    CONTENTS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 RENEWAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSTALLATION . . . . . . . . ...

  • Johnson Controls 340968-XIM-A-0108 - page 2

    340968-XIM-A-0108 2 Johnson Controls Unitary Products T A BLE OF CONTENTS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 RENEWAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 APPROVALS . . . . . . . . . . . . . . . ...

  • Johnson Controls 340968-XIM-A-0108 - page 3

    340968-XIM-A-0108 Johnson Controls Unitary Produ cts 3 GENERAL YORK Model DNA units are cooling/heating air conditioners designed for outdoor installation. Only gas pipi ng, electric power and duct connection s are required at th e point of installation. The gas-fired heate rs have spark to pilot ignition . The tubul ar heat exchangers are aluminiz ...

  • Johnson Controls 340968-XIM-A-0108 - page 4

    340968-XIM-A-0108 4 Johnson Controls Unitary Products INST ALLA TION LIMIT A TIONS These units must be installed in accordance with the follow- ing national and loca l safety codes. 1. National Electrical Code ANSI/NFPS No. 70 or Canadi an Electrical Code Part 1, C22.1 (latest editions). 2. National Fuel Gas Code Z223.1 or CAN/CGA B149 .1 or .2 Ins ...

  • Johnson Controls 340968-XIM-A-0108 - page 5

    340968-XIM-A-0108 Johnson Controls Unitary Produ cts 5 CLEARANCES All units require certain clearances for proper operation an d service. Refer to T able 10 for the clearances required for combustion, construction, serv icin g and proper unit opera- tion. DUCT WORK These units are adaptable to downflow use as well as rear supply and return air duct ...

  • Johnson Controls 340968-XIM-A-0108 - page 6

    340968-XIM-A-0108 6 Johnson Controls Unitary Products SERVICE ACCESS Access to all serviceable components is provided by the fol- lowing removable panels: • Blower compartment • Gas contro l/ el e c tr ical service access Refer to Figure 7 for location of these access panels and min- imum clearances. THERMOST A T The room thermostat should be l ...

  • Johnson Controls 340968-XIM-A-0108 - page 7

    340968-XIM-A-0108 Johnson Controls Unitary Produ cts 7 T ABLE 3: NA TURAL GAS APPLICA TION DA T A A V AILABLE ON MODELS INPUT (MBH) 1 OUTPUT (MBH) GAS RATE 2 FT. 3 /HR . NUMBER OF BURNERS T E MP. RISE °F AT FULL INPUT 3 MIN. MAX. 1 1/2, 2, 2-1/2, 3, 3-1/2 T ON 45 36 42 2 25 55 2, 2-1/2 70 56 65 3 30 60 3, 3-1/2 T ON 70 56 65 3 25 55 4, 5 T O N 80 ...

  • Johnson Controls 340968-XIM-A-0108 - page 8

    340968-XIM-A-0108 8 Johnson Controls Unitary Products GAS PIPING Proper sizing of gas piping d epends on the cubic feet per hour of gas flow required, spec ific gravity of the gas and the length of run. National Fuel Gas Code Z223.1 o r CAN/CGA B149.1 or .2 should be followed in all cases unless super- seded by local codes or gas company requiremen ...

  • Johnson Controls 340968-XIM-A-0108 - page 9

    340968-XIM-A-0108 Johnson Controls Unitary Produ cts 9 i 4. All piping should be cleaned of dirt and scale by ham- mering on the outside of the pipe and blowi ng out the loose dirt and scale. Before initial start-up, be sure that all of the gas l ines external to the u nit have been purged of air . 5. The gas supply should be a separate line and in ...

  • Johnson Controls 340968-XIM-A-0108 - page 10

    340968-XIM-A-0108 10 Johnson Controls Unitary Products T ABLE 7: PHYSICAL DA T A MODEL DNA 018 024 030 036 042 048 060 EV APORA TOR BLOWER CENTRIFUGAL BLOWER (Dia. x W. in.) 10 x 8 10 x 8 10 x 8 1 1 x 10 1 1 x 10 12 x 1 1 12 x 1 1 F AN MOTOR HP (3 S peed) 1/2 1/2 1/2 3/4 3/4 1 1 EV APORA TOR COIL R O W S D E E P 2222333 FINS PER INCH 14 13 13 15 13 ...

  • Johnson Controls 340968-XIM-A-0108 - page 11

    340968-XIM-A-0108 Johnson Controls Unitary Produ cts 11 FIGURE 7 - UNIT DIMEN SIONS - FRONT All dimensions are in inches. They are subject to change with- out notice. Certified dimensions will be provided upon request. T ABLE 9: UNIT DIMENSIONS FRONT UNIT S IZE DIMENSION “A” “B” 018 thru 042 33-1/2 18-1/4 048 and 060 41-1/2 23-1/8 T ABLE 10 ...

  • Johnson Controls 340968-XIM-A-0108 - page 12

    340968-XIM-A-0108 12 Johnson Controls Unitary Products FIGURE 8 - UNIT DIMENSIONS - FRONT & BOTTOM 2 6 - 3 / 4 6 4 - 5 / 8 8 - 7 / 8 1 1 - 7 / 8 1 9 - 1 / 4 H I G H V O L T A G E C O N N . 1 - 3 / 3 2 " D I A . K N O C K O U T F R O N T C O N D E N S A T E D R A I N 3 / 4 " ' N P T I G A S S U P P L Y 1 - 5 / 8 " D I A . K N ...

  • Johnson Controls 340968-XIM-A-0108 - page 13

    340968-XIM-A-0108 Johnson Controls Unitary Produ cts 13 SEQUENCE OF OPERA TION The unit is controlled b y a c onventional heating/cooling ther- mostat common to this class of equipment. HEA TING The control board begins a call for he at when W1 is ener- gized (connected to R). The control ignores W2 until pilot ignition has been established. The co ...

  • Johnson Controls 340968-XIM-A-0108 - page 14

    340968-XIM-A-0108 14 Johnson Controls Unitary Products The control recognize s a call for 2nd stage heat when W2 is energized (connected to "R"). The control e nergizes the hig h gas output and induced draft motor on high speed. If the call for 2nd stage heat go es away a nd the 1st stage call remains, the control de energize s the high g ...

  • Johnson Controls 340968-XIM-A-0108 - page 15

    340968-XIM-A-0108 Johnson Controls Unitary Produ cts 15 2. Pressure Switch (PS) - If the draft moto r should fail, the pressure switch prevents the ignition controls and gas valves from being energi zed. 3. Flame Sensor - The flame sensor and controls are located per Proper Fla me Adjustment, Figure 12 . If an ignition control fails to detect a sig ...

  • Johnson Controls 340968-XIM-A-0108 - page 16

    340968-XIM-A-0108 16 Johnson Controls Unitary Products 2. T urn off all electric power to the appliance if service is to be performed. 3. Remove the control access panel. 4. T urn the gas valve switch to the OFF position. DO NOT FORCE. 5. Replace the control access panel. POST -ST ART CHECK LIS T (GAS) After the entire control circuit has been ener ...

  • Johnson Controls 340968-XIM-A-0108 - page 17

    340968-XIM-A-0108 Johnson Controls Unitary Produ cts 17 T o adjust the pilot flame: 1. Remove the pilot adjustment cover screw . 2. Adjust the pilot adjustment screw to achieve the p roper pilot flame. 3. Replace the pilot adjustment cover screw after the pilot flame is set. T o remove the pilot assembly: 1. Disconnect the wiring from the control b ...

  • Johnson Controls 340968-XIM-A-0108 - page 18

    340968-XIM-A-0108 18 Johnson Controls Unitary Products CHECKING SUPPLY AIR CFM To check the supply ai r CFM after the initial balancin g has been complete d: 1. Remove the two ¼ inch dot plugs in the duct panel. 2. Insert at least 8 inches of ¼ inch tubing into each of these holes for sufficient penetration into the a irflow on both sides of the ...

  • Johnson Controls 340968-XIM-A-0108 - page 19

    340968-XIM-A-0108 Johnson Controls Unitary Produ cts 19 FIGURE 13 - DNA COIL DELTA P VS. AIRFLOW DNA018 DNA024-30 DNA042 DNA048-60 ID Coil Delta P DNA Coil Delta P vs Airflow Airflow (CFM) DNA036 DNA024-30 DNA036 DNA042 DNA048-60 DNA018 400 600 800 1600 1200 1400 2000 1000 2200 1800 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 T ABLE 13: SUPERHEA T CHARGI ...

  • Johnson Controls 340968-XIM-A-0108 - page 20

    340968-XIM-A-0108 20 Johnson Controls Unitary Products T ABLE 14: SUPERHEA T CHARGING T ABLE FOR DNA024 OUTDOOR TEMP . °F SUPERHEA T A T COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM INDOOR WB TEMP . (°F) 55 57 59 61 63 65 67 69 71 73 75 65 13.9 16.5 19.0 21.5 24.1 26.6 29.2 29.7 30.3 30.9 31.5 70 9.5 12 .5 15.5 18.5 21.5 24.5 27.5 28.2 28.8 29.4 30. ...

  • Johnson Controls 340968-XIM-A-0108 - page 21

    340968-XIM-A-0108 Johnson Controls Unitary Produ cts 21 T ABLE 17: SUPERHEA T CHARGING T ABLE FOR DNA042 OUTDOOR TEMP . °F SUPERHEA T A T COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM INDOOR WB TEMP . (°F) 55 57 59 61 63 65 67 69 71 73 75 65 18.0 19.7 21.4 23.0 24.7 26.3 28.0 29.1 30.2 31.3 32.4 70 13.4 15.3 17.3 19.3 21.2 23.2 25.2 26.6 28.1 29.6 31 ...

  • Johnson Controls 340968-XIM-A-0108 - page 22

    340968-XIM-A-0108 22 Johnson Controls Unitary Products FIGURE 14: TYPICAL WIR ING DIAGRAM DNA 018 THRU 060 (208/230-1-60 POWER SUPPL Y) ...

  • Johnson Controls 340968-XIM-A-0108 - page 23

    340968-XIM-A-0108 Johnson Controls Unitary Produ cts 23 TYPICAL WIRING DIAGRAM NOTES (SEE FIGURE 14) 1. All field wiring to be accomplished following ci ty , local and/or national codes in effect at time of installation of this unit. 2. Caution: Label all wires prior to disconnection when ser- vicing controls. Wiring errors can cause improper and d ...

  • Johnson Controls 340968-XIM-A-0108 - page 24

    Subject to change without notice. Pr inted in U.S.A. 340968-XIM-A-0108 Copyright © 2008 b y Johnson Controls, Inc. All rig hts reserved. Supersedes: 286483-XIM-B-0807 Johnson Controls Unita ry Products 5005 York Drive Norman, OK 73069 ...

Manufacturer Johnson Controls Category Air Conditioner

Documents that we receive from a manufacturer of a Johnson Controls 340968-XIM-A-0108 can be divided into several groups. They are, among others:
- Johnson Controls technical drawings
- 340968-XIM-A-0108 manuals
- Johnson Controls product data sheets
- information booklets
- or energy labels Johnson Controls 340968-XIM-A-0108
All of them are important, but the most important information from the point of view of use of the device are in the user manual Johnson Controls 340968-XIM-A-0108.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Johnson Controls 340968-XIM-A-0108, service manual, brief instructions and user manuals Johnson Controls 340968-XIM-A-0108. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Johnson Controls 340968-XIM-A-0108.

A complete manual for the device Johnson Controls 340968-XIM-A-0108, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Johnson Controls 340968-XIM-A-0108 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Johnson Controls 340968-XIM-A-0108.

A complete Johnson Controls manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Johnson Controls 340968-XIM-A-0108 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Johnson Controls 340968-XIM-A-0108, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Johnson Controls 340968-XIM-A-0108, that we can find in the current document
3. Tips how to use the basic functions of the device Johnson Controls 340968-XIM-A-0108 - which should help us in our first steps of using Johnson Controls 340968-XIM-A-0108
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Johnson Controls 340968-XIM-A-0108
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Johnson Controls 340968-XIM-A-0108 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Johnson Controls 340968-XIM-A-0108?

Use the form below

If you did not solve your problem by using a manual Johnson Controls 340968-XIM-A-0108, ask a question using the form below. If a user had a similar problem with Johnson Controls 340968-XIM-A-0108 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)