    Manual 2100-511 Page 1 of 27 INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE HEA T PUMPS MODELS W18H1 W24H1 W30H1 W36H1 W42H1 W48H1 W60H1 Manual : 2100-51 1 Supersedes: NEW File: V olume III T ab 17 Date: 10-14-08 Bard Manufacturing Company , Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. © Copyright 2008 ...

  • Bard W36H1 - page 2

    Manual 2100-511 Page 2 of 27 Content s Figures Figure 1 Fresh Air Damper Assembly ................... 5 Figure 2 Unit Dimensions ...................................... 7 Figure 3A Mounting Instructions .............................. 8 Figure 3B Mounting Instructions - W18, W24, W30, W36 .... 9 Figure 3C Mounting Instructions - W42, W48, W60 ..... 1 ...

  • Bard W36H1 - page 3

    Manual 2100-511 Page 3 of 27 GETTING OTHER INFORMA TION AND PUBLICA TIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Ele ctrical Code ...................... ANSI/ ...

  • Bard W36H1 - page 4

    Manual 2100-511 Page 4 of 27 W ALL MOUNT GENERAL INFORMA TION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE W 42 H 1– A 10 X X X X X A NOTE: Vent options X, B and M are without exhaust capability. May require separate field supplied barometric relief in buildi ng. SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external sign ...

  • Bard W36H1 - page 5

    Manual 2100-511 Page 5 of 27 DUCT WORK All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conse ...

  • Bard W36H1 - page 6

    Manual 2100-511 Page 6 of 27 s s e c c A e c i v r e S r o f d e r i u q e R s e c n a r a e l C w o l f r i A r e s n e d n o C e t a u q e d A d n a S L E D O M E D I S T F E L E D I S T H G I R H 6 3 W , H 0 3 W , H 4 2 W , H 8 1 W " 5 1 " 0 2 H 0 6 W , H 8 4 W , H 2 4 W " 0 2 " 0 2 o t d e r i u q e R s e c n a r a e l C m u ...

  • Bard W36H1 - page 7

    Manual 2100-511 Page 7 of 27 *Optional top outlet (factory installed only) for W30H and W36H models only. FIGURE 2 ) l a n i m o N ( s t n e m e r i u q e R n o i t a l l a t s n I d n a l a r u t c e t i h c r A r o f t i n U c i s a B f o s n o i s n e m i D L E D O M H T D I W ) W ( H T P E D ) D ( T H G I E H ) H ( Y L P P U SN R U T E R AB C B ...

  • Bard W36H1 - page 8

    Manual 2100-511 Page 8 of 27 FIGURE 3A W18H1, W24H1 MOUNTING INSTRUCTIONS ...

  • Bard W36H1 - page 9

    Manual 2100-511 Page 9 of 27 FIGURE 3B W30H1, W36H1 MOUNTING INSTRUCTIONS ...

  • Bard W36H1 - page 10

    Manual 2100-511 Page 10 of 27 FIGURE 3C W42H1, W48H1, W60H1 MOUNTING INSTRUCTIONS ...

  • Bard W36H1 - page 11

    Manual 2100-511 Page 11 of 27 FIGURE 4 ELECTRIC HEAT CLEARANCE W30H1, W36H1, W42H1, W48H1, W60H1 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is important to insure that the 1/4 inch minimum sp acing is maintained at all point ...

  • Bard W36H1 - page 12

    Manual 2100-511 Page 12 of 27 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 – MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS, FIGURE 2, FOR ACTUAL DIMENSIONS IF REQUIRED IF REQUIRED ...

  • Bard W36H1 - page 13

    Manual 2100-511 Page 13 of 27 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS ...

  • Bard W36H1 - page 14

    Manual 2100-511 Page 14 of 27 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW ...

  • Bard W36H1 - page 15

    Manual 2100-511 Page 15 of 27 ST ART UP THESE UNITS REQUIRE R-410A REFRIGERANT AND POL YOL ESTER OIL. GENERAL: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A refrigerant. 3. Use manifold gauges rated for R-410A (800 psi/250 psi low). 4. R-410A is a binary blend of H ...

  • Bard W36H1 - page 16

    Manual 2100-511 Page 16 of 27 ST ART UP (Continued) IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dish washing detergent. HIGH & LOW PRESSURE SWITCH All W**H wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switch. If tripped, this pressure switch ...

  • Bard W36H1 - page 17

    Manual 2100-511 Page 17 of 27 SEQUENCE OF OPERATION COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. HEATIN ...

  • Bard W36H1 - page 18

    Manual 2100-511 Page 18 of 27 FIGURE 8 DEFROST CONTROL BOARD ...

  • Bard W36H1 - page 19

    Manual 2100-511 Page 19 of 27 TROUBLESHOOTING SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE 1. NOTE: A thorough understanding of the defrost cycle sequence is essential. Review that section earlier in this manual prior to troubleshooting the control. Turn on AC power supply to unit. 2. Turn thermostat blower switch to “fan on” – the ...

  • Bard W36H1 - page 20

    Manual 2100-511 Page 20 of 27 CHECKING TEMPERATURE SENSOR OUTSIDE UNIT CIRCUIT 1. Disconnect temperature sensor from board and from outdoor coil. 2. Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open. 3. Check resistance reading to chart of resistance. Use sensor ambient temperature. (Tolerance of ...

  • Bard W36H1 - page 21

    Manual 2100-511 Page 21 of 27 TROUBLESHOOTING FIGURE 9 FAN BLADE SETTING MIS-1724 TABLE 2 FAN BLADE DIMENSION REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles. 3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws. 4. Unwire cond ...

  • Bard W36H1 - page 22

    Manual 2100-511 Page 22 of 27 TABLE 4A COOLING PRESSURE TABLE Low side pressure ± 4 PSIG High side pressure ± 10 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate charge we ...

  • Bard W36H1 - page 23

    Manual 2100-511 Page 23 of 27 TABLE 5 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductor ...

  • Bard W36H1 - page 24

    Manual 2100-511 Page 24 of 27 TABLE 6 RECOMMENDED AIRFLOW TABLE 7 INDOOR BLOWER PERFORMANCE l e d o M d e t a R * M F C d e t a R * P S E d e d n e m m o c e R e g n a R w o l f r i A d e e p S y r o t c a F n o i t c e n n o C H 8 1 W0 0 6 1 0 3 .5 2 7 - 5 7 5h g i H H 4 2 W0 0 80 2 .0 5 9 - 0 0 7h g i H H 0 3 W0 0 0 10 4 .0 0 3 1 - 0 3 9h g i H H ...

  • Bard W36H1 - page 25

    Manual 2100-511 Page 25 of 27 TABLES 8 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY TABLE 9 ELECTRIC HEAT s l e d o M1 - V 0 4 21 - V 8 0 23 - V 0 4 23 - V 8 0 23 - V 0 6 4 W Ks p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T B 47 . 6 10 5 6 3 14 . 4 10 4 2 0 1 58 . 0 25 6 0 7 11 . 8 10 0 8 2 1 64 . 4 10 0 5 0 25 . 2 10 6 3 5 12 . ...

  • Bard W36H1 - page 26

    Manual 2100-511 Page 26 of 27 W18H1-A W24H1-A W24H1-B W24H1-C W30H1-A W30H1-B W30H1-C W36H1-A W36H1-B W36H1-C W42H1-A W42H1-B W42H1-C W48H1-A W48H1-B W48H1-C W60H1-A W60H1-B W60H1-C TABLE 10 OPTIONAL ACCESSORIES r e b m u N t r a P 4 0 A - A 2 0 H W H EX 8 0 A - A 2 0 H W H EX 4 0 A - H 4 2 W H EX 8 0 A - H 4 2 W H EX 6 0 B - H 4 2 W H EX 5 0 A - 0 ...

  • Bard W36H1 - page 27

    Manual 2100-511 Page 27 of 27 TABLE 11 VENT & CONTROL OPTIONS W18, W24 W30, W36 W42, W48, W60 r e b m u N t r a Pn o i t p i r c s e D 4 1 - C M CT D O XXX 5 1 - C M C) y l n o e s a h P - 1 V 0 3 2 ( t i K t r a t S 1 XXX 1 1 1 K S) y l n o e s a h P - 1 V 0 3 2 ( t i K t r a t S 2 XXX 8 2 - C M CC A L XXX 2 - D A F Bd r a d n a t S - r e p m ...

Manufacturer Bard Category Heat Pump

Documents that we receive from a manufacturer of a Bard W36H1 can be divided into several groups. They are, among others:
- Bard technical drawings
- W36H1 manuals
- Bard product data sheets
- information booklets
- or energy labels Bard W36H1
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bard W36H1.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bard W36H1, service manual, brief instructions and user manuals Bard W36H1. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bard W36H1.

Similar manuals

A complete manual for the device Bard W36H1, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bard W36H1 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bard W36H1.

A complete Bard manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bard W36H1 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bard W36H1, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bard W36H1, that we can find in the current document
3. Tips how to use the basic functions of the device Bard W36H1 - which should help us in our first steps of using Bard W36H1
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bard W36H1
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bard W36H1 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bard W36H1?

Use the form below

If you did not solve your problem by using a manual Bard W36H1, ask a question using the form below. If a user had a similar problem with Bard W36H1 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)