    www .rosemount.com Reference Manual 00809-0100-4021, Rev DA November 2004 This product is a core component of the PlantWe b digital plant architecture. Rosemount 3144P T emperature T ransmitter ...

  • Emerson Process Management 3144P - page 2

    ...

  • Emerson Process Management 3144P - page 3

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P www .rosemount.com Rosemount 3144P T emperature T ransmitter Rosemount 3144P T emperature T ransmitter may be protected by one or more U.S. Patents Pending. Other foreign patent s pending. NOTICE Read this manual before working with the product. For personal and system safety , ...

  • Emerson Process Management 3144P - page 4

    ...

  • Emerson Process Management 3144P - page 5

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P www .rosemount.com T able of Content s SECTION 1 Introduction Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Transmi ...

  • Emerson Process Management 3144P - page 6

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P TOC -2 SECTION 3 HART Commissioning Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 375 Field Communicator . . . . . . ...

  • Emerson Process Management 3144P - page 7

    Reference Manual 00809-0100-4021, Rev DA November 2004 TOC -3 Rosemount 3144P Analog Input (AI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14 Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14 Configure the AI block . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 3144P - page 8

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P TOC -4 APPENDIX A Reference Data HART and Foundation Fieldbus Specificatio ns . . . . . . . . . . . . . . . . . . A-1 Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1 Physical Specifications . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 3144P - page 9

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P www .rosemount.com Section 1 Introduction Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1- 1 Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 1-2 Return of Materials . . . . . . . . . . . . . . ...

  • Emerson Process Management 3144P - page 10

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 1-2 Appendix A: S pecifications and Reference Data • S pecifications • Dimensional drawings • Ordering Information Appendix B: Approvals • Product Certifications • Installation Drawings Safety Instrumented Syst em (SIS) – HART only • Information regarding Safety Ce ...

  • Emerson Process Management 3144P - page 11

    Reference Manual 00809-0100-4021, Rev DA November 2004 1-3 Rosemount 3144P Environment al T emperature Effects The transmitter will operate within spec ifications for ambient temperatures between –40 and 185 °F (– 40 and 85 °C). Heat from the process is transferred from the thermowell to th e transmitter housing. If the expected process tempe ...

  • Emerson Process Management 3144P - page 12

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 1-4 NOTE Each transmitter is marked with a tag indicating the approvals. Install the transmitter in accordance with all applicable installation codes and approval and installation drawings (see Appendix B: Product Certifications). V erify that the operating atmosphere of the tra ...

  • Emerson Process Management 3144P - page 13

    Reference Manual 00809-0100-4021, Rev DA November 2004 1-5 Rosemount 3144P RETURN OF MATERIALS T o expedite the return process in North America, call the Emerson Process Management National Response Center (800-654-7768). This center , will assist you with any needed information or materials. The center will ask for the following information: • P ...

  • Emerson Process Management 3144P - page 14

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 1-6 ROSEMOUNT 3144P AND ROSEMOUNT 3144 / 3244MV DIFFERENCES The following table identifies the di f ferences between th e Rosemount 3144P and Rosemount 3144 and 3244MV T emperature Transmitters. Improved Rosemount 3144P Previous Rosemount 3144 and 3244MV Field Device Revision nu ...

  • Emerson Process Management 3144P - page 15

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P www .rosemount.com Section 2 Inst allation Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-2 Mounting . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 3144P - page 16

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 2-2 COMMISSIONING The 3144P must be configur ed for certain basic variables to operate. In many cases, all of these variables are pre-c onfigured at the factory . Configuration may be required if the configurat ion variables need to be changed. Commissioning consists of testing ...

  • Emerson Process Management 3144P - page 17

    Reference Manual 00809-0100-4021, Rev DA November 2004 2-3 Rosemount 3144P Set the Switches HART Without a LCD display 1. If the transmitter is installed in a loop, set the loop to manual mode and disconnect power . 2. Remove the housing cover on the el ectronics side of the transmitter . Do not remove the transmitter cover in explosive atmospheres ...

  • Emerson Process Management 3144P - page 18

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 2-4 T able 2-1. Transmitter Switch Locations. Write Protect Switch (HART and F OUNDATION Fiel dbus) The transmitter is equipped with a writ e-protect switch that can be positioned to prevent the accidental or deliberate change of configuration dat a. Alarm Switch (HART) The tran ...

  • Emerson Process Management 3144P - page 19

    Reference Manual 00809-0100-4021, Rev DA November 2004 2-5 Rosemount 3144P Figure 2-2. Incorrect Conduit Installation Figure 2-3. Recommended Mounting with Drain Seal If mounting the transmitter directly to the sensor assembly , use the process shown in Figure 2-4. If mounting the transmitter apart from the sensor assembly , use conduit between the ...

  • Emerson Process Management 3144P - page 20

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 2-6 INST ALLATION T ypical North American Inst allation 1. Attach the thermowell to the pipe or process cont ainer wall. Install and tighten thermowells and sensors. Apply process pressure to perform a leak test. 2. Attach necessary unions, couplings, and extension fittings. Sea ...

  • Emerson Process Management 3144P - page 21

    Reference Manual 00809-0100-4021, Rev DA November 2004 2-7 Rosemount 3144P T ypical European Inst allation 1. Mount the thermowell to the pipe or the process container wall. Inst all and tighten thermowells and sensors. Apply pressure and perform a leak check before starting the process. 2. Attach a connection head to the thermowell. 3. Insert the ...

  • Emerson Process Management 3144P - page 22

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 2-8 In Conjunction with a Rosemount 333 HART T ri-Loop (HART / 4–20 mA only) Use the dual-sensor option 3144P transmitter that is operating with two sensors in conjunction with a 333 HART T ri-Loop ® HART -to-Analog Signal Converter to acquire an independent 4– 20 mA analog ...

  • Emerson Process Management 3144P - page 23

    Reference Manual 00809-0100-4021, Rev DA November 2004 2-9 Rosemount 3144P LCD Display T ransmitters ordered with the LCD disp lay option (code M5) are shipped with the LCD display installed. Af ter-market installation of the LCD display on a conventional 3144P transmitter requires a small instrument screwdriver and the LCD display kit, which inclu ...

  • Emerson Process Management 3144P - page 24

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 2-10 Multichannel Inst allation (HART / 4–20 mA only) Y ou can connect several transmitters to a single master power supply (see Figure 2-7). In this case, the system may be grounded only at the negative power supply terminal. In multichann el installations where several trans ...

  • Emerson Process Management 3144P - page 25

    Reference Manual 00809-0100-4021, Rev DA November 2004 2-1 1 Rosemount 3144P Figure 2-8. T ransmitter T erminal Block Figure 2-9. HART / 4–20 mA Wiring Diagram “+” Sensor T erminals (1 – 5) Te s t Ground 3144P Single-Sensor Connections Diagram 3144P Dual-Sensor Connections Diagram * T ransmitter must be configured fo r a 3-wire RTD in order ...

  • Emerson Process Management 3144P - page 26

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 2-12 Power/Current Loop Connections Use copper wire of a sufficient size to ensure that the volt age across the transmitter power terminals does not go below 12.0 V dc. 1. Connect the current signal leads as shown in Figure 2-10. 2. Recheck the polarity and correctness of connec ...

  • Emerson Process Management 3144P - page 27

    Reference Manual 00809-0100-4021, Rev DA November 2004 2-13 Rosemount 3144P F OUNDATION Fieldbus Figure 2-1 1. Transmitter T erminal Block Figure 2-12. F OUNDATION Fieldbus Field Wiring Diagram Sensor T erminals (1 – 5) Ground Power T erminals 3144P Single-Sensor Connections Diagram 3144P Dual-Sensor Connections Diagram * T ransmitter must be con ...

  • Emerson Process Management 3144P - page 28

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 2-14 Sensor Connections Figure 2-9 on page 2-1 1 (HART) and Figure 2-12 on page 2-13 (F OUNDATION fieldbus) shows the correct sensor wiring connections to the transmitter sensor terminals. T o ensure an adequate sensor connection, anchor the sensor lead wires beneath the flat wa ...

  • Emerson Process Management 3144P - page 29

    Reference Manual 00809-0100-4021, Rev DA November 2004 2-15 Rosemount 3144P NOTE Do not allow the voltage to drop below 12.0 V dc at the transmitter terminals when changing transmitter configurati on parameters, or permanent damage to the transmitter could result. Figure 2-13. Load Limits. F OUNDATION fieldbus Powered over F OUNDATION fieldbus with ...

  • Emerson Process Management 3144P - page 30

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 2-16 Shielding Reco mmendations The following are recommended prac tices are from API S tandard 552 (T ransmission S tandard) section 20.7 and fr om field and laboratory testing. If more than one recommendation is given fo r a sensor type, start with the first technique shown or ...

  • Emerson Process Management 3144P - page 31

    Reference Manual 00809-0100-4021, Rev DA November 2004 2-17 Rosemount 3144P Option 3 1. Ground the sensor wiring shield at the sensor , if possible. 2. Ensure the sensor wiring and signal wiring shields are electrically isolated form the transmitter housi ng and other fixtures that may be grounded. 3. Ground the signal wiring shie ld at the power s ...

  • Emerson Process Management 3144P - page 32

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 2-18 ...

  • Emerson Process Management 3144P - page 33

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P www .rosemount.com HART Section 3 HART Commissioning Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 375 Field Communicator . . . . . . . . ...

  • Emerson Process Management 3144P - page 34

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-2 HART 375 FIELD COMMUNICATOR The Menu T ree and Fast Key sequences use the following device revisions: • S tandard 3144P: Device Revision Dev v3, DD v2 • 3144P SIS: Device Revision Dev v2, D D v1 The 375 Field Communicator exchanges in formation with the transmitter from ...

  • Emerson Process Management 3144P - page 35

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-3 Rosemount 3144P HART Menu T ree Figure 3-1 displays a complete 3144P menu tree for use with the 375 Field Communicator . Options listed in bold type indicate that a selection provides other options. For 3144P SIS Safety Certified transmitter , see “3144P SIS Safety Certified Menu T ree” ...

  • Emerson Process Management 3144P - page 36

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-4 HART Fast Key Sequences Fast key sequences are listed below for common 3144P transmitter functions. NOTE: The fast key sequences assume that “Device Revision Dev v3, DD v2 is being used. T able 3-1 provides alphabetical function lists for all Field Communicator tasks as we ...

  • Emerson Process Management 3144P - page 37

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-5 Rosemount 3144P HART AMS One of the key benefits of intelli gent devices is the ease of device configuration. When used with AMS, the 3144P is easy to configure and provides instant and accurate alert s and alarms. The main configuration screen of the 3144P is the “Configurat ion Properti ...

  • Emerson Process Management 3144P - page 38

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-6 HART CHECK OUTPUT Before performing other transmitte r online operations, review the configuration of the 3144P digital outp ut parameters to ensure that the transmitter is operating properly . Process V ariables The 3144P process variables provide the transmitter output. Th ...

  • Emerson Process Management 3144P - page 39

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-7 Rosemount 3144P HART Change T ype and Connections The Connections command allows the user to se lect the sensor type and the number of sensor wires to be connecte d. Select from the following sensor types: • 2-, 3-, or 4-wire Pt 100, Pt 200, Pt 500, Pt 1000 platinum RTDs ( α = 0.00385 ? ...

  • Emerson Process Management 3144P - page 40

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-8 HART Sensor 1 Serial Number The Sensor 1 S/N variable provides a location to list the serial number of the attached sensor . It is useful for identifying sensors and tracking sensor calibration information. AMS Right click on the device and select “Configuration Properties ...

  • Emerson Process Management 3144P - page 41

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-9 Rosemount 3144P HART Te r m i n a l Te m p e r a t u r e The Te r m i n a l Te m p command sets the terminal temperature unit s to indicate the temperature at the transmitter terminals. AMS Right click on the device and select “Configuration Properties” from the menu. Select the Electro ...

  • Emerson Process Management 3144P - page 42

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-10 HART 4. Select OK after verifying the variable settings from the variable mapping menu. 5. Select OK to return the control loop to automatic control. 6. Select HOME to return to the Online menu. 7. Select 1 Device Setup, 3 Configuration, 3 Dual-sensor configuration, 1 Diffe ...

  • Emerson Process Management 3144P - page 43

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-1 1 Rosemount 3144P HART NOTE If Sensor 1 and/or Sensor 2 should fa il while PV is configured for average temperature and Hot Backup is not enabled, the transmitter will go into alarm. For this reason, when PV is Sensor Average it is recommended that Hot Backup be enabled when dual-element se ...

  • Emerson Process Management 3144P - page 44

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-12 HART Apply changes made (see “Appl y AMS Changes” on page 3-5). Hot Backup Configuration The Config Hot BU command configures the transmitter to automatically use Sensor 2 as the primary sensor if Sensor 1 fails. With Hot Backup enabled, the primary variable (PV) mu st ...

  • Emerson Process Management 3144P - page 45

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-13 Rosemount 3144P HART 10. From the Home screen, select 1 Device Setup, 3 Configuration, 3 Dual Sensor Configuration, 4 Configure Hot Backup to prepare to configure the transmitter for Hot Backup. 1 1. Select yes to enable Hot Backup. 12. Select OK after you set the control loop to manual. 1 ...

  • Emerson Process Management 3144P - page 46

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-14 HART 5. Select OK to return the control loop to automatic control. Select HOME to return to the Home screen. 6. From the Home screen, select 1 Device Setup, 3 Configuration, 2 Sensor Configuration, 1 Change T ype and Conn, 3 Sensor 1 Setup to configure Sensor 1. 7. Set the ...

  • Emerson Process Management 3144P - page 47

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-15 Rosemount 3144P HART Reranging the transmitter sets the m easurement range to the limit s of the expected readings. Setting the measurement range to these limits maximizes transmitter performance; the transmitter is most accurate when operated within the expected temperatur e range for the ...

  • Emerson Process Management 3144P - page 48

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-16 HART Figure 3-2. Change in Input versus Change in Output with Damping Enabled. AMS Right click on the device and select “Configuration Properties” from the menu. If Sensor 1 is mapped as your pr imary variable, select the Sensor 1 tab. • Snr1 damp Apply changes made ( ...

  • Emerson Process Management 3144P - page 49

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-17 Rosemount 3144P HART Example: The high alarm value has been set to 20.8 mA. Therefore, the low saturation level, S, must be as follows: 20.5 ≤ S ≤ 20.7 mA. Preset alarms can either be 1 Rosemount or 2 NAMUR-compliant . Use the failure mode switch on the front side of the electronics (s ...

  • Emerson Process Management 3144P - page 50

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-18 HART 2. Choose from Floating Precision or One- , Tw o - , Three- , or Four-Digit Precision by pressing F4, ENTER . Press F2 to send the information to the transmitter . T o change the meter bar graph, perform the following steps: 1. From the home screen, select 1 Device Set ...

  • Emerson Process Management 3144P - page 51

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-19 Rosemount 3144P HART Message The Message variable provides the most specific user-defined means for identifying individual transmitters in mu lti-transmitter environments. It allows for 32 characters of information and is stored with the other configuration data. The message variable has n ...

  • Emerson Process Management 3144P - page 52

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-20 HART Intermittent Threshold The threshold value can be changed from the default value of 0.2%. T urning the Intermittent Sensor Detect feature OFF or leaving it ON and increasing the threshold value above the default do es not affect the time needed for the transmitter to o ...

  • Emerson Process Management 3144P - page 53

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-21 Rosemount 3144P HART T ransmitter Behavior with Inte rmittent Sensor Detect OFF When the Intermittent Sensor Detect feature is switched OFF , the transmitter tracks all process temperature changes, even if they are the consequence of an intermittent sensor . (The transmit ter in effect beh ...

  • Emerson Process Management 3144P - page 54

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-22 HART AMS Right click and select “Diagnostics and Calibration.” Choose “T est” and select “loop test,” “self test,” or “master reset.” Right-click on device and choose “status” to view errors. ...

  • Emerson Process Management 3144P - page 55

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-23 Rosemount 3144P HART Loop T est The Loop T est command verifies the output of the transmitter , the integrity of the loop, and the operations of any recorders or similar devices installed in the loop. T o initiate a loop test, perform the following procedure: 1. Connect an external ampere ...

  • Emerson Process Management 3144P - page 56

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-24 HART MULTIDROP COMMUNICATION Multidropping refers to the connection of several transmitters to a single communications transmission line. Communication between the host and the transmitters takes place digit ally with the analog output of the transmitters deactivated. Many ...

  • Emerson Process Management 3144P - page 57

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-25 Rosemount 3144P HART USE WITH THE HART T RI-LOOP T o prepare the 3144P transmitter with dual-sensor option for use with a Rosemount 333 HART T ri-Loop, you must configure the transmitter to Burst Mode and set the process variable ou tput order . In Burst Mode, the transmitter provides digi ...

  • Emerson Process Management 3144P - page 58

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-26 HART NOTE T ake careful note of the process variable output order . Y ou must configure the HART T ri-Loop to read the variables in the same order . 5. Select OK to return the control lo op to automatic control. AMS Right click and select “Configuration” from the menu s ...

  • Emerson Process Management 3144P - page 59

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-27 Rosemount 3144P HART 3. Select temperature units for Chan nel 1 that match the dif ferential temperature units of the transmitter . 4. S pecify a range for the TV such as –100 to 100 °C. If the range is large, then a sensor drift of a few degrees will represent only a small percent of r ...

  • Emerson Process Management 3144P - page 60

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-28 HART CALIBRATION Calibrating the transmitter increases the precision of your measurement system. The user may use one or more of a number of trim functions when calibrating. T o understand the trim func tions, it is necessary to understand that HART transmitters operate dif ...

  • Emerson Process Management 3144P - page 61

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-29 Rosemount 3144P HART Figure 3-6. T rim . Sensor Input T rim The Sensor T rim command allows the user to digitally alter the transmitter ’s interpretation of the input signal as shown in Figure 3-6 on page 3-29. The sensor trim command trims, in en gineering (°F , °C, °R, K) or raw ( ? ...

  • Emerson Process Management 3144P - page 62

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-30 HART a. Select “No” if a sensor is connected to the transmitter b. Select “Y es” if using a calibration device. By selecting yes, the transmitter will be put into acti ve calibration mode (see “Active Calibrator and EMF Compensation” on page 3-31). This is criti ...

  • Emerson Process Management 3144P - page 63

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-31 Rosemount 3144P HART a. Select “No” if a sensor is connected to the transmitter b. Select “Y es” if using a calibration device. By selecting yes, the transmitter will be put into acti ve calibration mode (see “Active Calibrator and EMF Compensation” on page 3-31). This is criti ...

  • Emerson Process Management 3144P - page 64

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-32 HART EMF compensation allows the transmitter to provide sensor measurements that are not affected by unwanted volt ag es, which are typically due to thermal EMFs in the equipment connected to the transmitter or by some types of calibration equipment. If this equipment also ...

  • Emerson Process Management 3144P - page 65

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-33 Rosemount 3144P HART T o disable the transmitter-sensor matching feature from the HOME screen select 1 Device Setup , 3 Configuration , 2 Sensor Confi g, 1 Change T ype/Conn . Choose the appropriate sensor type from the ENTER SENSOR T YPE prompt. When using two sensors, repeat S teps 1 – ...

  • Emerson Process Management 3144P - page 66

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-34 Rosemount 3144P HART 1. From the HOME screen, select 1 Device setup , 2 Diag/Service , 2 Calibration , 2 D/A trim . Set the control loop to manual and select OK . 2. Connect an accurate reference meter to the transmitter at the CONNECT REFERENCE METER prompt. T o do so, shunt the power to ...

  • Emerson Process Management 3144P - page 67

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-35 Rosemount 3144P HART T ROUBLESHOOTING HART / 4–20 mA If a malfunction is suspected despit e the absence of a diagnostics message on the 375 Field Communicator display , follow the procedures described in T able 3-1 to verify that transmitter hardware and process connections are in good w ...

  • Emerson Process Management 3144P - page 68

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-36 HART T able 3-2. 375 Field Communicator Error Warning Descriptions – HAR T (1) Message Description Add item for ALL device types or only for this ONE device type Asks the user whether the hot key item being adde d should be added for all device types or only for the type ...

  • Emerson Process Management 3144P - page 69

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-37 Rosemount 3144P HART Out of memory for hotkey configuration. Delete unnecessary items. There is no more memory available to store addi tional hotkey items. Unnecessary items should be deleted to make space available. Overwrite existing configuration memory Requests permission to overwrite ...

  • Emerson Process Management 3144P - page 70

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-38 HART LCD Display The LCD display displays abbr eviated diagnostic messages for troubleshooting the transmitter . T o accommodate two-word messages, the display alternates between the first and second word. Some diagnostic messages have a higher priority than ot hers, so mes ...

  • Emerson Process Management 3144P - page 71

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-39 Rosemount 3144P HART AMS Sof tware (HART / 4-20 mA only) If a malfunction is suspected despit e the absence of a diagnostics message, follow the procedures described in T able 3-4 to verify that transmitter hardware and process connections are in good working order . Under each of four maj ...

  • Emerson Process Management 3144P - page 72

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-40 HART T able 3-5. AMS Error Warning Descriptions (1) Message Description Command not implemented The connected device does not support this function. Communication error Either a device sends back a response indicating that the message it receiv ed was unintelligible, or the ...

  • Emerson Process Management 3144P - page 73

    Reference Manual 00809-0100-4021, Rev DA November 2004 3-41 Rosemount 3144P HART AMS Screens AMS provides advanced diagnostic messa ges, as well as help screens for the messages. Using the help screens can pr ovide quick reference to remedying the situation. The trouble shooting sect ion for this manual can also be pasted in AMS to assist in quick ...

  • Emerson Process Management 3144P - page 74

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-42 HART Hot BackUp ® Hot Backup is enabled and Sensor 1 or Sensor 2 has failed. The following is displayed on the Process V ariable Screen. The suspect sensor should be investigated as soon as possible, and replaced as necessary . Sensor Drif t Alarm When the Drift Alert warn ...

  • Emerson Process Management 3144P - page 75

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P www .rosemount.com F OUNDATION Fieldbus Section 4 F OUNDATION Fieldbus Configuration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 General ...

  • Emerson Process Management 3144P - page 76

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-2 F OUNDATION Fieldbus GENERAL BLOCK INFORMATION Device Description Before configuring the device, ensu re the host has the appropriate Device Description file revision for this device . The device descriptor can be found on www .rosemount.com. The initial rele ase of the Rose ...

  • Emerson Process Management 3144P - page 77

    Reference Manual 00809-0100-4021, Rev DA November 2004 4-3 Rosemount 3144P F OUNDATION Fieldbus NOTE When an upstream block is set to OOS, this will imp act the output status of all downstream blocks. The figure below depicts the hierarchy of blocks: Link Active Scheduler The 3144P can be designated to act as the backup Link Active Scheduler (LAS) ...

  • Emerson Process Management 3144P - page 78

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-4 F OUNDATION Fieldbus Block instantiation is done by the host cont rol system or configuration tool, but not all hosts are required to implement this functionality . Please refer to your specific host or configuration tool manual for more information. Cap abilities Virtual Co ...

  • Emerson Process Management 3144P - page 79

    Reference Manual 00809-0100-4021, Rev DA November 2004 4-5 Rosemount 3144P F OUNDATION Fieldbus Analog Input Block (index number 1400, 1500, and 1600) The Analog Input Function Block (AI) processes the measurements from the sensor and makes them available to other function blocks. The output value from the AI block is in engineering uni ts and cont ...

  • Emerson Process Management 3144P - page 80

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-6 F OUNDATION Fieldbus REPORTS The 3144P supports alert report s. The Repor ts option bit must be set in the features bit string to use this feature. If it is not set, the host must poll for alerts. SOFT W LOCK and HARD W LOCK Inputs to the security and write lock f unctions i ...

  • Emerson Process Management 3144P - page 81

    Reference Manual 00809-0100-4021, Rev DA November 2004 4-7 Rosemount 3144P F OUNDATION Fieldbus MAX_NOTIFY The MAX_NOTIFY parameter value is th e maximum number of alert report s that the resource can have sent without getting a confirmation, corresponding to the amount of buffer sp ace available for alert messages. The number can be set lower , to ...

  • Emerson Process Management 3144P - page 82

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-8 F OUNDATION Fieldbus MAINT_ALARMS A maintenance alarm indicates the device or some part of the device needs maintenance soon. If the condition is ignored, the device will eventually fail. There are five parameters associ ated with MAINT_ALARMS, they are described below . MAI ...

  • Emerson Process Management 3144P - page 83

    Reference Manual 00809-0100-4021, Rev DA November 2004 4-9 Rosemount 3144P F OUNDATION Fieldbus ADVISE_ACTIVE The ADVISE_ACTIVE parameter displays which of the advisories is active. Only the advisory with the highe st priority will be displayed. This priority is not the same as the ADVISE_PRI parameter described above. This priority is hard coded w ...

  • Emerson Process Management 3144P - page 84

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-10 F OUNDATION Fieldbus T able 4-4. Resource Block SUMMARY_S TATUS messages T able 4-5. Resource Block RB.DET AILED_ST A TUS SENSOR T RANSDUCER BLOCK NOTE When the engineering units of the XD_SCALE in the associated AI Block are selected, the engineering units in the T ransduc ...

  • Emerson Process Management 3144P - page 85

    Reference Manual 00809-0100-4021, Rev DA November 2004 4-1 1 Rosemount 3144P F OUNDATION Fieldbus T able 4-7. Sensor Transducer Block XD_ERR messages T able 4-8 lists the potential errors and the possible corrective actions for the given values. The corrective actions are in order of increasing system level compromises. The first step should al way ...

  • Emerson Process Management 3144P - page 86

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-12 F OUNDATION Fieldbus Custom Meter Configuration Shipped from the factory , Pa rameter #1 (sensor 1) is configured to display the Primary V ariable (temperature) from the LCD Transducer Block. When shipping with dual sensors, sensor 2 will be configured to display T o change ...

  • Emerson Process Management 3144P - page 87

    Reference Manual 00809-0100-4021, Rev DA November 2004 4-13 Rosemount 3144P F OUNDATION Fieldbus Self T est Procedure for the LCD The SELF_TEST parameter in the Reso urce block will test LCD segments. When running, the segments of the di splay should light up for about five seconds. If your host system supports methods refer to your host documentat ...

  • Emerson Process Management 3144P - page 88

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-14 F OUNDATION Fieldbus ANALOG INPUT (AI) Simulation Simulate replaces the channel value coming from the Sensor T ransducer Block. For testing purposes, it is possib le to manually drive the output of the Analog Input Block to a desired value. There are two ways to do this. Ma ...

  • Emerson Process Management 3144P - page 89

    Reference Manual 00809-0100-4021, Rev DA November 2004 4-15 Rosemount 3144P F OUNDATION Fieldbus Indirect Select indirect when the desired out put is a calculated measurement based on the sensor measurement (e .g. ohm or mV). The relationship between the sensor measurement and the calculated measurement will be linear . XD_SCALE and OUT_SCALE The X ...

  • Emerson Process Management 3144P - page 90

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-16 F OUNDATION Fieldbus If Host System Does Not Support Methods: 1. Put transducer b lock into OOS mode. a. Go to MODE_BLK.T ARGET b. Choose OOS (0x80) 2. Go to SENSOR_CONNECTION. a. Choose 4-wire (0x4) 3. Go to SENSOR_TYPE. a. Choose PT100A385 4. Put the transducer blo ck bac ...

  • Emerson Process Management 3144P - page 91

    Reference Manual 00809-0100-4021, Rev DA November 2004 4-17 Rosemount 3144P F OUNDATION Fieldbus AI2 as T erminal T emperature (body temperature) 1. Put the AI Block into OOS mode. a. Go to MODE_BLK.T ARGET b. Choose OOS (0x80) 2. Go to CHANNEL a. Choose Body T emperature 3. Go to L_TYPE a. Choose Direct 4. Go to XD_Scale a. Choose UNITS_INDEX to b ...

  • Emerson Process Management 3144P - page 92

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-18 F OUNDATION Fieldbus Alarm Priority Alarms are grouped into five levels of priority: Stat us When a PV is passed from one function block to another , it passes a ST A TUS along with the PV . The ST A TUS ca n be: GOOD, BAD, or UNCER T AIN. When a fault occurs in the device, ...

  • Emerson Process Management 3144P - page 93

    Reference Manual 00809-0100-4021, Rev DA November 2004 4-19 Rosemount 3144P F OUNDATION Fieldbus Analog Input Diagnostics T able 4-10. AI BLOCK_ERR Conditions. T able 4-1 1. T roubleshooting the AI block Condition Number Condition Name and Description 0 Other 1 Block Configuration Error: the selected channel carries a measurement that is incompatib ...

  • Emerson Process Management 3144P - page 94

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-20 F OUNDATION Fieldbus OPERATION Overview This section contains information on operation and maintenance procedures. METHODS AND MANUAL OPERATION Each F OUNDATION fieldbus host or configuration tool has different ways of displaying and performing operations. Some hosts will u ...

  • Emerson Process Management 3144P - page 95

    Reference Manual 00809-0100-4021, Rev DA November 2004 4-21 Rosemount 3144P F OUNDATION Fieldbus Sensor Calibration, Lower and Upper T rim Methods In order to calibrate the transmitter , run the Lower and Upper T rim Methods. If your system does not support methods, manually configure the Transducer Block parameters listed below . 1. Set MODE_BLK.T ...

  • Emerson Process Management 3144P - page 96

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-22 F OUNDATION Fieldbus St atistical Process Monitoring (SPM) S tatistical Process Monitoring algorithm is intended to provide basic information regarding the behavior of process measurements such as PID control block and actual valve position. The algorithm can monitor up to ...

  • Emerson Process Management 3144P - page 97

    Reference Manual 00809-0100-4021, Rev DA November 2004 4-23 Rosemount 3144P F OUNDATION Fieldbus Monitoring Phase The monitoring phase start s after the learning process is complete. The algorithm compares the current values to the baseline values of the mean and standard deviation. During this phase the algorithm computes the percent change in mea ...

  • Emerson Process Management 3144P - page 98

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-24 F OUNDATION Fieldbus SPM#_Thresholds The SPM#_Thresholds are used to allow alerts to be sent when the values are beyond the threshold values that have been set for each parameter . Mean Limit Alert Limit value in percent change of the Mean compared with the baseline mean va ...

  • Emerson Process Management 3144P - page 99

    Reference Manual 00809-0100-4021, Rev DA November 2004 4-25 Rosemount 3144P F OUNDATION Fieldbus T ROUBLESHOOTING GUIDES Figure 4-2. 3144P troubleshooting flowchart Device does not appear on segment. Problem Identified? Ye s No Perform Recommended Action, see T able 4-12. Check Segment, see “Device does not st ay on segment” in T able 4-12 for ...

  • Emerson Process Management 3144P - page 100

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-26 F OUNDATION Fieldbus T able 4-12. Troubleshooting guide . Symptom (1) Cause Recommended Actions Device does not show up on segment Unknown Recycle power to device No power to device 1. Ensure the device is connected to the segment. 2. Check voltage at terminals. There shoul ...

  • Emerson Process Management 3144P - page 101

    Reference Manual 00809-0100-4021, Rev DA November 2004 4-27 Rosemount 3144P F OUNDATION Fieldbus Figure 4-3. Problems with communications flowchart COMMUNICATIONS ESTABLISHED BUT HAVE “BLOCK_ERR” OR AN “ALARM” CONDITION. See “PlantWeb ™ Alert s” on page 4-7 Read the following parameters in the Resource Block to determine the recommend ...

  • Emerson Process Management 3144P - page 102

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-28 F OUNDATION Fieldbus F OUNDATION Fieldbus If a malfunction is suspected despit e the absence of a diagnostics message, follow the procedures described in T able 4-13 to verify that transmitter hardware and process connections are in good working order . Under each of sympto ...

  • Emerson Process Management 3144P - page 103

    Reference Manual 00809-0100-4021, Rev DA November 2004 4-29 Rosemount 3144P F OUNDATION Fieldbus LCD Display NOTE The bar graph is not used for Foundation fieldbus devices, nor are the “Sensor 1, Differential, Sensor 2, Multidrop, or Bust Mode” annunciators.” The following are the default tags for each of the possible Function blocks which di ...

  • Emerson Process Management 3144P - page 104

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-30 F OUNDATION Fieldbus All other custom tags that are entered must be: numbers 0 - 9, letters A - Z, and/or spaces. The following are the standard temper ature unit s codes displayed on the LCD: All other custom units that are entered must be: numbers 0 - 9, letters A - Z, an ...

  • Emerson Process Management 3144P - page 105

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P www .rosemount.com Section 5 Maintenance Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 5-2 SAFETY MESSAGES Instructions and procedures in this s ...

  • Emerson Process Management 3144P - page 106

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 5-2 MAINTENANCE The 3144P transmitter has no moving part s and require a minimum amount of scheduled maintenance. The transmitte r features a modular design for easy maintenance. If a malfunction is suspected, check for an external cause before performing the diagnostics as disc ...

  • Emerson Process Management 3144P - page 107

    Reference Manual 00809-0100-4021, Rev DA November 2004 5-3 Rosemount 3144P 3. Loosen the two screws that anchor th e electronics module assembly to the transmitter housing. 4. Firmly grasp the screws and assemb ly and pull it straight out of the housing, taking care not to damage the interconnecting pins. NOTE If you are replacing the electronics m ...

  • Emerson Process Management 3144P - page 108

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 5-4 ...

  • Emerson Process Management 3144P - page 109

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P www .rosemount.com Certified SIS Section 6 Certified Safety Instrumented System (SIS) 4–20 mA only Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-1 Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson Process Management 3144P - page 110

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 6-2 Certified SIS INST ALLATION No special installation is required in addition to the standard installation practices outlined in this document. Always ensure a proper seal by installing the electronics housing cover(s) so that metal cont acts metal. Environmental limit s are a ...

  • Emerson Process Management 3144P - page 111

    Reference Manual 00809-0100-4021, Rev DA November 2004 6-3 Rosemount 3144P Certified SIS Security Switch Position the security switch to the “ON” position to prevent accidental or deliberate change of configuration data during normal operation. SIS Additions In addition to the dual sensor configur ations available in the standard 3144P , the sa ...

  • Emerson Process Management 3144P - page 112

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 6-4 Certified SIS 375 FIELD COMMUNICATOR The Menu T ree and Fast Key sequences a ssume that Dev v1, DD v2 (for SIS) is being used. 3144P SIS Menu T ree Figure 6-2 displays a complete 3144P SIS menu tree for use with the 375 Field Communicator . Options listed in bold type indica ...

  • Emerson Process Management 3144P - page 113

    Reference Manual 00809-0100-4021, Rev DA November 2004 6-5 Rosemount 3144P Certified SIS 3144P SIS Fast Key Sequences Fast key sequences are listed below for 3144P SIS Safety Certified transmitter functions. NOTE: T able 6-1 provides alphabetical function lists for all Field Communicator tasks as well as their corresponding fast key sequences. For ...

  • Emerson Process Management 3144P - page 114

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 6-6 Certified SIS OPERATION AND MAINTENANCE Proof T est The following proof tests are recommended. In the event that an error is found in the safety functionality , proof test results and corrective actions t aken must be documented at www . rosemount.com/safety . Use "T ab ...

  • Emerson Process Management 3144P - page 115

    Reference Manual 00809-0100-4021, Rev DA November 2004 6-7 Rosemount 3144P Certified SIS Proof test intervals are based on sensor failure rates from the Safety Equipment Reliability Handbook , exida.com, 2003. A low stress environment is assumed, with 30% of SIL 2 PFDavg limit budgeted for the transmitter and sensor element. See the FMEDA report fo ...

  • Emerson Process Management 3144P - page 116

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 6-8 Certified SIS ...

  • Emerson Process Management 3144P - page 117

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P www .rosemount.com Prior Use SIS Section 7 Prior Use (PU) Safety Instrumented System 4–20 mA only Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-1 Safe Failure Fraction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag ...

  • Emerson Process Management 3144P - page 118

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 7-2 Prior Use SIS SAFE FAILURE FRACTION The Safe Failure Fraction calculation for the combination of the 3144P and the process sensor must consider the effect s of the transmitter ’s process sensor diagnostics. The following is an example only . The 3144P FMEDA report should b ...

  • Emerson Process Management 3144P - page 119

    Reference Manual 00809-0100-4021, Rev DA November 2004 7-3 Rosemount 3144P Prior Use SIS Changing Switch Position The Failure Mode and Securi ty switches are located on the top center of the electronics module (see Figure 7-1). The electronics module is on the electronics side of the transmitte r housing. For transmitters with LCD displays, the ele ...

  • Emerson Process Management 3144P - page 120

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 7-4 Prior Use SIS ...

  • Emerson Process Management 3144P - page 121

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P www .rosemount.com Appendix A Reference Dat a HART and Foundation Fieldbus S peci fications . . . . . . . . page A-1 HART / 4–20 mA Specifications . . . . . . . . . . . . . . . . . . . . . p age A-6 Foundation Fieldbus Specifications . . . . . . . . . . . . . . . . . page A-8 ...

  • Emerson Process Management 3144P - page 122

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P A-2 Mounting T ransmitters may b e attached directly to the sensor . Op tional mounting brackets (codes B4 and B5) permit remote mounting. See “Optional T ransmitter Mounting Brackets” on page A-12. Wei gh t Enclosure Ratings NEMA 4X, CSA Enclosure T ype 4X, IP66, and IP68. ...

  • Emerson Process Management 3144P - page 123

    Reference Manual 00809-0100-4021, Rev DA November 2004 A-3 Rosemount 3144P External Ground Screw Assembly The external ground screw assembly can be ordered by specifying code G1 when an enclosure is specified. However , some approvals include the ground screw assembly in the transmitter shipme nt, hence it is not necessary to order code G1. The tab ...

  • Emerson Process Management 3144P - page 124

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P A-4 Accuracy Reference Accuracy Example (HART only) When using a Pt 100 ( α = 0.00385) sensor input wi th a 0 to 100 °C span: Digital Accuracy would be ±0.10 °C, D/A accuracy would be ±0.02% of 100 °C or ±0.02 °C, T otal = ±0.12 °C. Differential Cap ability Exists Betw ...

  • Emerson Process Management 3144P - page 125

    Reference Manual 00809-0100-4021, Rev DA November 2004 A-5 Rosemount 3144P Ambient T emperature Effect T able A-1. Ambient T emperature Effect T ransmitters may be installed in loca tions where the ambient temperature is between –40 and 85 °C (–40 and 185 °F). T o maintain excellent accuracy perfo rmance, each transmitter is individually char ...

  • Emerson Process Management 3144P - page 126

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P A-6 HART / 4–20 MA SPECIFICATIONS Power Supply External power supply required. T ransmitters operate on 12.0 to 42.4 V dc transmitter terminal voltage (with 250 ohm load, 18.1 V dc power supply voltage is required). T ransmitter power terminals rated to 42.4 V dc. Wiring Diagr ...

  • Emerson Process Management 3144P - page 127

    Reference Manual 00809-0100-4021, Rev DA November 2004 A-7 Rosemount 3144P T emperature Limits HART Communicator Connections 375 Field Communicator connections ar e permanently fixed to power/signal block. Failure Mode The 3144P features software and ha rdware failure mode detection. An independent circuit is designed to pr ovide backup alarm outpu ...

  • Emerson Process Management 3144P - page 128

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P A-8 F OUNDATION FIELDBUS SPECIFICATIONS Power Supply Powered over F OUNDATION Fieldbus with standard fieldbus power supplies. T ransmitters operate on 9.0 to 32.0 V dc, 1 1 mA maximum. Transmitter power terminals are rated to 42.4 V dc. Wiring Diagram See Figure 2 on page A-13. ...

  • Emerson Process Management 3144P - page 129

    Reference Manual 00809-0100-4021, Rev DA November 2004 A-9 Rosemount 3144P Statu s If self-diagnostics detect a sensor burnout or a transmitter failure, th e status of the measurement will be updated accordi ngly . The status may also send the PID output to a safe value. F OUNDATION Fieldbus Parameters Sof tware Upgrade in the Field Software for th ...

  • Emerson Process Management 3144P - page 130

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P A-10 Instantiable Function Blocks • All the function blocks used by the transmitter are instantiable, meaning the total number of function blocks is only limited by the physical memory available in the transmitter . Since on ly the instantiated blocks can use physical memory , ...

  • Emerson Process Management 3144P - page 131

    Reference Manual 00809-0100-4021, Rev DA November 2004 A-1 1 Rosemount 3144P T ransmitter Dimensional Drawing T op V iew Side View Dimensions are in inches (millimeters) T ransmitter Dimensional Drawing for Conduits with M20 x 1.5, PG 13.5, and JIS G 1 / 2 Entries T op V iew Front View Dimensions are in inches (millimeters) 2.0 (51) 4.4 (1 12) Labe ...

  • Emerson Process Management 3144P - page 132

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P A-12 Optional T ransmitter Mounting Brackets Option Code B4 Bracket Option Code B5 Bracket Dimensions are in inches (millimeters) 1.04 (26) 1.55 (39) 3.65 ±0.06 (92) 1.0 (25) 2.81 ±0.03 (71) 0.41 (10) Diameter 0.375 (10) Diameter (2 Places) 2.0 ± 0.03 (50) 3044-2101A01A; B01B ...

  • Emerson Process Management 3144P - page 133

    Reference Manual 00809-0100-4021, Rev DA November 2004 A-13 Rosemount 3144P FIGURE 1. HART / 4–20 mA Wiring Diagram 3144P Single-Sensor Connections Diagram 3144P Dual-Sensor Connections Diagram * T ransmitter must be configured fo r a 3-wire RTD in order to recognize an RTD with a compensation loop. ** Emerson Process Managem ent provides 4-wire ...

  • Emerson Process Management 3144P - page 134

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P A-14 ORDERING INFORMATION Model Product Description 3144P T emperature Transmitter Code T ransmitter Housing T ype/Conduit Entry D1 Field Mount Housing (Dual-Compartment), Aluminum, 1 / 2 –14 NPT D2 Field Mount Housing (Dual-Compartment), Aluminum, M20 x 1.5 (CM20) D3 Field Mo ...

  • Emerson Process Management 3144P - page 135

    Reference Manual 00809-0100-4021, Rev DA November 2004 A-15 Rosemount 3144P Code Options PlantWeb Functionality A01 Regulatory control suite: PID with autotune, arit hmetic, signal characteri zer , input selector – F OUNDATION fieldbus only D01 Diagnostics suite: SPM diagnostics, drift alert – F OUNDATION fieldbus only Mounting Bracket B4 Unive ...

  • Emerson Process Management 3144P - page 136

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P A-16 St andard Configuration Both standard and custom configuration settings may be changed. Unless specified, the transmitter will be shipped as follows: Custom Configuration The 3144P transmitter can be ordered wi th custom configuration. The table below lists the requirement ...

  • Emerson Process Management 3144P - page 137

    Reference Manual 00809-0100-4021, Rev DA November 2004 A-17 Rosemount 3144P T o custom configure the 3144P with the dual-sensor option transmitter for one of the applications described below , indi cate the appropriate option code in the model number . If a sensor type is not specified, the transmitter will be configured for two 3-wire Pt 100 ( α ...

  • Emerson Process Management 3144P - page 138

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P A-18 Option Code U6 A verage T emperature Primary Usage When average measurement of two dif ferent process temper atures is required.If a sensor fails, an alert will be sent and the primary variable will hold the measurement of the working sensor . Primary V ariable Sensor Avera ...

  • Emerson Process Management 3144P - page 139

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P www .rosemount.com Appendix B Product Certifications Rosemount 3144P With HART / 4–20 mA . . . . . . . . . . . . . p age B-1 Rosemount 3144P With Foundation fi eldbus . . . . . . . . . p age B-6 Inst allation Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p ...

  • Emerson Process Management 3144P - page 140

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P B-2 E5 Explosion Proof for Class I, Division 1, Groups A, B, C, D. Dust Ignition-Proof for use in Class II/III, Division 1, Groups E, F , and G . Explosion-Proof and Dust Ignition-Proof when installed in accordance with Rosemount drawing 03144-0320. Indoor and outdoor use. NEMA ...

  • Emerson Process Management 3144P - page 141

    Reference Manual 00809-0100-4021, Rev DA November 2004 B-3 Rosemount 3144P N1 CENELEC / A TEX T ype n Approval (Zone 2) Certificate Number: BAS01A TEX3432X A TEX Category Marking II 3 G EEx nL IIC T6 (T amb = –40 to 50 °C) EEx nL IIC T5 (T amb = –40 to 75 °C) U i = 55V S pecial Conditions for Safe Use (X): The transmitter is not capable of wi ...

  • Emerson Process Management 3144P - page 142

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P B-4 N7 T ype N Approval Certificate Number: AUS Ex 02.3794X Ex n IIC T6 (T amb = –60 to 50 °C) Ex n IIC T5 (T amb = –60 to 75 °C) IP66 U n = 55 V P n = 1.3 W I7 Intrinsic Safety Approval Certificate Number: AUS Ex 02.3794X Ex ia IIC T6 (T amb = –60 to 50 °C) Ex ia IIC T ...

  • Emerson Process Management 3144P - page 143

    Reference Manual 00809-0100-4021, Rev DA November 2004 B-5 Rosemount 3144P Additional Certifications American Bureau of Shipping (ABS) T ype Approval ABS T ype Approval for temperature m easurements in hazardous locations on ABS Classed V essels, Marine and Of fshore Installations. T ype Approval is based on Factory Mutual (FM) Approval s; therefor ...

  • Emerson Process Management 3144P - page 144

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P B-6 ROSEMOUNT 3144P WITH F OUNDATION FIELDBUS Approved Manufacturing Locations Rosemount Inc. – Chanhassen, Minnesota, USA Rosemount T emperature GmbH – Germany Emerson Process Management Asia Pacific – Singapore European Union Directive Information The EC declaration of c ...

  • Emerson Process Management 3144P - page 145

    Reference Manual 00809-0100-4021, Rev DA November 2004 B-7 Rosemount 3144P T emperature codes: T5 (T amb = – 60 to 75 °C), T6 (T amb = – 60 to 50°C) Canadian S tandards Association (CSA) Approvals I6 CSA Intrinsic Safety / FISCO and Division 2 Intrinsically Safe / FISCO for use in Class I, Division 1, Groups A, B, C, and D; Class II, Division ...

  • Emerson Process Management 3144P - page 146

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P B-8 T able B-4. Input Entity Parameters Special Conditions for Safe Use (x): 1. The apparatus enclosure may cont ain light metals. The apparatus must be installed in such a manner as to minimize the risk of imp act or friction with other metal surfaces. 2. A T ransient protectio ...

  • Emerson Process Management 3144P - page 147

    Reference Manual 00809-0100-4021, Rev DA November 2004 B-9 Rosemount 3144P Brazilian Certifications Centro de Pesquisas de Ener gia Eletrica (CEPEL) Approval I2 CEPEL Intrinsic Safety – Consult factory for availability . Jap anese Certifications Japanese Industrial S tandard (JIS) Flameproof Certification E4 Consult factory for availability . Com ...

  • Emerson Process Management 3144P - page 148

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P B-10 Figure B-1. Factory Mutual Explosion-Pr oof Installation Drawing 03144-0320, Rev . AB 3144_3144-0320A01A ...

  • Emerson Process Management 3144P - page 149

    Reference Manual 00809-0100-4021, Rev DA November 2004 B-1 1 Rosemount 3144P Figure B-2. FM Intrinsic Safety and Noincendive Fiel d Circuit Configuration Installation Drawing 03144-0321, Rev AB. Sheet 1 of 3. 3144_3144-0321A01A ...

  • Emerson Process Management 3144P - page 150

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P B-12 Sheet 2 of 3. 3144_3144-0321A02A ...

  • Emerson Process Management 3144P - page 151

    Reference Manual 00809-0100-4021, Rev DA November 2004 B-13 Rosemount 3144P Sheet 3 of 3 3144_3144- 0321A04A ...

  • Emerson Process Management 3144P - page 152

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P B-14 Figure B-3. FM 3144 Fieldbus Intrinsic Safety / FISC O Installation Drawing 03144- 5075, Rev AB. Sheet 1 of 4. 3144-5075_1 ...

  • Emerson Process Management 3144P - page 153

    Reference Manual 00809-0100-4021, Rev DA November 2004 B-15 Rosemount 3144P Sheet 2 of 4. 3144-5075_ ...

  • Emerson Process Management 3144P - page 154

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P B-16 Sheet 3 of 4 3144-5075_3 ...

  • Emerson Process Management 3144P - page 155

    Reference Manual 00809-0100-4021, Rev DA November 2004 B-17 Rosemount 3144P Sheet 4 of 4 3144-5075_4 ...

  • Emerson Process Management 3144P - page 156

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P B-18 Figure B-4. CSA Intrinsic Safety Approval Conf iguration Installation Drawing 03144-0322, Rev . AA 3144_3144-0322A01A ...

  • Emerson Process Management 3144P - page 157

    Reference Manual 00809-0100-4021, Rev DA November 2004 B-19 Rosemount 3144P Figure B-5. CSA 3144 Fieldbus Intrinsic Safety / FISC O Installation Drawing 03144- 5076, Rev AA. Sheet 1 of 3. 3144_3144-5 076A01A_1 ...

  • Emerson Process Management 3144P - page 158

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P B-20 Sheet 2 of 3. 3144_3144-5076A01A_2 ...

  • Emerson Process Management 3144P - page 159

    Reference Manual 00809-0100-4021, Rev DA November 2004 B-21 Rosemount 3144P Sheet 3 of 3 3144_3144- 5076A01A_3 ...

  • Emerson Process Management 3144P - page 160

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P B-22 Figure B-6. ISSEPCENELEC Flame-Proof T emperature Measurement Assembly Installation Drawing 03144-0324, Rev . AA 3144_3144-0324A02A ...

  • Emerson Process Management 3144P - page 161

    Reference Manual 00809-0100-4021, Rev DA November 2004 B-23 Rosemount 3144P Figure B-7. S tandard Australia Quality Assurance Serv ices Flameproof T emperature Measurement Assembly Installation Drawing 03144-0325, Rev . AA 3144_3144- 0325A01A ...

  • Emerson Process Management 3144P - page 162

    Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P B-24 ...

  • Emerson Process Management 3144P - page 163

    ...

  • Emerson Process Management 3144P - page 164

    Emerson Process Management © 2004 Rosemount Inc. All rights reserved. ¢00809-0100-4021q¤ Rosemount, the Rosemount logotype, and Hot Backup are registered trademarks of Rosemount Inc. HART is a registered trademark of the HART Communication Foundation. T eflon is a registered trademark of E.I. du Pont de Nemours & Co. All other marks are the ...

Manufacturer Emerson Process Management Category Marine Instruments

Documents that we receive from a manufacturer of a Emerson Process Management 3144P can be divided into several groups. They are, among others:
- Emerson Process Management technical drawings
- 3144P manuals
- Emerson Process Management product data sheets
- information booklets
- or energy labels Emerson Process Management 3144P
All of them are important, but the most important information from the point of view of use of the device are in the user manual Emerson Process Management 3144P.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Emerson Process Management 3144P, service manual, brief instructions and user manuals Emerson Process Management 3144P. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Emerson Process Management 3144P.

A complete manual for the device Emerson Process Management 3144P, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Emerson Process Management 3144P by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Emerson Process Management 3144P.

A complete Emerson Process Management manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Emerson Process Management 3144P - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Emerson Process Management 3144P, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Emerson Process Management 3144P, that we can find in the current document
3. Tips how to use the basic functions of the device Emerson Process Management 3144P - which should help us in our first steps of using Emerson Process Management 3144P
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Emerson Process Management 3144P
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Emerson Process Management 3144P in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Emerson Process Management 3144P?

Use the form below

If you did not solve your problem by using a manual Emerson Process Management 3144P, ask a question using the form below. If a user had a similar problem with Emerson Process Management 3144P it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)