Manual Energy Tech Laboratories Modular Direct Fired Heaters

28 pages 6.85 mb
Download

Go to site of 28

Summary
  • Energy Tech Laboratories Modular Direct Fired Heaters - page 1

    April 2006 Rev. 9 FOR YOUR SAFETY The use and storage of gasoline or other flammabl e vapors and liquids in open containers in the vicinity of this appliance is hazardous . Standard and Modular Direct Fired Heaters Installation, Operation, and Maintenance Manual Modular Direct Fired Heater Standard Direct Fired Heater Direct Fired Module Save these ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 2

    TABLE OF CONTENTS WARRANTY ....................................................................................................................... ........................... 3 INSTALLA TION ................................................................................................................... .......................... 4 Mechanical ... ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 3

    3 WARRANTY This equipment is warranted to be free from defe cts in materials and workmanship, unde r normal use and service, for a period of 12 months from date of shipm ent. This warranty shall not apply if: 1. The equipment is not installed by a qualifi ed instal ler per the MANUFA CTURER’S installation instructions shipped with the product, 2. ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 4

    4 INSTALLATION It is imperative that this unit is in stalled and ope rated with the designed airflow, gas, and electrical supply in accordance with this manual. If there are any questions about any items, please call the service department at 1-866-784-6 900 for warranty and technical support issues. Mechanical WARNING: DO NOT RAISE VENTILATOR BY T ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 5

    5 Recom men ded S uppl y Du ctwor k S izes Bl ower Si ze Duct Size St rai ght Duct Lengt h 10 14 x 14 48 i n. 12 16 x 16 54 i n. 15 20 x 20 72 i n. 18 24 x 24 86 i n. 20 26 x 26 108 i n. 25 32 x 32 168 i n. through vertical portion of the ventilator base assembly flange using a minimum of eight (8) lug screws, an chor bolt s, or ot her suita ble fa ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 6

    6 Direct Fired Module Installation Indoor (INLINE) Installation Heat Module Add-On Installation Modular heat units shippe d to add heat onto existin g blower only application s require field mechanical and wiring installation. 1. Remove existing filter intake and lifting lugs from blower section in take side. 2. Attach heat module to blower intake ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 7

    7 Gas Pressure Table Gas Pressure Type Gas Pressure Size 1-3 Inlet Pressure 7 in. w.c. – 14 in. w.c. Size 4-5 Inlet Pressure 7 in. w.c. – 5 psi. Max. Manifold Pressure - Natural Gas 5 in. w.c. maximum Max. Manifold Pressure - Propane 2.5 in. w.c. maximum Gas Connection Sizes Unit Size Gas Pipe Size (NPT) Size 1 ¾” Size 2 1” Size 3 1” Siz ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 8

    8 Copper Wire Ampacity Wire Size AWG Maximum Amps 14 20 12 25 10 30 8 40 6 55 4 70 Electrical Before connecting powe r to the heater, read and understand this entire section of this docume n t. As-built wiring diagrams are furnished with each fan b y the factory, and are atta ched to the door of the unit. Electrical wiring and connections should be ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 9

    9 Remote Control Panel On units shipped with the optional remote control panel , an ele ctrical drop containing th e panel wiring is provided with the heate r. There is a terminal strip in side the remote panel th at matches the terminals in the heater unit. The remote panel shoul d be wired as shown below. BL YW RD BK PK RD WH OR BR GY BK RD YW PK ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 10

    10 Pilot Assembly OPERATION Prior to starting up or operating the heater, che ck al l fasteners for tightness. In particular, che ck the set screw in the wheel hu b, bearings and t he fan sheav es (pulleys). With p ower and gas to the heater OFF or prior to connecting ventilator to po wer, turn the fan whee l by ha nd to be sure it is not st riking ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 11

    11 Maxitrol M511 and M611 Low Fire Bypass Screw Mod Valve Voltage Summary Volts DC Firing Mode 0 to 5 VDC Low Fire 5 to 15 VDC Modulation 15 to 20 VDC High Fire Maxitrol MR212 Lo w Fire Bypass Scre w Average Man ifold Pressure vs. Firing Rate/Ft. of Bu rn er -1.0 0 0.00 1.00 2.00 3.00 4.00 5.00 6.00 0 100000 2000 00 300000 400000 50000 0 600000 Fi ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 12

    12 Adju st pilot fla me. Lock u ni t in to hig h f i re. Ad j us t incomi ng gas pressur e. Doe s h igh fi r e pr oduce at least a 70°F temp rise an d produce the correct m anifold pressu re? A djust h igh fire No Lock unit in to low fire. Yes Does thin flame fill ent i re b urne r le ng t h? Adju s t low fire. Sett in g i n comi n g p ressu re: P ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 13

    13 Maximum RPM and HP Chart Blower Size Maximum RPM Maximum HP 10” 1800 2 12” 1500 3 15” 1400 5 18” 1200 5 20” 1000 10 25” 900 20 Pulley Adjustment Illustration Setscrew Torque Thread Size Torque (IN/Lb) No. 10 33 1/4” 80 5/16” 156 3/8” 275 7/17” 384 1/2” 600 Final Start Up Procedure 1. With the air and burner systems in full ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 14

    14 Pulley Combination Chart Motor RPM 1725 1/3 to 1-1/2 H P MOTOR PULL EY Dd1 Dd2 Pd1 Pd2 AX BELTS 1VL34 1.9 2.9 2 3 Open Closed BLOWER PULLEY DATUM DIAMETER PITCH DI A METER 5 4 1/2 4 3 1/2 3 2 1/2 2 1 1/2 1 1/2 0 AK114 11 11.2 308 323 339 354 370 385 400 416 431 447 462 1/3 to 2 HP MOTOR PULL EY Dd1 Dd2 Pd1 Pd2 AX BELTS 1VL40 2.4 3.4 2.6 3.6 Open ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 15

    15 Flame Safety Controller Air Flow Switch DC Flame Signal DC Voltage Flame Status 0 to 5 VDC No Flame 6 to 11 VDC Weak Flame 12 to 18 VDC Strong Flame Sequence of Operation The direct-fired heater is most easily understood wh en broken down into smaller individual system s. There are two main systems, a make -up air fan and a heater. T he make-up ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 16

    16 Maxitrol 14 Amplifier High Temperature Limit airflow switch to close. The high airflo w switch prot ects against profile plate fail ures that cause excessive airflow through the burne r. In the ev ent that the pressure drop across th e burner is not in the range of the airflow switch, gas flow to the burne r is stopped by the Flame Safety Contro ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 17

    17 9 Begins Pilot Trial For Ignition and turns on PTFI LED 9 The pilot g as solenoid valve is opene d, the sp ark igniter begins spar king, and the flamerod sensor watches for flame initiation 9 When flame is establishe d, the FLAME LED is illuminated and m a in valve opens and the FSC powers the Maxitrol system and gas flow begin s modulating 9 Th ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 18

    18 Components The following image and list outlines the typical di rect fired heater components and their fun ctions. 1. Gas Inlet – Main gas supply conn ection 2. Motor Starter – Contactor with overload protec tion to start and prot ect motor. 3. Freeze-Stat Thermosta t (Optional) – De-energizes blo wer motor if the discharge air temperature ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 19

    19 Remote Panel Option The Remote Panel is a device used to control the ope r ation of the heater from a remote location. This unit is available in both a “2 Position” or “3 Position ” configuration and with or with out a cooling output. It also will accommodate both the Maxitrol discharge te mperature dial and the Maxitrol space sensing Se ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 20

    20 Troubleshooting The following tables list cause s and corrective actions for possibl e problems wit h direct fired heater units. Review these lists prior to consulting manufacture r. Airflow Troubleshooting Chart Problem Potential Cause Corrective Action Blown fuse or open circuit breaker Replace fuse or reset circuit breaker and check amps Disc ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 21

    21 Burner Troubleshooting Chart Problem Potential Cause Corrective Action Main gas if off Open main gas valve Air in gas line Purge gas line Dirt in pilot orifice Clean orifice with compressed air Gas pressure out of range Adjust to proper gas pressur e Pilot valve is off Turn pilot valve on Pilot orifice fitting leak Tighten pilot orifice Excessiv ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 22

    22 Remote Panel Troubleshooting Chart Light Indication Condition Possible Cause Bad voltage to unit Main disconnect i n “OFF” Position Circuit breaker tripped No Lights Power not available to Remote Panel Bad main transformer Proper unit Off Operation No problem Manual/Off/Auto Switch in “Off” Position (3 Position Remo te Panels Only) Impro ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 23

    23 Is Freeze-Stat open? Adjust or Replace Is end switch on Moto ri ze d Damp er closed? Adjust or Replace actuator YES YES NO Nothing Happe ns Is Overload tripped on starter? Reset & m easure FLA of m otor. Is it higher than rating? Adjust or change Pull ey NO NO YES Blower runs but there is no heat Is the air fl ow LED on Flame Saftey ill umin ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 24

    24 Flame Safety Service Guide (Airflow LED may or may not be illuminated) ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 25

    25 Flame Safety Service Guide (continued) (Airflow LED may or may not be illuminated) ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 26

    26 MAINTENANCE To guarantee trouble fre e operation of this heater, th e man ufacturer sugge sts following these guid elines. Most problems associated with f an failures are directly related to poor servi ce and maintenance. Please record any mainte nance or service performe d on this fan in the docum ent ation section located at the end of this ma ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 27

    27 Burner Orifice Drill Size Orifice Drill Size Gas Port 31 Air Port 43 2 weeks after startup 1. Belt tension should be checked after the first 2 weeks of fan ope ration. Belts tend to stretch and settle into pulleys after an in itial start-up sequence. Do not tension bel ts by changing the setting of the motor pulley , this will change the fan spe ...

  • Energy Tech Laboratories Modular Direct Fired Heaters - page 28

    28 April 2006 Rev. 9 Start-Up and Maintenance Documentation START-UP AND MEASUREMENTS SHOULD BE PERFORMED AFTER THE SYSTEM HAS BEEN AIR BALANCED AND WITH TH E HEAT ON (Warranty will be void without completion of this form) Job Information Job Name Service Company Address Address City City State State Zip Zip Phone Number Phone Number Fax Number Fax ...

Manufacturer Energy Tech Laboratories Category Fan

Documents that we receive from a manufacturer of a Energy Tech Laboratories Modular Direct Fired Heaters can be divided into several groups. They are, among others:
- Energy Tech Laboratories technical drawings
- Modular Direct Fired Heaters manuals
- Energy Tech Laboratories product data sheets
- information booklets
- or energy labels Energy Tech Laboratories Modular Direct Fired Heaters
All of them are important, but the most important information from the point of view of use of the device are in the user manual Energy Tech Laboratories Modular Direct Fired Heaters.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Energy Tech Laboratories Modular Direct Fired Heaters, service manual, brief instructions and user manuals Energy Tech Laboratories Modular Direct Fired Heaters. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Energy Tech Laboratories Modular Direct Fired Heaters.

A complete manual for the device Energy Tech Laboratories Modular Direct Fired Heaters, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Energy Tech Laboratories Modular Direct Fired Heaters by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Energy Tech Laboratories Modular Direct Fired Heaters.

A complete Energy Tech Laboratories manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Energy Tech Laboratories Modular Direct Fired Heaters - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Energy Tech Laboratories Modular Direct Fired Heaters, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Energy Tech Laboratories Modular Direct Fired Heaters, that we can find in the current document
3. Tips how to use the basic functions of the device Energy Tech Laboratories Modular Direct Fired Heaters - which should help us in our first steps of using Energy Tech Laboratories Modular Direct Fired Heaters
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Energy Tech Laboratories Modular Direct Fired Heaters
5. FAQ - Frequently Asked Questions