 SEER HP WITH AIR HANDLERS YHJD18S41S2 AHE18B 17.5 – 610 18.0 14.6 14.00 12.00 AHR18B 17.5 – 665 18.0 14 .9 13.00 11 . 0 0 AHV18B 17.5 – 615 18.0 1 ...

  • York YHJD18 thru 60 - page 5

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 5 — = Not applicable. MA Modular Air Handlers use Coil Only Ratings. YHJD42S41S4 AHE48D 24.5 – 1385 40.5 33.2 14.00 12.00 AHR48D 24.5 – 1320 39.5 29.6 13.00 11 . 0 0 AHV48D 24.5 – 1300 39.5 30.2 13.75 11 . 5 0 AV * 4 8 24.5 – 1385 42.0 32.6 14.50 12.00 AV * 6 0 24.5 – 1360 42.0 32.6 ...

  • York YHJD18 thru 60 - page 6

    571209-YTG-C-1012 6 Johnson Controls Unitary Products MA Modular Air Handlers use Coil Only Ratings. PSC furnaces, such as the TG8S, TGLS, and TG9S, use Coil Only Rating s. COOLING CAP ACITY - Up flow , Downflow & Horizo ntal Furnaces and Coils (Coil Only Ratings) UNIT MODEL COIL CFM RANGE (Min.-max.) COOLING MODEL WIDTH RA TED CFM NET MBH SEER ...

  • York YHJD18 thru 60 - page 7

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 7 YHJD18S41S2 T*(8,L)X*A12 14.5 UC24B 570 18.0 14.1 14.50 12.00 T*(8,L)X*A12 14.5 UC30B 570 18.0 14.1 14.50 12.00 T*(8,L)X*B12 17.5 FC/MC/PC18B 580 18.0 14.6 14.00 12.00 T*(8,L)X*B12 17.5 FC/MC/PC24B 620 18.0 14.9 14.00 12.00 T*(8,L)X*B12 17.5 FC/MC/PC30B 620 18.0 14.9 14.00 12.00 T*(8,L)X*B12 1 ...

  • York YHJD18 thru 60 - page 8

    571209-YTG-C-1012 8 Johnson Controls Unitary Products YHJD24S41S4 T*(8,L)V*A12 14.5 FC/MC/PC32A 775 24.0 17.2 14.00 12.00 T*(8,L)V*A12 14.5 FC /MC/PC37A 805 24.0 17 .3 14.50 12.00 T*(8,L)V*B12 17.5 FC /MC/PC35B 760 24.0 17 .2 14.00 12.00 T*(8,L)V*B12 17.5 FC /MC/PC43B 760 24.0 17 .2 14.00 12.00 T*(8,L)V*C16 21.0 FC/MC/PC35C 855 24.0 17.6 14.50 12.0 ...

  • York YHJD18 thru 60 - page 9

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 9 YHJD30S41S4 T*(8,L)V*A12 14.5 FC/MC/PC32A 1045 30.0 22.0 13.50 1 1.00 T*(8,L)V*A12 14.5 FC/MC/PC37A 950 30.0 22.0 14.50 12.00 T*(8,L)V*B12 17.5 FC/MC/PC35B 995 30.0 22.0 14.50 12.00 T*(8,L)V*B12 17.5 FC/MC/PC43B 1040 30.0 22.8 14.50 12.00 T*(8,L)V*C 16 21.0 FC/MC/PC35C 1025 30.0 22.0 14.50 12. ...

  • York YHJD18 thru 60 - page 10

    571209-YTG-C-1012 10 Johnson Controls Unitary Products YHJD36S41S4 T*(8,L)V*C20 21.0 FC/MC/PC48C 1 155 36.0 26.6 14.50 12.00 T*(8,L)V*C20 21.0 UC48C 1 155 36.0 26.8 14.50 12.00 T*(8,L)X*A12 14.5 FC /MC/PC37A 1290 36.0 27 .6 14.50 12.00 T*(8,L)X*B12 17.5 FC /MC/PC43B 1300 36.0 27 .6 14.50 12.00 T*(8,L)X*C16 21.0 FC/MC/PC43C 1 175 36.0 26.8 14.50 12. ...

  • York YHJD18 thru 60 - page 11

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 11 YHJD42S41S4 T*(8,L)V*C16 21.0 FC/PC60C 1420 41.5 32.2 14.00 12.00 T*(8,L)V*C 16 21.0 UC60C 1420 41.0 31.4 13.75 11 . 5 0 T*(8,L)V*C 20 21.0 FC/PC60C 1410 42.0 32.4 14.00 12.00 T*(8,L)V*C 20 21.0 UC60C 1410 41.0 31.4 14.00 12.00 T*(8,L)X*C 16 21.0 FC/PC60C 1360 42.0 32.6 14.50 12.00 T*(8,L)X*C ...

  • York YHJD18 thru 60 - page 12

    571209-YTG-C-1012 12 Johnson Controls Unitary Products PSC furnaces, such as the TG8S, TGLS, and TG9S, use Coil Only Rating s. YHJD48S41S4 T*9(C,V)*D20 24.5 FC/MC/PC60D 1615 44.5 33 .6 14.00 12.00 T*9(C,V)*D20 24.5 FC/MC62D 1630 45.0 34.0 14.00 12.00 T*9(C,V)*D20 24.5 UC60D 1615 44.0 33.0 14.00 12.00 T*9X*C16 21.0 FC/MC62D 1550 45.0 34.2 14.50 12.0 ...

  • York YHJD18 thru 60 - page 13

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 13 HEA TING CAP ACITY - With Air Handler UNIT MODEL AIR HANDLER COIL 1 MODEL HEA TING 2 47  F 17  F HSPF MBH COP KW MBH COP KW STD 13 SEER HP WITH AIR HANDLERS YHJD18S41S2 AHE18B – 18.0 3.70 1.43 1 1.1 2.28 1.43 7.70 AHR18B – 18.0 3.54 1.49 11 . 4 2.22 1.50 7.70 AHV18B – 18.0 3.50 1. ...

  • York YHJD18 thru 60 - page 14

    571209-YTG-C-1012 14 Johnson Controls Unitary Products COP equals MBH output divided by (tot al KW input x 3.412). HSPF (Heating Seasonal P erformance Fact or) is the tot al heati ng outpu t during a normal a nnual usage perio d for heating d ivided by the tot al electric power input during the same period. MA Modular Air Handlers use Coil Only Rat ...

  • York YHJD18 thru 60 - page 15

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 15 COP equals MBH output divided by (tot al KW input x 3.412). HSPF (Heating Seasonal Per formance Factor) i s the tot al heati ng o utput during a normal annual u sage period for heating divide d by the tot al electric power input during the same period. MA Modular Air Handlers use Coil Only Ra ...

  • York YHJD18 thru 60 - page 16

    571209-YTG-C-1012 16 Johnson Controls Unitary Products HEA TING CAP ACITY - With High Efficiency Motor Furnaces MODEL FURNACE MODEL COIL 1 MODEL HEA TING 2 47  F 17  FH S P F MBH COP KW MBH COP KW STD 13 SEER HP WITH HIGH EFFICIENCY MOTOR FURNACES 3 YHJD18S41S2 T*(8,L)V*A12 FC/MC/PC18A 18.0 3.5 8 1.37 7.7 2.28 0 .99 8.00 T*(8,L)V*A12 FC /MC/P ...

  • York YHJD18 thru 60 - page 17

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 17 YHJD18S41S2 Y*(8,L)C*B12 UC24B 18.0 3.70 1.34 10.5 2.96 1.04 8.20 Y*(8,L)C*B12 UC30B 18.0 3.70 1.34 10.4 2.96 1.03 8.20 Y*9C*B12 FC/MC/PC18B 18.0 3.60 1.36 7.7 2.30 0.98 8.00 Y*9C*B12 FC/MC/PC24B 18.0 3.74 1.34 10.5 2.94 1.05 8.30 Y*9C*B12 FC/MC/PC30B 18.0 3.74 1.34 10.5 2.94 1.05 8.30 Y*9C*B ...

  • York YHJD18 thru 60 - page 18

    571209-YTG-C-1012 18 Johnson Controls Unitary Products YHJD30S41S4 T * ( 8 , L ) V * A 1 2 F C / M C / P C 3 2 A 2 7 . 43 . 3 02 . 4 31 6 . 02 . 3 22 . 0 27 . 8 5 T*(8,L)V*A12 FC /MC/PC37A 27.2 3.48 2.29 15.7 2.42 1.90 8.05 T*(8,L)V*B12 FC /MC/PC35B 27.0 3.42 2.31 15.6 2.42 1.89 7.95 T*(8,L)V*B12 FC /MC/PC43B 27.6 3.52 2.30 15.7 2.42 1.90 8.15 T*(8 ...

  • York YHJD18 thru 60 - page 19

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 19 YHJD36S41S4 T*(8,L)X*C20 FC/MC/PC43C 34.0 3.66 2.72 21.4 2.80 2.24 8.20 T*(8,L)X*C 20 FC/MC/PC48C 34.2 3.70 2.71 21.6 2.84 2.23 8.20 T*(8,L)X*C 20 UC48C 34.6 3.80 2.67 21.8 2.84 2.25 8.20 T*9(C,V)*B12 FC/MC/PC43B 34.2 3.48 2.88 22.0 2.66 2.42 8.20 T*9(C,V)*C16 FC/MC/PC43C 34.0 3.52 2.83 22.0 ...

  • York YHJD18 thru 60 - page 20

    571209-YTG-C-1012 20 Johnson Controls Unitary Products YHJD42S41S4 T * 9 X * C 2 0 F C / P C 6 0 C 4 0 . 03 . 9 82 . 9 42 2 . 42 . 6 82 . 4 58 . 2 0 T*9X*C20 UC60C 39.5 3.90 2.97 22.2 2.64 2.46 8.20 T*9X*D20 FC/MC/PC60D 40.0 4.04 2.90 22.4 2.72 2.41 8.20 T*9X*D20 UC60D 39.5 4.00 2.89 22.4 2.70 2.43 8.20 Y*(8,L)C*C16 FC/PC60C 40.0 3.88 3.02 22.4 2. ...

  • York YHJD18 thru 60 - page 21

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 21 COP equals MBH output divided by (tot al KW input x 3.412). HSPF (Heating Seasonal Per formance Factor) i s the tot al heati ng o utput during a normal annual u sage period for heating divide d by the tot al electric power input during the same period. PSC furnaces, such as the TG8S, TG LS, a ...

  • York YHJD18 thru 60 - page 22

    571209-YTG-C-1012 22 Johnson Controls Unitary Products ACCESSORIES Refer to Price Manual for specific model numbers. St art Assist Kit (S1 -2SA067*) - May be required on 24, 30, 36, & 42 models when a T XV is installed. May also be required o n 18 & 60 models in low voltage application. The 48 mod el has factory installed st art assis t. Se ...

  • York YHJD18 thru 60 - page 23

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 23 TYPICAL INST ALLA TION TYPICAL FIELD WIRING 60” OVERHEAD CLEARANCE MINIMUM 18” SERVICE ACCESS CLEARANCE ON ONE SIDE WEA THERPROOF DISCONNECT SWITCH THERMOST A T 10” CLEARANCE AROUND PERIMETER CONTROL ACCESS P ANEL TO INDOOR COIL NEC CLASS 1 WIRING NEC CLASS 2 WIRING TO FURNACE OR AIR HA ...

  • York YHJD18 thru 60 - page 24

    571209-YTG-C-1012 24 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73- 87 °F), sensible capacity increa ses by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM ...

  • York YHJD18 thru 60 - page 25

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 25 Furnaces Coils T .C. S.C. KW T*(8,L)V*A12 FC/MC/PC18A 0.99 0.98 0.93 T*(8,L)V*A12 FC/MC/PC24A 1.02 1.06 0.93 T*(8,L)V*A12 FC/MC/PC30A 1.02 1.06 0.93 T*(8,L)V*A12 UC18A 0.99 0.99 0.93 T*(8,L)V*A12 UC24A 1.02 1.05 0.93 T*(8,L)V*A12 UC30A 1.02 1.05 0.93 T*(8,L)V*B12 FC/MC/PC18B 0.99 0.98 0.92 T* ...

  • York YHJD18 thru 60 - page 26

    571209-YTG-C-1012 26 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73- 87 °F), sensible capacity increa ses by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM ...

  • York YHJD18 thru 60 - page 27

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 27 Furnaces Coils T .C. S.C. KW T*(8,L)V*A12 FC/MC/PC32A 1.02 0.99 0.94 T*(8,L)V*A12 FC/MC/PC37A 1.06 1.04 0.94 T*(8,L)V*B12 FC/MC/PC35B 1.05 1.02 0.94 T*(8,L)V*B12 FC/MC/PC43B 1.06 1.04 0.94 T*(8,L)V*C16 FC/MC/PC35C 1.05 1.03 0.93 T*(8,L)V*C16 FC/MC/PC43C 1.07 1.04 0.93 T*(8,L)V*C20 FC/MC/PC35C ...

  • York YHJD18 thru 60 - page 28

    571209-YTG-C-1012 28 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73- 87 °F), sensible capacity increa ses by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM ...

  • York YHJD18 thru 60 - page 29

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 29 Furnaces Coils T .C. S.C KW T*(8,L)V*A12 FC/MC/PC32A 1.01 1.05 0.99 T*(8,L)V*A12 FC/MC/PC37A 1.02 1.06 0.95 T*(8,L)V*B12 FC/MC/PC35B 1.02 1.06 0.95 T*(8,L)V*B12 FC/MC/PC43B 1.04 1.09 0.96 T*(8,L)V*C16 FC/MC/PC35C 1.02 1.07 0.93 T*(8,L)V*C16 FC/MC/PC43C 1.04 1.09 0.93 T*(8,L)V*C20 FC/MC/PC35C ...

  • York YHJD18 thru 60 - page 30

    571209-YTG-C-1012 30 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73- 87 °F), sensible capacity increa ses by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM ...

  • York YHJD18 thru 60 - page 31

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 31 Furnaces Coils T .C. S.C. KW T*(8,L)V*A12 FC/MC/PC37A 1.03 1.03 1.00 T*(8,L)V*B12 FC/MC/PC43B 1.04 1.06 1.01 T*(8,L)V*C16 FC/MC/PC43C 1.04 1.04 0.96 T*(8,L)V*C16 FC/MC/PC48C 1.05 1.05 0.96 T*(8,L)V*C16 UC48C 1.05 1.05 0.96 T*(8,L)V*C20 FC/MC/PC43C 1.04 1.04 0.96 T*(8,L)V*C20 FC/MC/PC48C 1.05 ...

  • York YHJD18 thru 60 - page 32

    571209-YTG-C-1012 32 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73- 87 °F), sensible capacity increa ses by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM ...

  • York YHJD18 thru 60 - page 33

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 33 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7 3-87 °F), sensible capacity increases by 10 60 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM p ...

  • York YHJD18 thru 60 - page 34

    571209-YTG-C-1012 34 Johnson Controls Unitary Products Furnaces Coils T .C. S.C. KW T*(8,L)V*C16 FC/MC62D 0.99 0.99 0.95 T*(8,L)V*C16 FC/PC60C 0.98 0.98 0.96 T*(8,L)V*C16 UC60C 0.98 0.95 0.96 T*(8,L)V*C20 FC/MC62D 1.00 0.99 0.95 T*(8,L)V*C20 FC/PC60C 0.99 0.98 0.96 T*(8,L)V*C20 UC60C 0.98 0.96 0.94 T*(8,L)X*C16 FC/MC62D 1.00 0.99 0.95 T*(8,L)X*C16 ...

  • York YHJD18 thru 60 - page 35

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 35 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7 3-87 °F), sensible capacity increases by 10 60 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM p ...

  • York YHJD18 thru 60 - page 36

    571209-YTG-C-1012 36 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. Continu ed on next p age. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD18S41S2 EV APORA TOR COIL MODEL NO FC35 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 450 600 750 MBH COP KW MB ...

  • York YHJD18 thru 60 - page 37

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 37 Furnaces Coils MBH COP KW T*(8,L)V*A12 FC/MC/PC18A 1.03 0.99 1.04 T*(8,L)V*A12 FC/MC/PC24A 1.04 1.06 0.98 T*(8,L)V*A12 FC/MC/PC30A 1.04 1.06 0.98 T*(8,L)V*A12 UC18A 1.04 1.02 1.02 T*(8,L)V*A12 UC24A 1.04 1.06 0.98 T*(8,L)V*A12 UC30A 1.04 1.06 0.98 T*(8,L)V*B12 FC/MC/PC18B 1.03 0.99 1.04 T*(8, ...

  • York YHJD18 thru 60 - page 38

    571209-YTG-C-1012 38 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD24S41S4 EV APORA TOR COIL MODEL NO AHP30 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 600 800 1000 MBH COP KW MBH COP KW MBH COP KW 60 6 ...

  • York YHJD18 thru 60 - page 39

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 39 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD30S41S4 EV APORA TOR COIL MODEL NO AHP30 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 800 1000 1200 MBH COP KW MBH COP KW MBH COP KW 60 ...

  • York YHJD18 thru 60 - page 40

    571209-YTG-C-1012 40 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. Continu ed on next p age. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD36S41S4 EV APORA TOR COIL MODEL NO AHP36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1000 1200 1400 MBH COP K ...

  • York YHJD18 thru 60 - page 41

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 41 Furnaces Coils MBH COP KW T*(8,L)V*A12 FC/MC/PC37A 0.93 0.98 0.95 T*(8,L)V*B12 FC/MC/PC43B 0.93 0.98 0.95 T*(8,L)V*C16 FC/MC/PC43C 0.92 1.01 0.91 T*(8,L)V*C16 FC/MC/PC48C 0.91 1.02 0.90 T*(8,L)V*C16 UC48C 0.93 1.05 0.89 T*(8,L)V*C20 FC/MC/PC43C 0.92 1.01 0.91 T*(8,L)V*C20 FC/MC/PC48C 0.91 1.0 ...

  • York YHJD18 thru 60 - page 42

    571209-YTG-C-1012 42 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD42S41S4 EV APORA TOR COIL MODEL NO AHP48 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1200 1400 1600 MBH COP KW MBH COP KW MBH COP KW 60 ...

  • York YHJD18 thru 60 - page 43

    571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 43 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD48S41S4 EV APORA TOR COIL MODEL NO AHP48 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1400 1600 1800 MBH COP KW MBH COP KW MBH COP KW 60 ...

  • York YHJD18 thru 60 - page 44

    Subject to change without notice. Published in U .S.A. 571209-YTG-C-1012 Copyright © 2012 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 571209-YTG-B-1211 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSIN ...

Manufacturer York Category Heat Pump

Documents that we receive from a manufacturer of a York YHJD18 thru 60 can be divided into several groups. They are, among others:
- York technical drawings
- YHJD18 thru 60 manuals
- York product data sheets
- information booklets
- or energy labels York YHJD18 thru 60
All of them are important, but the most important information from the point of view of use of the device are in the user manual York YHJD18 thru 60.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals York YHJD18 thru 60, service manual, brief instructions and user manuals York YHJD18 thru 60. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product York YHJD18 thru 60.

Similar manuals

A complete manual for the device York YHJD18 thru 60, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use York YHJD18 thru 60 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of York YHJD18 thru 60.

A complete York manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual York YHJD18 thru 60 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the York YHJD18 thru 60, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the York YHJD18 thru 60, that we can find in the current document
3. Tips how to use the basic functions of the device York YHJD18 thru 60 - which should help us in our first steps of using York YHJD18 thru 60
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with York YHJD18 thru 60
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of York YHJD18 thru 60 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning York YHJD18 thru 60?

Use the form below

If you did not solve your problem by using a manual York YHJD18 thru 60, ask a question using the form below. If a user had a similar problem with York YHJD18 thru 60 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)