    TECHNICAL GUIDE SPLIT -SYSTEM AIR CONDITIONERS 10 SEER MODELS: H*RA018 THRU 060 (1.5 THRU 5 NOMINAL TONS, 1 PH) H*RA036 THRU 090 (3 THRU 7.5 NOMINAL TONS, 3 PH) MODELS: 018 - 060 (1 PH & 3 PH) MODELS: 076 - 090 (3 PH) Due to con tinuous p roduct improve ment, speci fica- tions are subj ect to change with out notice. Visit us on the web at www . ...

  • York H*RA036 THRU 090 - page 2

    036-21121-002 Rev. A (0602 ) 2 Unitary Products Group 1. Rat ed in accordance with ARI S tandard 1 10, utilization range “A”. 2. Dua l element fuses or HACR circuit br eaker . 3. All scrolls listed with a sup erscript “B” are Bristol scrolls. All sc rolls listed w ith a superscript “C” are Copeland scrolls. 4. The Unit Charge is correct ...

  • York H*RA036 THRU 090 - page 3

    036-21121-002 Rev. A (0602) Unitary Products Group 3 COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL ELECTRIC 2 HEA T KW W RA TED CFM NET MBH SEER W/O TXV SEER + TXV 3 EER TOT AL SENS. 1 PH 10 SEER AC WITH N1AH / G2FD H1RA018S06 N1AHB0806 2,5,8,10 17 G2FD024S17 650 19.0 14.1 10.50 - 9.80 H1RA024S06 N1AH ...

  • York H*RA036 THRU 090 - page 4

    036-21121-002 Rev. A (0602 ) 4 Unitary Products Group COOLING CAP ACITY - Up flow , Downflow , & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MBH SEER + TXV W/O TDR SEER + TXV 1 + TDR* EER TOT AL SE NS . H1RA018S06 575 725 14,17 G1F A024S14,17 650 18.0 13.3 10.00 - 9.20 14 G1F A03 ...

  • York H*RA036 THRU 090 - page 5

    036-21121-002 Rev. A (0602) Unitary Products Group 5 * Requires a 2FD Blower T ime Delay unless a standa rd furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace match-up. *** This coil is for upflow application only . H1RA036S25,46 1050 1350 17,21 G1F A036S17,21 1200 33.6 24.9 10.00 - 9.10 21,24 G1F A048S21,24 1200 3 ...

  • York H*RA036 THRU 090 - page 6

    036-21121-002 Rev. A (0602 ) 6 Unitary Products Group NOTES: 1. For condensing unit only . Does not include e ffect of evaporator motor power or heat. 2. Performance based on 1 5° superheat and 1 5° sub-cooling at condensing unit. a. Increase capacity 1% for each 2° increase in sub-cooling. b. Decrease capacity 1% for each 2° decrease in sub-co ...

  • York H*RA036 THRU 090 - page 7

    036-21121-002 Rev. A (0602) Unitary Products Group 7 ACCESSORIES* Refer to Price Manual for specific model numbers. Hard St art Kit - Provides increased starting torque for areas with low voltage. Compressor Blanket - Designed to further reduce the nor- mal compressor operating sound. Refer to price pages for specific match-ups. Off Cycle Timer Del ...

  • York H*RA036 THRU 090 - page 8

    036-21121-002 Rev. A (0602 ) 8 Unitary Products Group TYPICAL FIELD WIRING - 1 Phase Application TYPICAL FIELD WIRING - 3 Phase Application ALL FIELD WIRING T O BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES POWER WIRING 208/230-1-60 230-1-50 CONT ACTOR TERMINALS COIL GND. LUG CY R G W Y R GW POWER WIRING CONTROL WIRING F ACTORY WIRIN ...

  • York H*RA036 THRU 090 - page 9

    036-21121-002 Rev. A (0602) Unitary Products Group 9 Multipliers for determining the performance with other indoor sections . COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H1RA018S06 INDOOR COIL MODEL NO. G1F A024S14 ,17 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 550 650 750 ID DB (°F) 85 80 70 85 80 70 85 80 70 ID WB (°F) 72 67 57 72 67 5 ...

  • York H*RA036 THRU 090 - page 10

    036-21121-002 Rev. A (0602 ) 10 Unitary Products Group Multipliers for determining the p erformance with other indoor sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H1RA024S06 INDOOR COIL MODEL NO. G1F A024S14 , 17 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 600 800 1000 ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70 ID WB (°F) 72 ...

  • York H*RA036 THRU 090 - page 11

    036-21121-002 Rev. A (0602) Unitary Products Group 11 Multipliers for determining th e performance with other indoo r sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H2RA030S06 INDOOR COIL MODEL NO. G1F A036S17 ,21 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 800 1000 1200 ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70 ID WB (°F) 72 ...

  • York H*RA036 THRU 090 - page 12

    036-21121-002 Rev. A (0602 ) 12 Unitary Products Group Multipliers for determining th e performance with other indoo r sections. 1 Phase 3 Phase COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO . H2RA036S06, H1RA03 6S(25,46) INDOOR COIL MODEL NO. G1F A036S17 ,21 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 1 150 1250 1350 ID DB (°F) 85 80 70 85 8 ...

  • York H*RA036 THRU 090 - page 13

    036-21121-002 Rev. A (0602) Unitary Products Group 13 Multipliers for determining th e performance with other indoo r sections. 1 Phase 3 Phase COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H 1RA042S06, H1RA04 2S(25,46) INDOOR COIL MODEL NO. G1F A048S21 ,24 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 1200 1400 1600 ID DB (°F) 85 80 70 85 80 ...

  • York H*RA036 THRU 090 - page 14

    036-21121-002 Rev. A (0602 ) 14 Unitary Products Group Multipliers for determining th e performance with other indoo r sections. 1 Phase 3 Phase COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO . H1RA048S06, H1RA04 8S(25,46) INDOOR COIL MODEL NO. G1F A048S21 ,24 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 1200 1400 1600 ID DB (°F) 85 80 75 70 85 ...

  • York H*RA036 THRU 090 - page 15

    036-21121-002 Rev. A (0602) Unitary Products Group 15 Multipliers for determining th e performance with other indoo r sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H3RA060S06 INDOOR COIL MODEL NO. G1F A060S21 ,24 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 2050 1800 1550 ID DB (°F) 85 80 70 85 80 70 85 80 70 ID WB (°F) 72 67 57 72 ...

  • York H*RA036 THRU 090 - page 16

    036-21121-002 Rev. A (0602 ) 16 Unitary Products Group Multipliers for determining th e performance with other indoo r sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H1RA060S(25,46) INDOOR COIL MODEL NO. G2FD060S24A CONDENSER ENTERING AIR TEMPERA TURE ID CFM 1450 1700 1950 ID DB (°F) 85 80 70 85 80 70 85 80 70 ID WB (°F) 72 67 57 ...

  • York H*RA036 THRU 090 - page 17

    036-21121-002 Rev. A (0602) Unitary Products Group 17 Multipliers for determining th e performance with other indoo r sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H1RA076S(25,46) INDOOR COIL MODEL NO. K4EV090 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 2100 2600 3100 ID DB (°F) 85 80 70 85 80 70 85 80 70 ID WB (°F) 72 67 57 72 67 ...

  • York H*RA036 THRU 090 - page 18

    036-21121-002 Rev. A (0602 ) 18 Unitary Products Group Multipliers for determining th e performance with other indoo r sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H1RA090S(25,46) INDOOR COIL MODEL NO. K4EV090 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 2400 3000 3600 ID DB (°F) 85 80 70 85 80 70 85 80 70 ID WB (°F) 72 67 57 72 6 ...

  • York H*RA036 THRU 090 - page 19

    036-21121-002 Rev. A (0602) Unitary Products Group 19 MA TCHING INDOOR COMPONENTS G1UA 1/2 CASED UPFLOW G1HD HORIZONT AL DUCT G2FD* MUL TI-POSITION (UPFLOW , HORIZONT AL AND DOWNFLOW) * Available with factory installed horizontal drain pan. ADD-ON COILS - FOR FURNACE APPLICA TIONS G1NA UNCASED UPFLOW G1F A FULL CASED UPFLOW G2FD090 is upflow only . ...

  • York H*RA036 THRU 090 - page 20

    Subject to change without notice. Printed in U .S.A. 036-21121-002 Rev. A (0602) Copyright © by York International Corp. 2002. All right s reserved. Supersedes: 036-21 121-001 Rev . A (301) Unitary 5005 Norman Product s Y ork O K Group Drive 73069 NOTES ...

Manufacturer York Category Air Conditioner

Documents that we receive from a manufacturer of a York H*RA036 THRU 090 can be divided into several groups. They are, among others:
- York technical drawings
- H*RA036 THRU 090 manuals
- York product data sheets
- information booklets
- or energy labels York H*RA036 THRU 090
All of them are important, but the most important information from the point of view of use of the device are in the user manual York H*RA036 THRU 090.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals York H*RA036 THRU 090, service manual, brief instructions and user manuals York H*RA036 THRU 090. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product York H*RA036 THRU 090.

Similar manuals

A complete manual for the device York H*RA036 THRU 090, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use York H*RA036 THRU 090 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of York H*RA036 THRU 090.

A complete York manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual York H*RA036 THRU 090 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the York H*RA036 THRU 090, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the York H*RA036 THRU 090, that we can find in the current document
3. Tips how to use the basic functions of the device York H*RA036 THRU 090 - which should help us in our first steps of using York H*RA036 THRU 090
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with York H*RA036 THRU 090
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of York H*RA036 THRU 090 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning York H*RA036 THRU 090?

Use the form below

If you did not solve your problem by using a manual York H*RA036 THRU 090, ask a question using the form below. If a user had a similar problem with York H*RA036 THRU 090 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)