Manual Nortec Industries GS Series

78 pages 3.51 mb
Download

Go to site of 78

Summary
  • Nortec Industries GS Series - page 1

    GS Series Gas Steam Humidifier Installation, User & Maintenance Guide 1506222-D IMPORTANT: Read and save this guide for future reference. This guide to be left with equipment owner. ...

  • Nortec Industries GS Series - page 2

    FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS: Do not try to light any appliance. Do not touch any electrical switch; do not use any telephone in your building. Immediately call your gas supplier from a neighbor’s telephone. Follow th ...

  • Nortec Industries GS Series - page 3

    Table Of Contents GENERAL 1 - WARNING ................................................1 - DELIVERY ................................................1 - RECEIVING & UNPACKING EQUIPMENT ................................1 - GENERAL SPECIFICATIONS ......................................1 - MODEL DESIGNATION .........................................1 M ...

  • Nortec Industries GS Series - page 4

    PRINCIPLE OF OPERATION 22 - COMBUSTION .............................................2 2 - WATER MANAGEMENT ........................................2 2 - START UP PROCEDURE .......................................2 3 - FILLING THE SYSTEM .........................................2 3 - TESTING THE IGNITION SAFETY SHUT-OFF .............................2 ...

  • Nortec Industries GS Series - page 5

    GENERAL This installation guide has been designed to provide assistance when installing, mounting, and commissioning a GS Series humidifier. Actual on site application may vary. Consult Technical Services or your local NORTEC representative. WARNING · Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon mono ...

  • Nortec Industries GS Series - page 6

    -2- MODEL GS 100 SPECIFICATIONS FUEL BLOWER SPEED INPUT (BTUH)* STEAM CAPACITY (LBS/HR) MANIFOLD PRESS. IN W.C. NATURAL GAS MAX 140,000 105 -0.05 MIN 45,000 25 -0.05 PROPANE MAX 140,000 105 -0.35 MIN 50,000 25 -0.35 MODEL GS 200 SPECIFICATIONS FUEL BLOWER SPEED INPUT (BTUH)* STEAM CAPACITY (LBS/HR) MANIFOLD PRESS. IN W.C. NATURAL GAS MAX 280,000 21 ...

  • Nortec Industries GS Series - page 7

    -3- Snap on Installation Steamline Steam Outlet B or BH V enting T ype Control Wiring Main P ower Disconnect Shut Off T o Drain Auxiliar y Drain Air Gap with Funne l Ser vice Access Door (Mechanical) Service Access Door (Electrical) Clean Out Access Door Optional Stand Drain Gas Line Connection Fresh W ater Fill Line 3/4"min 30-80 psi Exhaust ...

  • Nortec Industries GS Series - page 8

    INDOOR INSTALLATION The installation must conform with local building codes or, in the absence of local codes, with the ANSI Z223.1, National Fuel Gas Code, and/or CAN/CGA B149 Installation Codes. Refer to the Gas Piping section of this manual. LOCATING AND MOUNTING GS Series humidifiers are designed for floor mounting or on a GS Stand (optional). ...

  • Nortec Industries GS Series - page 9

    · DO NOT mount humidifiers in an area where freezing may occur. · If humidifiers are mounted on a roof, a properly ventilated, temperature controlled, (above freezing), weatherproof enclosure must be used. · DO NOT mount humidifiers on vibrating surface. Consult factory. · The humidifier shall not be installed directly on carpeting, tile or oth ...

  • Nortec Industries GS Series - page 10

    upstream of the gas supply connection to the appliance. COMBUSTION AIR REQUIREMENTS Provide for adequate combustion and ventilation air in accordance with Sections 8.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1, or Sections 7.2, 7.3, 7.4 of CAN/CGA B149 Installation Codes, or applicable provisions of the local b ...

  • Nortec Industries GS Series - page 11

    Location of air intake and flue gas terminal must comply with all local and national regulations. EXHAUST VENTING The GSTC and GSP are classed category I and III fan assisted gas appliances. This allows two methods of venting. Listed below are instructions for both venting systems, followed by specific requirements for each system. Review the requi ...

  • Nortec Industries GS Series - page 12

    -8- Trap UL Listed Cap Required Condensate tee and trap must be installed. T ake the condensate to a floor drain or a condensate pump. B type double wall vent with double wall connectors required for category I appliances. Limitations on horizontal distance when venting with B vent BH type double wall vent with double wall connectors required and a ...

  • Nortec Industries GS Series - page 13

    · For any vent lengths over 20 feet long, insulate the vent pipe to reduce the amount of condensate that could form in the flue gases. · When the venting passes through a cold area, or location that has large amounts of air passing over the venting, it should be insulated to prevent condensation from forming inside the venting. · Vent pipe passi ...

  • Nortec Industries GS Series - page 14

    · Vent pipe must be secured with hangers or pipe straps · All horizontal runs must be adequately supported with hangers or straps to prevent sagging. Installation as a Category I Appliance · The GS series humidifiers have a fan-assisted combustion which operates with a non-positive vent static pressure when installed with the appropriate vent di ...

  • Nortec Industries GS Series - page 15

    · This appliance should not be connected to a chimney flue servicing a separate appliance designed to burn solid fuel. Never connect this humidifier to a chimney servicing a fireplace. · This venting category cannot be used in direct vent applications. Installation as a Category III Appliance · This venting system can be installed horizontally o ...

  • Nortec Industries GS Series - page 16

    The vent terminal must be installed in the same atmospheric pressure zone as the combustion air inlet of the humidifier. If this is not possible (as in cases of positive or negative room pressures) the humidifier should be installed with the direct vent option. ELECTRICAL PRIMARY WIRING All work concerning the electrical installation must be perfor ...

  • Nortec Industries GS Series - page 17

    -1 3- L1 L2 Ground Ground Wire Ground Leg 2 Pole T erminal Block Dedicated Circuit Breaker Or Disconnect Note: - 600V/3 Phase Supply . Ground Ground Wire Ground Leg 2 Pole T erminal Block L3 Neutral L1 L2 Ground Ground Wire Ground Leg 2 Pole T erminal Block L3 Neutral NOTE: V oltage At T erminal Block Must Be In Accordance With Spec. Label. All Wir ...

  • Nortec Industries GS Series - page 18

    -1 4- W ARNING: Failure to wire the controller in accordance with the wiring diagram that was supplied with the unit could permanently damage the GSTC/GSP board. Such errors will void the unit warranty . GS SERIES EXTERNAL CONTROLS WIRING CONNECTIONS LOW VOL T AGE TERMINAL STRIP NOTE: This is a wiring diagram only . For specific wiring instructions ...

  • Nortec Industries GS Series - page 19

    CONTROL INSTALLATION · Mount any wall humidistat (control or high limit) over standard electrical box at height similar to typical thermostat. Any wall humidistat should be in location representative of overall space being humidified and not in path of blower pack or air supply grille. Do not mount on an outside wall where temperature fluctuations ...

  • Nortec Industries GS Series - page 20

    · The drain line should not end in a sink used frequently by personnel, or where plumbing codes prohibit it. Route to a floor drain or equivalent for safety reasons. Internal drain water tempering will ensure a maximum of 140ºF (60ºC) exiting water temperature. · Never install PVC piping as a drain line material. Always use material suitable fo ...

  • Nortec Industries GS Series - page 21

    -1 7- BH V ent (By Nortec) AHU Insulated S team Line (By others) Gas Line with Manual Shut-off (By others) W ater Supply Manual Shut-off Drain Lines Funnel With Air Gap Roof Curb (By others) Electrical Disconnect (By others) BH V ent (By Nortec) Insulated S team Line (By others) Gas Line with Manual Shut-off Electrical Disconnect (By others) Roof C ...

  • Nortec Industries GS Series - page 22

    -1 8- FRONT RIGHT TOP Lef t Mi ni mu m Req u i red C lear anc es Mode l Front Left Right Back GS T C Out door 100 30" (76cm ) 0 40" (101.6 cm ) 6" (15.25 cm ) GS TC O utdoor 200 30" (76cm ) 0 40" (101.6 cm ) 6" (15.25 cm ) GS TC O utdoor 300 30" (76cm ) 30" (76cm ) 40" (101.6 c m ) 6" (15.25 c m ) G ...

  • Nortec Industries GS Series - page 23

    · The integral base of the GS Outdoor model is designed to mount on a curb. The curb must be built to structurally support the entire weight of the humidifier when in operation. Required curb dimensions are given in Figure #16 . · Ensure that the humidifier is mounted level. · The pan in the bottom of all outdoor models has a pipe chase for rout ...

  • Nortec Industries GS Series - page 24

    system can be damaged is by the failure of both devices. EXHAUST VENTING - OUTDOOR UNITS · All required exhaust venting is provided with each GS Outdoor model, by Nortec, including rain cap and storm collar. All venting components external to the unit are shipped with the unit and must be installed on site. Refer to Figure #19 for venting componen ...

  • Nortec Industries GS Series - page 25

    FILL WATER SUPPLY LINE · Each unit is supplied with a ½” NPT male connection to the fill valve. Refer to Figure #21 for connection details. A minimum fill rate of 10 l/min (2.6 gal/min) is required for all unit sizes. Allowable pressure range is 30-80 psig. · Always install a manual shut off within the building to allow isolation of the water ...

  • Nortec Industries GS Series - page 26

    STEAM LINES · The steam outlet connection is located at the back of the GS Outdoor unit. Steam hose(s) and clamps are supplied with the unit and are intended to provide a flexible coupling outside of the unit to the building steam lines. See Figure #23. · GS Outdoor models can develop steam pressures up to 12”w.c. to overcome duct and steam lin ...

  • Nortec Industries GS Series - page 27

    On initial start-up, the solenoid operated fill valve fills the tank. The water level reaches the backup float first and then the main float. If the backup and main floats do not read the same water level during the operation of the unit, the unit will shut down on a fault. The unit will continue to fill the unit to the top green position. The drai ...

  • Nortec Industries GS Series - page 28

    · At the completion of the float test, the humidifier will begin the combustion sequence by energizing the combustion blowers · All blowers will run at full output for 30 seconds to pre-purge the combustion chamber. During this time the controller will monitor that all air proving switches closed to prove air flow · The igniter(s) will be energi ...

  • Nortec Industries GS Series - page 29

    -2 5- GS INSPECTION CHECK LIST HUMIDIFIER MOUNTING £ Verify proper clearances around the unit £ Humidifier mounted level £ Humidifier properly secured to stand and stand bolted to floor £ All service doors accessible £ Roof curb sized correctly (Outdoor Model Only) GAS PIPING £ Correct gas line size installed £ Certified manual shut off valv ...

  • Nortec Industries GS Series - page 30

    -2 6- SUPPLY WATER LINE £ Nortec supplied adapter installed on fill valve (½”NPT) £ Manual shut off valve and union installed £ Verified pressure (30 – 80 psig) £ Water source of 10 l/min (2.6 gpm) £ Leak tested £ ½” dia. At max 4ft of the unit DRAIN LINES £ Air gap located within 3ft of the unit £ Minimum drain line size of 1” in ...

  • Nortec Industries GS Series - page 31

    · Close the shut-off valve in the water supply line · Isolate the humidifier from the electrical power supply at the main disconnect switch SCALE MANAGEMENT The gas humidifier will periodically “blowdown” water from the tank to reduce the concentration of total dissolved solids that accumulate during long term operation. Gas Humidifiers are s ...

  • Nortec Industries GS Series - page 32

    · Conductivity: Measured in micromhos. Follow the directions for the conductivity pen found inside the box. Multiply the digital reading by 1.5. The recommended operating range for conductivity is 0 - 1500 micromhos. Consult the factory is you measure outside these parameters. Tech - nology Water Type Water Cond. Range Hard - ness Range Silica Ran ...

  • Nortec Industries GS Series - page 33

    REGUL AR M AI NT ENANCE P REV ENT I V E M AI NT ENANCE Ho t S u r fa ce Igni tor X - Chec k f or c ont i nui t y . - Chec k t hat Fl am e S ens or i s s t rai ght . - Clean s ens or wit h fine s t eel wool . - Remov e fr om t he uni t and c lean wi t h c om pres s ed air from out s i de m at t i ng. N OTE : I t i s re comm e nde d to re pl a ce t h ...

  • Nortec Industries GS Series - page 34

    · Ensure that power is switched on again during periods of demand. · The GSTC model of the Gas Steam humidifier includes a pre-cleaning sequence feature. When activated (through the keypad), the unit will flush the humidifier, refill with cold water, and flush again reducing the scale accumulated at the bottom of the tank. CLEANING THE STEEL TANK ...

  • Nortec Industries GS Series - page 35

    The switch board must be replaced into the same position as before cleaning and the tie -wrap must be used to hold the float chamber in position. SERVICING THE UNIT Caution: Disconnect power before servicing this appliance. Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operat ...

  • Nortec Industries GS Series - page 36

    6. Once the pressure has been adjusted, replace the locking cap. 7. Replace the screw in the “out” pressure port and tighten firmly. COMPONENT REPLACEMENT CONSULT FACTORY PRIOR TO THE REPLACEMENT OF ANY COMPONENT. All service work must be performed by experienced and trained personnel. Only use original NORTEC spare parts to replace defective c ...

  • Nortec Industries GS Series - page 37

    with a new burner. Inspect and replace any gaskets that may be damaged. Tighten the 4 brass nuts of burner mounting plate to a torque of 95 in-lb. 8. Leak test the gas train before re-commissioning the humidifier. Removal and Installation of the Combustion Blower 1. Shut off electrical power and gas supply to the humidifier. 2. Remove the right sid ...

  • Nortec Industries GS Series - page 38

    11. Leak test the gas train before re-commissioning the humidifier. Air Switch Replacement 1. Shut off electrical power to the appliance. 2. Remove right side service panel. 3. Remove wiring connections to switch. 4. Remove pressure hose(s) from switch noting proper location. 5. Remove screws (2) holding the switch. 6. Reverse above procedure to re ...

  • Nortec Industries GS Series - page 39

    Ignition Module Replacement 1. Shut off electrical power to the humidifier. 2. Remove the front electrical access door. 3. Disconnect all wiring connections to the ignition module, labeling as required. 4. Remove the 2 screws securing the ignition module and remove. 5. Reverse the above sequence to install the new module. Transformer Replacement 1. ...

  • Nortec Industries GS Series - page 40

    Drain Pump Replacement 1. Drain the unit completely. If the pump is broken use the auxiliary drain out port. 2. Shut off electrical power to the appliance. 3. Remove front and right doors. 4. Remove wiring connections to the pump. 5. Remove hoses attached to the pump. 6. Reverse above procedure to re-install. NOTE: To avoid water spillage (some wat ...

  • Nortec Industries GS Series - page 41

    Removal of Heat Exchanger 1. 1. Take the humidifier out of operation. 2. 2. Disconnect the gas supply pipe from the connection on the humidifier and close off the pipe. 3. 3. Unlock and remove the right side panel(s). 4. 4. On Direct Vent units only: Remove hoses from air intake manifold and air inlet elbows. 5. 5. Dismount flue gas pipe at the flu ...

  • Nortec Industries GS Series - page 42

    -3 8- ...

  • Nortec Industries GS Series - page 43

    3 DAY DRAIN 3 DAY DRAIN FUNCTION SW3/7 Function Disabled OFF Function Enabled (Factory set) ON KEEP WARM 3 DAY DRAIN FUNCTION SW5/7 Function Enabled ON Function Disabled (Factory set) - 3 day drain OFF MAINTENANCE (GSP) MAINTENANCE INTERVAL (GSP) SW3/8 500 hour (Factory set) OFF 1000 hour ON ANALOG CHANNEL 1 Input Range SW1/1 SW4/1 SW 4/2 0-10V inp ...

  • Nortec Industries GS Series - page 44

    INPUT CHANNEL DUAL CHANNEL FUNCTION SW4/5 One Channel Input OFF Dual Channel Inputs ON TIME PROPORTIONING TIME PROPORTIONING SW4/7 Disabled (Factory set) OFF Enabled ON BLOWDOWN (GSP) BLOWDOWN SW5/1 SW 5/2 SW5/3 5% ON OFF OFF 10% OFF ON OFF 15% ON ON OFF 20% OFF OFF ON 25% (Factory set) ON OFF ON 30% OFF ON ON 35% ON ON ON MAINTENANCE SHUTDOWN MAIN ...

  • Nortec Industries GS Series - page 45

    NORTEC GST C-400 VERSION X.XX SYSTEM L OCK OUT 09.05.02 9:30 SYSTEM ST A TUS USER SETTINGS SERVICE LEVEL MENU MENU USE THE UP/DOWN ARROWS TO M OV E T HE POINTER TO SELECT A MENU ITEM. TO O P EN T HE SELECTION, PRESS THE ENTER BUTTON. INTRODUCT ORY SCREEN MAIN MENU Keypad Display Menu S tructure GENERAL NOR TEC TC CONTROLLER Menu Structure NOTES: Go ...

  • Nortec Industries GS Series - page 46

    MENU MENU ENTER MENU MAIN MENU SYSTEM ST ATUS USER SETTINGS ST ATUS : LOCK OUT DEMAND CHANNEL 1 0% DEMAND CHANNEL 2 0% CAP ACITY LIMIT 0% 1 2 SYSTEM DEMAND XXX% BURNERS ACTIVE X/X OUTPUT/BURNER XXXLB T OT AL OUTPUT XXXLB 1 2 3 WA TER LEVEL: X FILL V AL VE ON DRAIN V AL VE OFF DRAIN COOLING: SMART 1 4 2 3 1. DISPLA Y TOGGLES BETWEEN LOCKOUT , ACTIVE ...

  • Nortec Industries GS Series - page 47

    MENU SERVICE INTERV AL SECURITY L OOP [0/1] 3D A YD R A I N O N SAFETY SENSORS [0/1] KEEP WARM OFF T ANK SENSORS [0/1] BL OWDOWN RATE 25% FT BL OWDOWN ON XXX HOURS S TA R T D AT E: M M : D D: Y Y REMAINING XXX HOURS 1 1 1 3 3 4 2 2 2 3 1. DISPLA YS THE USER SELECT ABLE MAINTE NANCE INTERV AL 1. DISPLA YS ST A TUS OF THE SECURITY LOOP (O = OPEN I = ...

  • Nortec Industries GS Series - page 48

    ENTER MENU MENU MENU MENU MAIN MENU SYSTEM STA TUS SERVICE LEVEL USER SETTINGS SERVICE INTERVAL XXX HOURS SERVICE HIST ORY X/Y STEAM HOURS XXXX (DATE/ TIME) FAU LT HI S TO R Y X / Y (TYPE OF F AUL T) (DATE/ TIME) THIS WILL DRAIN CONTENTS OF TANK THIS WILL DRAIN CONTENTS OF TANK CONTINUE? SERVICE INTERVAL XXX HOURS SERVICE INTERVAL XXX HOURS CLEAR R ...

  • Nortec Industries GS Series - page 49

    ENTER MENU MENU MENU MAIN MENU SYSTEM STA TUS SERVICE LEV EL USER SETTINGS SHORT CYCLE DELAY SECONDS XX SHORT CYCLE DELAY CHANGE VALUE XX BURNER 1 ENABLED DISABLED THIS WILL DRAIN CONTENTS OF TANK THIS WILL DRAIN CONTENTS OF TANK CONTINUE? SERVICE INTERVAL SERVICE HISTORY FAU LT H I S TO R Y TANK DRAIN TANK PRE -CLEA N SHORT CYCLE DELAY BURNERS 1 S ...

  • Nortec Industries GS Series - page 50

    ENTER MENU MENU MAIN MENU SYSTEM ST A TUS SERVICE LEVEL USER SETTINGS TIME HH:MM DA TE MM.DD .YY UNITS: LB/HR DA TE/TIME/UNITS LANGUAGE CONTROLS WATER MANAGEMENT CONTROL TYPE CAP ACITY LIMIT CALIBRATE 1 1. VERTICAL ARROW INDICATES ADDITIONAL SELECTIONS AVAILABLE BY SCROLLING . SELECT LANGUAGE ENGLISH FRENCH GERMAN SELECT LANGUAGE ENGLISH FRENCH GER ...

  • Nortec Industries GS Series - page 51

    FTBD HOURS CHANGE HOURS? XXX FTBD HOUR CHANGE HOUR? XX FILL CORRCTN CHANGE VAL UE XXX% FLOA T CHEC K CHANGE VAL UE HH :MM DRAIN CORRCTN CHANGE VAL UE XXX% DRAIN COOL ON OFF SMART BLOWDOWN RA TE CHANGE VAL UE XX% STEAM OUTPUT ENTER MENU MAIN MENU SYSTEM ST ATUS SERVICE LEVEL USER SETTINGS DA TE/TIME/UNITS FTBD HOURS XXX FTBD HOUR XX BLOWDOWN RA TE X ...

  • Nortec Industries GS Series - page 52

    MENU MENU SET MAXIMUM CAP ACITY XXX% SET MAXIMUM CAP ACITY XXX% CALIBRATE SIGNAL? CALIBRA TE SIGNAL CALIBRA TE 4957 DATE/TIME/UNITS DATE/TIME/UNITS LANGUAGE CONTROLS LANGUAGE CONTROLS WA TER MANAGEMENT WA TER MANAGEMENT CONTROL TYPE CONTROL TYPE CAP ACITY LIMIT CAP ACITY LIMIT CALIBRATE CALIBRATE USE UP/DOWN ARROWS TO SE T MAXIMUM CAP ACITY PRESS E ...

  • Nortec Industries GS Series - page 53

    -4 9- NORTEC TC CONTROLLER INTRODUCTORY SCREEN Product name NORTEC GSTC (100-600) Version The display will indicate the revision level of the control software System Depending on system activity, the display will toggle between LOCKOUT, ACTIVE or STANDBY. Date/Time The actual date and time will be displayed. MAIN MENU The main menu lists the availa ...

  • Nortec Industries GS Series - page 54

    -5 0- SYSTEM STATUS SCREEN 1: Status: Displays the present status of the system. Depending on system activity at the time, the field could display: lockout (security loop open), active (unit generating steam) or standby (security loop closed but no modulation demand signal). Demand channel 1: This field will display the modulation demand input on t ...

  • Nortec Industries GS Series - page 55

    SCREEN 4: Service interval: This field displays the user (or factory default) setting for the humidifiers service reminder in steam hours. Remaining: This field displays the amount of time (steam hours) remaining before the next service is to be performed. Start Date: This field displays the date this service interval began. SCREEN 5: Security loop ...

  • Nortec Industries GS Series - page 56

    -5 2- SERVICE LEVEL The service level area is where service related tasks are performed. Below is a description of each field and what can be performed in them. When a parameter requires a change, press the two arrow keys and enter the password (0335). As long as you remain in this section, you will not need to enter the password more than once. Se ...

  • Nortec Industries GS Series - page 57

    Y = total number of recorded services (up to 10 maximum). STEAM HOURS XXX (DATE/TIME) This field displays the steam hours and the date and time when the specific service (X) was performed. Fault history In this area the customer can view the history of recorded faults for the humidifier. FAULT HISTORY X/Y The fault history stores the last 54 system ...

  • Nortec Industries GS Series - page 58

    Tank Pre-Clean The tank pre-clean feature when activated will activate the drain valve for a fixed period of time (depending on unit size). The fill valve will then activate, filling the tank partially with cold water. At the completion of the fill cycle the tank will once again drain. This will help to flush out any accumulated minerals as well as ...

  • Nortec Industries GS Series - page 59

    -5 5- User Settings When a parameter requires a change, press the two arrow keys and enter the password (0335). As long as you remain in this section, you will not need to enter the password more than once. Date / Time Units This field is used for modifying the Date, time and the units of measurement. The date and time are important parameters when ...

  • Nortec Industries GS Series - page 60

    Language Controls This field allows the user to select the menu language of choice (English, French, German) Here the user can select the language of choice for the menu displays. To set the language, highlight the selection then enter the user code (0335). Press enter. Use the UP/DOWN arrows to select the choice (English, French, German). Pressing ...

  • Nortec Industries GS Series - page 61

    FTBD Hour Works in conjunction with FTBD hours. Here the user sets the time of day (24 hour format) when they want the FTBD to execute. The time can be set to trigger the cycle during off hours, when the humidity requirements are minimal. The time is adjusted in one-hour increments. Blowdown Rate This parameter adjusts the frequency of blowdown cyc ...

  • Nortec Industries GS Series - page 62

    Fill CORRCTN (correction) Used for adjusting the fill rate. Adjustments to be made under factory direction only. Drain CORRCTN (correction) Used for adjusting the drain rate. Adjustments to be made under factory direction only. Drain Cool The customer can select the type of drain water tempering they require (depending on local plumbing codes) The ...

  • Nortec Industries GS Series - page 63

    Transducer Input This section is used to configure the controller for transducer signals In this section you can adjust the proportional, integral and derivative constants. There is also a PID learn algorithm which will tune the various PID constants for optimal performance. Capacity Limit In this section the customer can adjust the maximum output ...

  • Nortec Industries GS Series - page 64

    FAULT LIST GSTC f au lt displayed GSP fa ult co de displayed Descript ion of f ault Troubleshooting FAUL T NO BURNERS AVAI LI BLE NBF Once the GS controller detects an ignition module fail, it will index to t he next available ignition module. If all ignitio n modules have failed o r there a re none a vai lab le (i n the case of a 100 unit) this fa ...

  • Nortec Industries GS Series - page 65

    FAULT LIST FAUL T GAS RE-IGNITION BURNER X GIF-X Following an i gnition module fault if the modules gas valve activates t his fault will b e genera ted. -Ensure that the ignition module is not miswired or that the mod ule is not faulty by swapping it wi t h a known good one. If the problem follow s the ignition module, replace the m odule -Cons ult ...

  • Nortec Industries GS Series - page 66

    WARNING LIST GSTC Warning displayed GSP warning displayed Descript ion of w arning: Troubleshooting WARNIN G IGNITION MODULE X FAIL IMW-X Once the controller activates an ignition module, it will allow 4 minutes for the gas valve to activate. After the trial period, if the gas valve has not activated, a fault will be generated. The module will be l ...

  • Nortec Industries GS Series - page 67

    -6 3- ...

  • Nortec Industries GS Series - page 68

    GS Series Internal Components Spare Parts -6 4- Number Description Part # GS 100 GS 200 GS 300 GS 400 GS 500 GS 600 101 Cover Plate, Clean-Out Port 2523457 1 1 2 2 3 3 102 Gasket, Tank Cover Plate 2524361 1 1 2 2 3 3 103 Secondary Safety Switch 1504832 1 1 1 1 1 1 104 Fill Box 2526152 1 1 1 1 1 1 105 Vacuum Break Valve ½” npt 1505959 1 1 1 1 1 1 ...

  • Nortec Industries GS Series - page 69

    -6 5- GS Series Internal Components Spare Parts - continued Number Description Part # GS 100 GS 200 GS 300 GS 400 GS 500 GS 600 126 Igniter / flame sensor gasket 1506892 1 2 3 4 5 6 127 Hot Surface Igniter Replacement kit 110-120V Models 2528418 1 2 3 4 5 6 208-240V Models 1507695 1 2 3 4 5 6 128 Flame Sensor Replacement Kit 1507694 1 2 3 4 5 6 Ign ...

  • Nortec Industries GS Series - page 70

    -6 6- ...

  • Nortec Industries GS Series - page 71

    -6 7- GS Series Indoor Cabinetry Spare Parts Number Description Part # GS 100 GS 200 GS 300 GS 400 GS 500 GS 600 201 Service Door Assembly Mini 2524439 1 Single 2524440 1 Double 2524441 1 1 Triple 2524458 1 1 202 Fron t Door Assembly 2528421 1 1 1 1 1 1 203 Recessed Handle 2523444 1 1 1 1 2 2 204 Transformer 24/16V 15VA 50/60 hz 1505760 1 1 1 1 1 1 ...

  • Nortec Industries GS Series - page 72

    -6 8- 16 19 20 21 22 23 24 25 26 27 28 29 30 31 32 34 33 35 36 37 38 39 40 41 43 44 2 11 7 42 6 8 9 12 13 14 1 15 3 18 17 4 10 5 GS Series Outdoor Cabinetry Exploded View ...

  • Nortec Industries GS Series - page 73

    -6 9- De s cr i pti o n P a rt # GS 100 GS 200 GS 300 GS 400 GS 500 GS 600 1 T r a n s f o r m e r 2 4 / 1 6 V 1 5 V A 1 5 0 5 7 6 0 111111 2 T r a n s f o r m e r 2 0 8 - 2 4 V a c 2 5 0 V A 1 5 0 6 7 1 9 111111 F u s e 6 . 2 5 A m p f o r 2 0 8 V t r a n s f o r m e r 1 5 0 5 0 2 0 111111 3 a L C D D i s p l a y A s s e m b l y 1 5 0 7 7 4 1 1111 ...

  • Nortec Industries GS Series - page 74

    -7 0- 25 F an Hood 1507811 1 1 1 1 1 1 26 Cov er P l at e T op P anel 1508109 1 1 1 1 1 1 27 G as k et , S t eam l i ne 100 1508105 1 200/ 300 1507872 1 1 400/ 500/ 600 1507871 1 1 1 28 Cov er P l at e S t eam Li ne 100 1508106 1 200/ 300 1507870 1 1 400/ 500/ 600 1507810 1 1 1 29 S t ep-up t rans former (120/ 240V opt i on) 1508167 1 1 1 1 1 1 30 ...

  • Nortec Industries GS Series - page 75

    GS S tand Assembly Instructions 150-7308 06/26/2003 43.1in 109.4cm 43.1in 109.4cm 35.7in 90.7cm 30.2in 76.7cm O 0.5in 1.3cm DET AIL B DET AIL A A B FL OOR STAND , A SSEMBL Y INSTRUCTIONS , GS/SE ASSEMBLY INSTRUCTIONS 1. UNP ACK STAND AND CHECK THAT ALL PIECES ARE PRESENT AND UNDAMAGED . 2. ASSEMBLE STAND TO CONFIGURA TION SHOWN ON SHEET 1. HAND TIG ...

  • Nortec Industries GS Series - page 76

    -7 2- Item GS 100 GS 200 GS 300 GS 400 GS 500 GS 600 Gas Pressure Natural Gas m in "wc/mbar Natural Gas max "wc/m bar Propane min Propane max Min free air opening in/cm 13/33 23/58 35/89 47/119 59/150 71/180 Input BTU's Max 140,000 280,000 420,000 560,000 700,000 840,000 Min GSTC 45,000 Direct vent m in 60,000 Gas Piping Size in/cm 1 ...

  • Nortec Industries GS Series - page 77

    LIMITED WARRANTY Walter Meier Inc. and/or Walter Meier Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years from date of shipment, that THE COMPANY's manufactured and assembled products, not otherwise expressly warranted, are free from defects in material and workmanship. No warranty is made against cor ...

  • Nortec Industries GS Series - page 78

    PRINTED IN CANADA Walter Meier (Climate USA) Inc. 826 Proctor Avenue, Ogdensburg, New York 13669 Walter Meier (Climate Canada) Ltd. 2740 Fenton Road, Ottawa, Ontario K1T3T7 Tel: 866 NORTEC 1 Fax: 613 822 7964 northamerica.climate@waltermeier.com www.humidity.com ...

Manufacturer Nortec Industries Category Humidifier

Documents that we receive from a manufacturer of a Nortec Industries GS Series can be divided into several groups. They are, among others:
- Nortec Industries technical drawings
- GS Series manuals
- Nortec Industries product data sheets
- information booklets
- or energy labels Nortec Industries GS Series
All of them are important, but the most important information from the point of view of use of the device are in the user manual Nortec Industries GS Series.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Nortec Industries GS Series, service manual, brief instructions and user manuals Nortec Industries GS Series. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Nortec Industries GS Series.

A complete manual for the device Nortec Industries GS Series, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Nortec Industries GS Series by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Nortec Industries GS Series.

A complete Nortec Industries manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Nortec Industries GS Series - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Nortec Industries GS Series, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Nortec Industries GS Series, that we can find in the current document
3. Tips how to use the basic functions of the device Nortec Industries GS Series - which should help us in our first steps of using Nortec Industries GS Series
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Nortec Industries GS Series
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Nortec Industries GS Series in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Nortec Industries GS Series?

Use the form below

If you did not solve your problem by using a manual Nortec Industries GS Series, ask a question using the form below. If a user had a similar problem with Nortec Industries GS Series it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)