Reliance Water Heaters 317686-000 - page 1
1 Instruction Manual PRINTED 0810 317686-000 KEEP THIS MANUAL IN THE POCKET ON HEA TER FOR FUTURE REFERENCE WHENEVER MAINTENANCE ADJUSTMENT OR SERVICE IS REQUIRED. ALL TECHNICAL AND W ARRANTY QUESTIONS: SH OU LD BE DIR EC TED T O THE LOCA L DE AL ER FROM WHO M TH E W A TE R HEA TE R W AS PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE T O THE COMP ...
-
Reliance Water Heaters 317686-000 - page 2
2 SAFE INST ALLA TION, USE AND SERVICE The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. Read and obey all saf ...
-
Reliance Water Heaters 317686-000 - page 3
3 GENERAL SAFETY INFORMA TION ...
-
Reliance Water Heaters 317686-000 - page 4
4 GENERAL SAFETY INFORMA TION at le as t 1 8" (4 5. 7 cm ) ab ov e th e floo r. This will reduce, but not eliminate, the ri sk ...
-
Reliance Water Heaters 317686-000 - page 5
5 Thank Y ou for purchasing this water heater . Properly installed and maintained, it should give you years of trouble free service. Abbreviations Found In This Instruction Manual: • CSA -CanadianStandards Association • ANSI- AmericanNationalStandardsInstitute • NFP A -NationalFireProtection ...
-
Reliance Water Heaters 317686-000 - page 6
6 INST ALLA TION REQUIREMENTS FOR THE COMMONWEAL TH OF MASSACHUSETTS COMMONWEAL TH OF MASSACHUSETTS For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or o ...
-
Reliance Water Heaters 317686-000 - page 7
7 PP SS (SEE ACCESS PA NE L CAUTION) W 6 (1 5 cm ) MA XIMU M AI R GA P TO A SUIT ABLE DRAI N TYPICAL INST ALLA TION * CAUTION HARNESS HAS 120 VAC. IN OPERATION. ** See “PLANNIN G THE VENT SYSTEM” , “CONDENSA TE” and “BLOWER ASSEMBL Y INST ALLA TION” for more information. *** The side recirculation loop connections may not be used as the ...
-
Reliance Water Heaters 317686-000 - page 8
8 TYPICAL INST ALLA TION CONDENSA TE HOSE AND DRAIN P AN FIGURE 1A. ...
-
Reliance Water Heaters 317686-000 - page 9
9 TYPICAL INST ALLA TION FIGURE 2. MIXING V AL VE / THERMAL EXP ANSION T ANK USAGE AND SP ACE HEA TING MIXING V AL VES DA NGER Wa ter temperatur e over 125° F (52°C) c an cause severe burns instantl y resulting in severe injury or death. Children, the elderly and the physically or mentally disabled are at highest risk for scald injury . Fe el wat ...
-
Reliance Water Heaters 317686-000 - page 10
10 F ACTS TO CONSIDER ABOUT THE LOCA TION Car efull y cho os e an ind oor loca ti on for the new wate r hea te r , beca us e the placement is a very important consideration for the safety of the occupants in the building and for the most economical use of the appliance. This water heater is not for use in manufactured (mobile) homes or outdoor inst ...
-
Reliance Water Heaters 317686-000 - page 11
11 in an alcove or closet, the entire oor must be covered by the panel. Failuretoheedthiswarningmayresultinarehazard. Minimum clearances between water heater and combustible construction are 0 inch at the sides and rear , 5.5” (14.0 cm)? ...
-
Reliance Water Heaters 317686-000 - page 12
12 Such a condition often will result in a yellow , luminous burner flame, causing sooting of the combustion chamber , burners and flue tubes and creates a risk of asphyxiation. Do not install the water heater in a conned space unless an adequate supply of air for combustion and ventilation is brought in to ...
-
Reliance Water Heaters 317686-000 - page 13
13 Figure 7. The water heater should have clearances of at least 1 inch (25 mm) from the sides and back and 6 inches (15 0 mm) from the front of the appliance. The opening should directly communicate with the outdoors or should communicate through a vertical or horizontal duct to the outdoors or spaces t ...
-
Reliance Water Heaters 317686-000 - page 14
14 T h i s w a t e r h e a t e r s h o u l d n o t b e c o n n e c t e d t o a n y h e a t i n g s y s t e m s o r co mpo nent(s )us edwit hanon -p otab lewaterh eatinga ppli ance. Al l pi ping co mpo nents c onne cted to thi s uni t fo r sp ace hea ting app lica tion s shoul d be suit abl e for use w ith p otabl e water . To x ...
-
Reliance Water Heaters 317686-000 - page 15
15 THERMAL EXP ANSION As wate r is heate d, it exp ands (therm al exp ansi on). In a closed system the volume of water will grow when it is heated. As the volume of water grows there will be a corre spondi ng increa se in water pressure due to ther mal expa nsio n. Therm al expansi on can caus e pre matu re tan ...
-
Reliance Water Heaters 317686-000 - page 16
16 discharge opening must not be blocked or reduced in size under any cir cum sta nces. Exc ess iv e le ngt h, o ve r 30 fee t (9 .1 4 m) , or use of mo re tha n four el bo ws can ca use rest ri cti on an d redu ce th e disc ha rge capacity of the valve. No valve or other obstruction is to be placed between the ...
-
Reliance Water Heaters 317686-000 - page 17
17 A g as l ine of suf f ic ient size mu st b e r un t o th e wate r he ater . Co nsult t he c urre nt edit ion of Na tion al Fuel G as Co de (A NSI Z 223 . 1/NFPA54)andyourga ssuppli erc once rni ngpipes ize. There must be: • A readily accessible manual shuttoff valve in ...
-
Reliance Water Heaters 317686-000 - page 18
18 N ev er us e th i s w a t er he at er un l es s it is co mp l e te ly fu ll of wa t er . To pr ev en t d a m a ge to t he ta nk , t he ta nk mu st be l le d w it h w at er . W at er mu st o w fr om thehotwaterfaucetbeforeturning“ON”gastothewaterheate ...
-
Reliance Water Heaters 317686-000 - page 19
19 TERMINA TION CLEARANCES SIDEW ALL POWER VENT V X VEN T TERMINAL AIR SUPPL Y INLE T A RE A WHERE TERMINAL IS NO T PERMITTED v v A G V FIXE D CLOSED FIXE D CLOSED OPERABLE OPERABLE V C B B B B F B V V A J V H M X X V V K B E D L POWER VENT (using room air for combustion) EXTERIOR CLEARANCES FOR SIDE WA LL VENT TERMINA TION FIGURE 15. V ent termina ...
-
Reliance Water Heaters 317686-000 - page 20
20 PLANNING THE VENT SYSTEM Plan the route of the vent system from the discharge of the blower to the planned location of the vent terminal. Refer to V AA instruction on page 26 while planning the vent system. 1. Layout total vent system to use a m ini mum of vent pipe and elbows. 2. Thiswater heateris capableofventing ? ...
-
Reliance Water Heaters 317686-000 - page 21
21 The condensate trap may be primed by lling the CONDENSA TE U-ASSEMB L Y with tap water while the water heater is not operating. The system is fully primed when the water level reaches the adaptor connected into the T ee. In most installations the water heater will self-prime thecondensate trap during? ...
-
Reliance Water Heaters 317686-000 - page 22
22 CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERA TION. VERIFY PROPER OPERA TION AFTER SERVICING. POWER VENT WIRING SCHEMA TIC - FIGURE 19. m a y b e e a si er to ma rk bo t h t h e i n si de an d ou t s i de wa ll . Al i g n h o le s by drilling a hole through center of ...
-
Reliance Water Heaters 317686-000 - page 23
23 INST ALLA TION OF VENT SYSTEM, SIDEW ALL With the route of the venting system and selection of materials completed, as discussed in the section of this manual titled PLANNING THE VENT SYSTEM, the through the wallvent terminalin placeand therst section of piping, up to rst elbow , in ...
-
Reliance Water Heaters 317686-000 - page 24
24 VENT ATTENUA TI ON ASSEMBL Y IN S T A L L A TIO N I N S T R U CT IO NS The V ent Attenuation Assembly (V AA) is designed to provide a reduction in fan noise created in the blower wheel. This installation of this V AA is optional. Review directions thoroughly prior to installing the new V AA. Please contact the manuf ...
-
Reliance Water Heaters 317686-000 - page 25
25 b a r b , u s e a w i r e t i e o r h o s e c l a m p (n o t s u p p l i e d w i t h k i t) and se cure. 6 . T a ke t h e o t h er e n d of t h e f l ex i b le t u bi n g a nd s l id e i t t hr o u gh the h ose c lamp o n the j acket top cover an d inst all it i nto one of the f our bar b f itt ings in ...
-
Reliance Water Heaters 317686-000 - page 26
26 VENT PIPE PREP ARA TION 1. INITIAL PREP ARA TION A. Make sure the solvent cement you are planning to use is designedforthespecicapplicationyouareattempting. B. Know the physical and chemical characteristics and limitations of the PVC and CPVC piping materials that you are about to use. C. Know the reputation of your manuf ...
-
Reliance Water Heaters 317686-000 - page 27
27 B. Deburring U se a k n i fe , p l a s t i c p i p e de b u r r i ng t oo l , o r l e t o r e m o v e b ur r s f r o m t h e e nd o f s m a l l d ia m e t e r p i p e . Be s u re to re m o v e a l l b ur r s f r o m ar o u n d t he i ns i d e a s w e ll a s t h e o u ts i d ...
-
Reliance Water Heaters 317686-000 - page 28
28 ...
-
Reliance Water Heaters 317686-000 - page 29
29 It is recommended that lower water temperatures be used to avoid the risk of scalding. It is further recommended, in all cases, that the water temperaturebe set for thelowest temperature whichsatises your hot water needs. This will also provide the most energy efcient operat ...
-
Reliance Water Heaters 317686-000 - page 30
30 FOR YOUR INFORMA TION ST ART UP CONDITIONS SMOKE/ODOR It is not uncommon to experience a small amount of smoke and odor during the initial start-up. This is due to burning off of oil from metal parts, and will disappear in a short while. STRANGE SOUNDS Possib le noises due to expansi on and contract ion of some metal parts during periods of heat ...
-
Reliance Water Heaters 317686-000 - page 31
31 BURNER OPERA TION AND INSPECTION Flood damage to a water heater may not be readily visible or immediately de te cta bl e. Ho wev er , ov era pe ri od of tim ea o od ed wa ter he at er w il l create dangerous conditions which can cause DEA TH, SERIOUS BODIL Y INJURY , OR PROPERTY DAMAGE. ...
-
Reliance Water Heaters 317686-000 - page 32
32 TEMPERA TURE-PRESSURE RELIEF V AL VE TEST D ANGER • Burn hazard . • Hot water discharge. • Ke ep clear of Te mperatur e- Pressure Relief Valve discharge outlet . It is recommended that the T emperature-Pressure Relief V alve should be checked to ensure that it is in operating condition every 6 months. Wh en ch ec ki ng th e T em pe ra tur ...
-
Reliance Water Heaters 317686-000 - page 33
33 LEAKAGE CHECKPOINTS Neveruse thiswaterheater unlessit iscompletelylled withwater . T o prevent damage to the tank, the tank must be lled with water . W atermustowfromthe hotwaterfaucetbeforeturning“ON” gas to the wa ...
-
Reliance Water Heaters 317686-000 - page 34
34 Key No. Part Description 1 Outer Door 2 Anode 3 Control Valve Assembly 4 Plastic T op 5 Blower Assembly 6 Switch and Harness Assembly 7 T&P V alve 8 Drain Valve 9 Wiring Harness 10 Anode Outlet 1 1 V ent Pipe Assembly #1 12 V ent Pipe Assembly #2 13 Vent Pipe Assembly #3 14 Inlet T ube 15 Pipe Nipple 16 Burner T ube Assembly 17 Hot Surface I ...
-
Reliance Water Heaters 317686-000 - page 35
35 TROUBLESHOOTING GUIDELINES TROUBLE SHOOTING Pleasecheckguidelinesbelow .Foryoursafety ,waterheaterserviceshouldbeperformedonlybyaqualiedservicetechnician. ReadtheGENERAL SAFETYINFORMA TIONsectionrst. INTELLI-VENT TROUBLESHOOTING CHART - USER CONTROL # LED ST A ...
-
Reliance Water Heaters 317686-000 - page 36
36 # LED ST A TUS PROBLEM SOLUTION 7 8 9 Self diagnostic check has detected a problem with the gas valve driver circuit, internal microprocessor , or other internal circuits. 1 Turn the power of f for 10-20 seconds then on again to clear these error codes. 2 If any of these error codes persist or cannot be cleared - replace the gas control valve/th ...
-
Reliance Water Heaters 317686-000 - page 37
37 Theseguidelinesshouldbeutilizedbyaqualiedserviceagent. TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES ...
-
Reliance Water Heaters 317686-000 - page 38
38 TROUBLESHOOTING GUIDELINES NOTES ...
-
Reliance Water Heaters 317686-000 - page 39
39 THIS W ARRANTY IS APPLICABLE T O THE ORIGINAL OWNER ONL Y . If the glass lined tank in this water heater shall prove upon examination by (the warrantor) to have leaked during the warranty period in normal residential use, due to natural corrosion from potabl ...
-
Reliance Water Heaters 317686-000 - page 40
40 Copyright © 2010 Reliance W ater Heater Company . All rights reserved. www .reliancewaterheaters.com 500 T ennessee W altz Parkway Ashland Cit y, TN 37015 Te chnical Support 800-365-4054 Parts 800-821-2017 ...
Do you have a question concerning Reliance Water Heaters 317686-000?
Use the form below
If you did not solve your problem by using a manual Reliance Water Heaters 317686-000, ask a question using the form below. If a user had a similar problem with Reliance Water Heaters 317686-000 it is likely that he will want to share the way to solve it.