Manual Fluke Data Acquisition System/Data Logging System 2680A

74 pages 9.57 mb
Download

Go to site of 74

Summary
  • Fluke Data Acquisition System/Data Logging System 2680A - page 1

    ® 2680A/2686A Data Acquisi tion System/Data Lo gging System Getting Started Guide June 2002 © 2002 Fluk e Corporation. A ll rights reserved. Pr inted i n USA All product nam es are trad emarks of their respec tive com panies. ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 2

    Limited Warranty and Limit ation of Liability Each Fluke pr oduct is w arranted to b e free from d efects in mater ial and w orkmans hip under norm al use and serv ice. The warra nty period is one year and beg ins on the d ate of shipm ent. Parts, pr oduct repairs and s ervices are warranted for 90 days. This warranty extends o nly to the or iginal ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 3

    i Safety In fo rmat io n W Caution This is an IEC safety Class 1 product. Before using, the ground wire in the line cord or rear panel binding post must be connect to an earth ground fo r safety. Interfe rence In form ation This equipm ent gene rates and us es radio fre quency energy and if not ins talled a nd used in s trict accordanc e with the m ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 4

    ii SAFETY TERMS IN THIS MANUAL This device has been designed and tested to meet the requi rements of EN61010-1 (Safety Requir ements for Electr ical Equipm ent for Measurement, Control and Laboratory Use). It is an Installat ion Category II device intended for operation from a normal single phase supply. The DIO relay controls are rated to 250 V ac ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 5

    iii XW WARNING Use the proper fuse. To avoid fire hazard, for fuse replacement use only a 1/2 ampere, 250 V time delay line fuse. DC POWER SOURCE The device may also be ope rated from a 9 V to 45 V dc powe r source when either the rear panel ground binding post or the power cord grounding conductor is connected properly. The input is protected by a ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 6

    iv XW WARNING DO NOT OPERATE IN EXPLOSI VE ATMO SPHERES To avoid personal injury or death, do not remove the device cove r without first removing the power source connec ted to the rear panel. Do not operate the device without the cover properly installed. Ther e is no need for the operator to remove the cover. DO N OT A TTEMP T T O OPE RAT E IF PR ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 7

    v Additi onal Safety Inf ormatio n The fo llowing table p rovides add itional s afety inform ation. General Specificat ions Specification Characteristi c Size 473 mm (18.6 in) x 423 m m (17 in) x 237 mm (9.3 in) Weight 2680A/2686A (empty) 8.5 Kg (18.9 lb) 2680A – FAI 0.8 Kg (1.8 lb) 2680A – PAI 1.2 Kg (2.7 lb) 2680A – DIO 0.8 Kg (1.8 lb) Powe ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 8

    vi ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 9

    vii Table of Contents Contents Page Safety I nformation ........................................................................................... i Introducti on ..................................................................................................... 1 Contacting Fluke ................................................................. ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 10

    2680A/2686A Getting Start ed Guide viii Module Con figuratio n Dialog .............................................................. 31 Analog Channel Conf igura tion Dialog ................................................ 31 DIO Config uration Dialog ................................................................... 31 Computed Channe l Configura ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 11

    1 Getting Started Introduc tion The 2680A Data Acq uisition Sy stem (DAS) and 2686A Data L ogg ing System (DLS) provide 20 to 120 cha nnels that operate i n conjun ction with F luke DAQ software to form a data a cquisitio n system . The 2686A com es with a rem ov able PC Card (PCMCI A) for stand- alone stor age operation. This s ocket accep ts A TA ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 12

    2680A/268 6A Getting Start ed Guide 2 Contac ting Fluke To contac t Fluke, cal l one of the following telephone num bers: USA: 1-888- 99-FLUKE (1-888-993- 5853) Canada: 1- 800-36-FLUKE (1- 800-363-5853) Europe: +3 1 402-675- 200 Japan: +8 1-3- 3434-0181 Singapore : +65- 738-5655 Anywhere in the world : +1-425- 446-5500 O r , v i s i t F l u k e ’ ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 13

    Getting Star te d Configuri ng the 268X A 3 Configuring t he 268XA You must conf igure th e 268XA dev ice befo re using it. The following sections provide b asic con figurat ion inform ation. Refer to th e Users M anual for additi onal config uration inf orm ation. Reviewing and Setting the Base Channel Number Perform the proced ure belo w to rev i ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 14

    2680A/268 6A Getting Start ed Guide 4 REVIEW Communic ations displ ay for reviewi ng the Base C hannel Num ber (BCN) SET Communic ations displ ay for setti ng the BCN SET Base Channe l Number dis play for s etting the BCN 10s digits (for exam ple, 45) REVIEW Base Channe l Number dis play for rev iewing the BC N number (for ex ample, 4 5) CH Front P ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 15

    Getting Star te d Configuri ng the 268X A 5 Reviewing and Setting the Line Frequency Perform the proced ure below to review or se t the line frequency . Line frequen cy selection allows the dev ice to optim ize internal c ircuitry for be st accuracy . (See Figure 2 f or exam ples.) • Line Frequency Choice s Se lect 50 Hz or 6 0 Hz as th e frequen ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 16

    2680A/268 6A Getting Start ed Guide 6 REVIEW Communic ations displ ay for reviewi ng the line frequency SET Communic ations displ ay for setti ng the line frequency SET Hz Line frequ ency dis play for set ting the line freque ncy to 60 H z SET Hz Line frequ ency dis play for set ting the line freque ncy to 50 H z REVIEW Hz Line frequ ency dis play ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 17

    Getting Star te d Configuri ng the 268X A 7 Reviewing and Setting the Network Type Perform the proced ure in be low to rev iew or se t the network type to isola ted. Perform the proced ure in Table 4 to review o r set the ne twork type to g eneral. An isolated network consists of on ly 268XA Series and NetDAQ 26X dev ices and one or more hos t com ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 18

    2680A/268 6A Getting Start ed Guide 8 REVIEW Communic ations displ ay for reviewi ng the netw ork type SET Communic ations displ ay for setti ng the network type SET Network dis play for sett ing the netw ork type to isolated SET Network dis play for sett ing the netw ork type to general REVIEW Network dis play for rev iewing the netw ork type (iso ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 19

    Getting Star te d Configuri ng the 268X A 9 If you set Fluke DAQ Software for general network operation, you m ust set the network ty pe of each dev ice to gene ral. You will need to enter an I P address, and possibly a sock et port, subne t m ask and g ateway address into eac h device . Get this inform ation from y our network adm i nistrat or. Ta ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 20

    2680A/268 6A Getting Start ed Guide 10 REVIEW Comm unica tions di splay f or rev iewi ng the ne twor k type SET Communic ations displ ay for setti ng the network type SET Network dis play for sett ing the netw ork type to general SET Socket Port dis play for s etting the firs t digit (for the exam ple 0 4369) SET Socket Port dis play for s etting t ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 21

    Getting Star te d Configuri ng the 268X A 11 SET IP address dis play for s etting an IP:0 digit (for ex ample, 1 29:196:152 :101) SET IP address dis play for s etting an IP:1 digit (for ex ample, 129 :1 9 6:152 :101) SET IP address dis play for s etting an IP:1 digit (for ex ample, 129 :19 6 :152 :101) SET IP address dis play for s etting an IP:2 d ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 22

    2680A/268 6A Getting Start ed Guide 12 Reviewing and Setting the General Network Socket Port Perform the proced ure belo w to rev iew or se t the genera l netw ork Socket Port (1024 to 655 35). The defaul t is 04369. I n order t o comm unicate with e ach other, a host com puter and an device m ust use t he sam e socket por t number. (See Fig ure 4 ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 23

    Getting Star te d Configuri ng the 268X A 13 Reviewing and Setting the General Network IP Address Perform the proced ure belo w to review or set the dev ice’s genera l network I nternet Protocol (IP) addre ss. • General Network I P Address Enter th e IP A ddress supplied by your network adm inistrato r for ea ch BCN. The fo rm at is four 3 dig ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 24

    2680A/268 6A Getting Start ed Guide 14 Reviewing and Setting the Subnet Mask and Default Gateway If comm unication be tween the hos t compute r and the 2680 S eries pass es thro ugh a router or g ateway, y ou must set the subne t mask and default g ateway add ress on both the h ost com puter and t he dev ice. Get this inform ation f rom y our netwo ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 25

    Getting Star te d Configuri ng the 268X A 15 The network number of the dev ice must m atch that of the gat eway. For example, i f the gatew ay I P address is 12 9.196.180.93, and the subne t mask is 255.255.255.0, the network number is 129. 196.180.0, and the dev ice IP address m ust be in the rang e 129.196.180.1 t o 129.196.180.2 54. Table 7. Rev ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 26

    2680A/268 6A Getting Start ed Guide 16 Viewing the Device Ethernet Address Perform the proced ure in be low to v iew the D evice Ethe rnet ad dress. (See F igure 5 for exam ples.) The netwo rk adm inistrat or must k now the device Ethe rnet add ress when the dev ice operat es on a g eneral n etwork. You do not need th is inf orm ation when you oper ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 27

    Getting Star te d Configuri ng the 268X A 17 REVIEW Communic ations displ ay for viewin g the devic e Ethernet ad dress REVIEW Ethernet addr ess dis play for view ing byte 0 (f or example 0 0-80 -40-12-34-56 ) REVIEW Ethernet addr ess dis play for view ing byte 2 (f or example 00-80- 4 0-12-34-56 ) REVIEW Ethernet addr ess dis play for view ing byt ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 28

    2680A/268 6A Getting Start ed Guide 18 Host C ompu ter and Ne twork P repar atio n This sec tion con tains info rm ation for pre paring your hos t computer and sett ing up network com m unication, as sum mariz ed below. Installi ng Host Computer Ethernet Adapter Skip this se ction if y ou have an E thernet ad apter ins talled on y our com puter. Si ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 29

    Getting Star te d Host Computer and Networ k Prepar at ion 19 1 Install Ethernet Adapter 3 Install Networking Software 4 Install Fluke DAQ Software Ethernet Card OR Windows 98/NT or higher Fluke DAQ for Windows 2 Interconnect Host Computers and Instruments Instrument PC Card alg02f.eps Figure 6. Preparing for Netw ork Operation ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 30

    2680A/268 6A Getting Start ed Guide 20 Device and Host Computer Interconnection You may inter connect 268X devices a nd host com puter(s) w ith 10/10 0 Base T (twiste d pair ) wiring . If y our site is already w ired, you can use the wire in place. I f your site i s not wired, y ou are co nnecting your device di rectly to your host computer. Host C ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 31

    Getting Star te d Host Computer and Networ k Prepar at ion 21 Direct connec tion be tween a sing le host computer and a sing le dev ice with 10/100Base T is poss ible, bu t you m ust use a spe cial c able that h as it s transmit and receiv e lines cro ssed. RJ-45 10/100BaseT Outlets (Typical) Instrument 1 Host Computer 2 Host Computer 1 Instrument ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 32

    2680A/268 6A Getting Start ed Guide 22 Installi ng Host Computer Networking Software To establish Etherne t comm unication in y our host com puter, you m ust do the following : • I nstall a driv er fo r the ad apter • I nstall TCP/I P proto col st ack • Set host computer n etwork ing param eters This sec tion di scusses ins talling the adap t ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 33

    Getting Star te d Host Computer and Networ k Prepar at ion 23 Setting Host Computer Networking Parame ters This sec tion di scusses how to set y our host com pute r network ing param eters af ter you insta ll your ada pter and netw orking software. I f you plan to use Fluke DAQ software for g eneral ne twork opera tion, and y ou are just now enabl ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 34

    2680A/268 6A Getting Start ed Guide 24 I ntroduci ng Fl uke DAQ Software Fluke DAQ soft ware provides a gra phical user interf ace (GUI) to the 264XA and 268XA family of data acquisition products. You can use Fluke DAQ softw are to easily perform the followi ng: Note Fluke DAQ supports the NetDAQ de vices (2640A a nd 2645A) as wel l as the 2680A an ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 35

    Getting Star te d Ins tall ing Fluk e DA Q Soft ware 25 Note You will need to reboot your computer after you install t he Fluke DAQ software. During ins tallation, the following directori es and fil es are ins talled on y ou PC. alg100s.bmp The Fl uke DAQ subdirectorie s contain the foll owing information Alarm Collec ted alarm data and form at inf ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 36

    2680A/268 6A Getting Start ed Guide 26 Unders tanding t he User Inte rface Fluke DAQ software has a st andardized and e asy to use inte rface. This sec tion explains th e com ponents of the inte rface. Using the Toolbar A toolbar appears on all of the Fluke DAQ dialogs. Use the toolbar buttons to add and config ure device s 268XA devices a nd to na ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 37

    Getting Star te d Understan ding the Us er Interfac e 27 Table 3-1. F luke DAQ Toolbar Button s (cont) Button Function Trend button. Used to ac cess the Trend dialog to view t he scanne d data c ollected fro m 268 XA de vi ces. Alarm button. You can use t he Alarm View dialog to view On Li ne and History alarms. The Alarm s tatus icon c an also as ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 38

    2680A/268 6A Getting Start ed Guide 28 Understanding the Workspace Area The Work space A rea consis ts of a n etwork TreeVi ew and a se t of button s. Use the Workspac e Area to : • Open, Save, and Rem ove config uration files. Yo u can also us e the Save As button to renam e an existing configura tion fi le. • I nsert and Remov e devices, m od ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 39

    Getting Star te d Understan ding the Us er Interfac e 29 Checking Operational Status The icons in the TreeView chang e to indicat e the device status. Be low a re all the possible ic ons and th eir m eaning: Device Status Icon • Yellow or b lue device icons indic ates the dev ice is no t connected. • Green d evice icon indica tes the dev ice is ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 40

    2680A/268 6A Getting Start ed Guide 30 Configuration Dialogs The Config uration dia log that ap pears depend s on the node (device, m odule, or channel) y ou select in the TreeView pa nel. You can also use copy and pa ste funct ionality to s ave conf iguration tim e. Channel setting s can be cop ied from one channe l to ano ther in the same dev ice ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 41

    Getting Star te d Understan ding the Us er Interfac e 31 Note The Save command saves the ac tual 2686A configura tion to the PC Card. The Load command loads the co nfiguration f rom the PC Card to the 268 6A. • Set up the device g eneral set tings • Specify which module w ill con trol the trig ger out sig nal for m aster/ slave operation Module ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 42

    2680A/268 6A Getting Start ed Guide 32 Communication Dialogs The Comm unication d ialogs disp lay the comm unication status of connected network com ponents and allow you to interact w ith thos e com ponents. Fluk e DAQ uses the following Comm unication d ialogs. U sing the C omm unication d ialogs y ou can monito r and in terac t with: Device Comm ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 43

    Getting Star te d Understan ding the Us er Interfac e 33 Trend Dialog You can use the Trend dia log to view the s canned da ta collec ted from the 268XA devices. Th e charts c an be On Line or Histor ical. You ca n use the Expo rt button to export data to a CSV file tha t you can m anipula te using Excel. Alarm Di alog You can use the Al arm View d ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 44

    2680A/268 6A Getting Start ed Guide 34 Managing Your Network Using Fluke DAQ The f ollowing procedures provide detailed instr uctions for using Fluke DAQ to : • I nsert and config ure 268XA dev ices, module s, channe ls, and com puted channels. • Start a scan • View scan da ta. • View alarm s. Inserting and Configuring a 268XA Device To ins ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 45

    Getting Star te d Managin g Your Networ k Using Fluke DAQ 35 The dialog box ent ries inclu de: Configuratio n file Click the button or the button the to load an exis ting config uration fi le. Network Type Isolated i f the PC is connected directly to the 268XA dev ice or Gen eral if the 268XA is par t of a network . Por t Nu mber 4369 is the de fau ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 46

    2680A/268 6A Getting Start ed Guide 36 4. Specify the Base Cha nnel (1 to 99) an d Device Type and cl ick OK. A dev ice is attached to the new co nfig uration. As par t of th e insert ion proce ss, you can specify a base ch annel num ber. This n um ber is used to differ entiate ch annels in differ ent dev ices. You can inser t up to 9 9 Base Ch ann ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 47

    Getting Star te d Managin g Your Networ k Using Fluke DAQ 37 6. Set the I P Address o n the D evice S ettings d ialog. O ther field s are op tional. You may need to contac t your I nternet sup port s taff to de term ine the IP Address. alg106s.bmp The dialog box ent ries inclu de: IP Addres s Enter th e IP A ddress of th e device y ou are addi ng. ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 48

    2680A/268 6A Getting Start ed Guide 38 Monitor Chann el Select a chan nel m easurement t o display on the dev ice front pane l. You can also choo se to in crement though ac tive ch annels or to autom atical ly scan through a ll activ e channe ls. Defau lt is N one. Scan Para me ter s Parameter s you can set to sta rt, stop, and sav e scan d ata. No ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 49

    Getting Star te d Managin g Your Networ k Using Fluke DAQ 39 Inserting and Configuring a Module To insert and configure a m odule 1. High light a d evice in the TreeVi ew panel an d click the Insert button. alg107s.bmp 2. Specify the num ber a nd type of m odules you wan t to ins ert in the Mo dule dialog box. alg108s.bmp The dialog box ent ries in ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 50

    2680A/268 6A Getting Start ed Guide 40 3. Click OK . The m odules are added to the d evice and app ear in the TreeView panel. alg109s.bmp 4. Select one of the ana log m odules you inser ted and the Ana log Module se tting s dialog appea rs. alg110s.bmp ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 51

    Getting Star te d Managin g Your Networ k Using Fluke DAQ 41 The dialog box ent ries inclu de: Interval T rigger Uses the i nterv al tim er (int erval 1 timer) to set the sc an rate fo r norm al operation i n a m odule. The in terv al is user settable. External Trigge r Uses the Trig ger inpu t sig nal to star t a scan. Every tim e the exte rnal tr ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 52

    2680A/268 6A Getting Start ed Guide 42 Note If you are con figuring a DIO mod ule, th e Totalize r Configuration dialog appears. alg111s.bmp The dialog box ent ries inclu de: Start Count Used to spe cify a start count. Debounce Select deboun ce to ig nore signa ls with a per iod less t han 2 ms (50 0 Hz); otherwise, s ignals u p to 5 k Hz can be co ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 53

    Getting Star te d Managin g Your Networ k Using Fluke DAQ 43 Inserting and Configuring a Channel After se lecting a module, y ou need to ad d channe ls to th e module. To insert and configure a C hannel 1. Highlig ht a m odule in the TreeView pan el and c lick the Inser t button . alg112s.bmp 2. Specify the num ber o f channels y ou want to ins ert ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 54

    2680A/268 6A Getting Start ed Guide 44 4. Select a chan nel and the Module s etting s dialog appea rs. alg115s.bmp The dialog box ent ries inclu de: CH # XX-Y YY. The firs t two dig its ident ify the chassis ( 01-99). Th e next dig it identi fies the m odule (1- 6), and th e last two d igits identify the chan nel (1- 20). Label Use the la bel f iel ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 55

    Getting Star te d Managin g Your Networ k Using Fluke DAQ 45 Alarm 1 or A larm 2 Each channe l has two alarm s. You can set the alarm s to Off, Low , or High. A n alarm condition occu rs when a measur em ent falls be low a low alarm value (Low) or ri ses above a high alarm value (Hi gh). Fluke DAQ records all alarm conditions in a data f ile. Open ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 56

    2680A/268 6A Getting Start ed Guide 46 2. Specify the num ber o f channels y ou want to ins ert on the I nsert Chann el dialog box. alg117s.bmp 3. Click OK . The com puted chann els are add ed and app ear in the Tree View panel. alg118s.bmp ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 57

    Getting Star te d Managin g Your Networ k Using Fluke DAQ 47 4. Select a com puted channe l and th e Computed Cha nnel sett ings dialog appears. alg119s.bmp The dialog box ent ries inclu de: CH # Computed chann els ar e assigned ch annel num bers fr om 901 to 960. Label Use the la bel f ield to ide ntify w here the com puted channel is u sed. Unit ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 58

    2680A/268 6A Getting Start ed Guide 48 Alarm 1 or A larm 2 Each channe l has two alarm s. You can set the alarm s to Off, Low , or High. A n alarm condition occu rs when a measur em ent falls be low a low alarm value (Low) or ri ses above a high alarm value (Hi gh). Fluke DAQ records all alarm conditions in a data f ile. Digita l Outp u t Used to o ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 59

    Getting Star te d Managin g Your Networ k Using Fluke DAQ 49 Using Equations wit h Computed Channels Each computed channel can hav e an express ion of 250 char acters bu t the maxim um numb er of charact ers avai lable in all 60 cha nnels i s limited to 6,000 character s. For exam ple, you could use an equ ation to c alcula te the ra te of flow i n ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 60

    2680A/268 6A Getting Start ed Guide 50 alg120s.bmp The follow ing is a list of the val id notatio ns. Axxx Alarm on/off (Boo lean value o f 1 or 0) Cxxx An y channel m easurement C9xx Computed cha nnel TS Time since last m easurem ent (m illi second s) TOT To talize r Operator s +, -, *, /, **, unary +, unary - , abs, exp, int, ln, log , and sqr. ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 61

    Getting Star te d Managin g Your Networ k Using Fluke DAQ 51 Starting a Scan You can scan for data us ing a config uration s can, a device scan, or by using Spy . All scann ing options are avail able in the Comm unication window. Note You must have channels config ured for oper ation befo re starti ng a scan. Start ing a Configuration Scan To start ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 62

    2680A/268 6A Getting Start ed Guide 52 Start ing a Device Scan To start a devic e scan 1. Click the on the Fluke DAQ toolbar and highlight a dev ice in the TreeVi ew pan el. 2. Click to sta rt the sc an. Click to stop the sc an. alg122s.bmp ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 63

    Getting Star te d Managin g Your Networ k Using Fluke DAQ 53 Start ing a Scan Using Spy Spy trig gers and c ollects its own m easurem ents from up to eig ht channel s from any com bination of devices. The d ata is not stored and the dev ices you a re checking do not need to be scann ing. To start a Spy scan 1. Click the on the Fluke DAQ toolbar. Th ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 64

    2680A/268 6A Getting Start ed Guide 54 Viewing M odule Measurement Data You can view m easurement data from a m odule as it is reco rded. Sel ecting a module shows a ll 20 ch annels a s for the Com pute r Channels. Mod ules th at hav e no channels con figur ed display ques tion mark s. NC indica tes that a channel is not config ured. To view module ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 65

    Getting Star te d Managin g Your Networ k Using Fluke DAQ 55 Using the Digital I/O Poi nts Communication Dialog You can use t he Dig ital I /O Points Com m unication di alog to set any of t he 8 relay s or 20 DIO pins ac tive when an alarm condition o ccurs in th e channe l. You can also view status o f all of the relay s and DIO pins and s et or c ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 66

    2680A/268 6A Getting Start ed Guide 56 Using Trend to View Collected Data You can use the Trend dia log to view the s canned da ta collec ted from the 268XA devices. Th e charts c an be On Line or Histor ical. You ca n use the Expo rt button to export data to a CSV file tha t you can m anipula te using Excel. You can select up to eig ht channel s t ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 67

    Getting Star te d Managin g Your Networ k Using Fluke DAQ 57 The dialog box ent ries inclu de: Pen Click to selec t the dev ice, m odule, o r channel th at you wan t to v iew in the char t. You can v iew up to 8 item s on the cha rt. Type Specify On Line or H istory scan view. H istory view show s the last set o f data display ed with the pe ns. Zo ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 68

    2680A/268 6A Getting Start ed Guide 58 alg127.bmp Device ID Any dev ice from 1 to 99. Module A specific m odule in a device o r you can select al l of the m odules. Start D ate/Sta rt T ime Start Da te and St art Tim e are used to sel ect the da ta. Da ta is sto red with the date the scan began. Duration Duration is the am ount of tim e to be conv ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 69

    Getting Star te d Managin g Your Networ k Using Fluke DAQ 59 Changing the Chart Display To change the s trip chart d isplay • The Trend Se tting dia log appea rs when you doubl e-click on the chart screen. Use the Trend Setting s dialog to chang e the lo cation of the uppe r and lowe r boundary points, the s caling seen on the c hart, an d the co ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 70

    2680A/268 6A Getting Start ed Guide 60 Viewing Alarms You can use the Al arm View dia log to view On L ine and History alarms. You can filter t he ala rms by device ID , module and chann el. When an alarm occurs, the color of the dev ice icon in the con figura tion wind ow changes to r ed. As long as the alarm exists, the i con rem ains red. I n th ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 71

    Getting Star te d Managin g Your Networ k Using Fluke DAQ 61 The dialog box entrie s for On Line include: Type Specify On Line or H istory alarm view. Ack Click the appropria te button to acknowledg e the Las t Alarm or All Al arms. Alarm Devi ce Filters Choose to v iew alarm s from a select s et of d evices, m odules, and channel. When you cho ose ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 72

    2680A/268 6A Getting Start ed Guide 62 Alarm Devi ce Filters Choose to v iew alarm s from a select s et of d evices, m odules, and channel. Using Fluke DAQ System Secur ity Features You can use t he syst em secur ity fea tures to p rotect dev ice con figura tion inform ation. The sy stem security feature a llows th e adm inistrato r to add and remo ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 73

    Getting Star te d Managin g Your Networ k Using Fluke DAQ 63 Configuring Web and Alarm Mail Settings You can use the Web and Alarm Mail Setti ngs dialog to enter Fluke DAQ web configuration inform ation and to co nfigure Fluke DAQ to send e-m ail m essages report ing alarm condition. The Web Sett ings portion of dialog is used to specify a URL wher ...

  • Fluke Data Acquisition System/Data Logging System 2680A - page 74

    2680A/268 6A Getting Start ed Guide 64 The dialog box ent ries inclu de: Data Server IP Addres s The IP address o f the com puter running the Fluke DAQ applica tion. Fluke DAQ fills in this field with the first I P address found on the com puter. Note You must change th is sett ing if you wan t to use a di fferent i nterface or if you are u sing a ...

Manufacturer Fluke Category Network Card

Documents that we receive from a manufacturer of a Fluke Data Acquisition System/Data Logging System 2680A can be divided into several groups. They are, among others:
- Fluke technical drawings
- Data Acquisition System/Data Logging System 2680A manuals
- Fluke product data sheets
- information booklets
- or energy labels Fluke Data Acquisition System/Data Logging System 2680A
All of them are important, but the most important information from the point of view of use of the device are in the user manual Fluke Data Acquisition System/Data Logging System 2680A.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Fluke Data Acquisition System/Data Logging System 2680A, service manual, brief instructions and user manuals Fluke Data Acquisition System/Data Logging System 2680A. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Fluke Data Acquisition System/Data Logging System 2680A.

A complete manual for the device Fluke Data Acquisition System/Data Logging System 2680A, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Fluke Data Acquisition System/Data Logging System 2680A by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Fluke Data Acquisition System/Data Logging System 2680A.

A complete Fluke manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Fluke Data Acquisition System/Data Logging System 2680A - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Fluke Data Acquisition System/Data Logging System 2680A, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Fluke Data Acquisition System/Data Logging System 2680A, that we can find in the current document
3. Tips how to use the basic functions of the device Fluke Data Acquisition System/Data Logging System 2680A - which should help us in our first steps of using Fluke Data Acquisition System/Data Logging System 2680A
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Fluke Data Acquisition System/Data Logging System 2680A
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Fluke Data Acquisition System/Data Logging System 2680A in a specific country, if it was not possible to solve the problem on our own.