Manual BlueWalker SNMP CP-504

99 pages Not applicable
Download

Go to site of 99

Summary
  • BlueWalker SNMP CP-504 - page 1

    NetAgent UPS SNMP Agent User ’ s Manual ...

  • BlueWalker SNMP CP-504 - page 2

    User Guide for NetAgent Version 6 .0 Firmware version 2.42 Copyright Information Copyright © 2000-2009, Mega S ystem Technologies, Inc. All rights reserved. Reproduction without permi ssion is prohibited. Technical Support and Contact Information Mega System Technologies, Inc. Tel: +886-2-87922060 Fax: +886-2-87922066 Web: www.megatec.com.tw E-mai ...

  • BlueWalker SNMP CP-504 - page 3

    Contents Chapter1. Introduction ________________________________________ 1 Section1. Features __________________________________________ 1 Section2. Applications _______________________________________ 2 2.1 NetAgent makes your UPS on the Internet ____________________ 2 2.2 NetAgent Provides Shutdown Utilities ________________________ 2 2.3 NetAgen ...

  • BlueWalker SNMP CP-504 - page 4

    2.1.3 Current S tatus ______________________________________ 22 2.1.4 Remote Control ____________________________________ 22 2.1.5 Meter/Chart ________________________________________ 24 2.1.6 Modem S tatus (For 3 Ports NetAgent II only) ______________ 25 2.1.7 Environment Sensors-NetFeeler II ______________________ 26 2.2 Configuration ___________ ...

  • BlueWalker SNMP CP-504 - page 5

    2.6 AC power status _______________________________________ 60 2.7 Battery S tatus _________________________________________ 60 2.8 S tatus History _________________________________________ 60 Chapter 8. SNMPView – Wi ndows Based UPS Management System __ 61 Section1. Introduction ______________________________________ 61 Section2. System Requirem ...

  • BlueWalker SNMP CP-504 - page 6

    Appendix B -3 Po rt s NetAgent II with SMS Modem ________________ 87 Appendix C –SMS Serv er with SMS Modme ______________________ 91 4 ...

  • BlueWalker SNMP CP-504 - page 7

    Chapter1. Introduction Section1. Features NetAgent is a new generation SNMP (Simple Network Management Protocol) monitoring product. Not only could remote control the UPS and get the current status of it, the NetAgent II –3Ports al so could provide ot her functions, ex. connect to Modem or GS M Modem to make the monitoring possible when there is ...

  • BlueWalker SNMP CP-504 - page 8

    Section2. Applications 2.1 NetAgent makes your UPS on the Internet When the UPS connects with NetAgen t, the system manager could check each and every UPS condition by a comp uter with Browser installed. The manager could monitor and control the UPS by simply input the IP address of the NetAgent which connects to the UPS. When there is a power abno ...

  • BlueWalker SNMP CP-504 - page 9

    Fig.1 NetAgent connection Software Fig.2 3 Port NetAgent II Diagram 3 ...

  • BlueWalker SNMP CP-504 - page 10

    4 Section3. NetAgent Models 3.1 NetAgent Models NetAgent II Model P/N Package Contents Internal/External 1/3 Ports 1/3 phases CP504 CT504 1. 1Port Internal card 2. NetAgent Utility CD 3. User Manual Internal CP503 CT503 1. 1Port External card 2. NetAgent Utility CD 3. User Manual 4. Adaptor External 1 Port 1/3 phases BP505 1. 3 Port External Agent ...

  • BlueWalker SNMP CP-504 - page 11

    5 DP532 DT532 1.Enternal NetAgent Mini with LCD Display 2. NetAgent Utility CD 3. User Manual 4. 5.3V DC adapter External *DT/CT version same dim ension as DP/CP. *DT/CT has RTC and 2MB flash to m aintain correct date/time and log saving. ...

  • BlueWalker SNMP CP-504 - page 12

    3.2 Pictures of NetAgent II NetAgent II(BP ,CP/CT ,DP/CT Series) CP504 CP503 BP506 BP505 NetAgent Mini (DP Series) DP520 DP522 DP532 6 DP801 DP802 ...

  • BlueWalker SNMP CP-504 - page 13

    3.3 NetAgent Package Contents n NetAgent Utility CD, including: ♦ Netility:Configure NetAgent IP address, update firmware ♦ ClientMate:Windows, Linux, Fr eeBSD shutdown utility. ♦ SNMPView:Windows platform multiple NetAgent UPS management software. ♦ SMS Server: SMS Notification ♦ UPS MIB:MIB file for the Network Management System ♦ Tim ...

  • BlueWalker SNMP CP-504 - page 14

    3 Ports NetAgent (Int ernal / External) : LED Table Yellow Red Green Status Solid Off Solid Off Solid ON Power ON Flashing Solid ON Solid ON System initial Solid ON Solid Off Solid ON Normal operation Solid ON Flashing Solid ON No connection to UPS Flashing Flashing Writing data to flash memory Solid ON Green light : Power state Red light : Connect ...

  • BlueWalker SNMP CP-504 - page 15

    3.5 NetAgent Mini Out looking NetAgent Mini External NetAgent Mini Internal Module Light signal application of NetAgent Mini - Status LED Light color Signal definition Condition description Green Power state On: Normal power Red Connection st ate with UPS Flash: no connection with UPS Orange Correspondence st ate Light flashes when Netagent transmi ...

  • BlueWalker SNMP CP-504 - page 16

    Chapter 2. NetAgent UPS Installation Before using the NetAgent, the proper har dware and software configuration is necessary. Hardware installation is to connect the NetAgent and UPS and network. Software configuration includes the IP address.Firmware upgrade. Or using the Browser or Telnet for configuration. You could also install the shutdown uti ...

  • BlueWalker SNMP CP-504 - page 17

    Chapter 3. NetAgent, UPS and Network Connection NetAgent II and NetAgent Mini provides Ex ternal and Internal model for different UPS interface requirement. Please reference the following description for detailed information of UPS and network connection. Section1. Install the NetAgent II with UPS and Network NetAgent II - External NetAgent II - In ...

  • BlueWalker SNMP CP-504 - page 18

    Section2. Install the NetAgent Mini with UPS and Network NetAgent Mini - External NetAgent Mini -Internal o T o UPS n To L A N p To DC Adapter n To L A N o To U P S 2.1 For External NetAgent Mini n Connect the NetAgent Mini to LAN, using the UTP port. o Connect the cable from NetAgent Mi ni to the serial port of UPS. p Plug the DC adapter to UPS ou ...

  • BlueWalker SNMP CP-504 - page 19

    Chapter 4. Using Netility Setup IP.Update Firmware Section1. Install Netility n Insert NetAgent Utility CD to the CD-RO M driver and execute Netility.exe. o After complete installation, there will be a ‘Netility’ group in Windows ’Start’ Æ ‘Program Group’. Fig.6 Netility Group p Click “Netility” could initiate the Netility and ente ...

  • BlueWalker SNMP CP-504 - page 20

    n Launch Device Click Launch Device or double click the Ne tAgent listed in the table to launch it. Enter the Account (Login Name) and Pass word (Login Password) set earlier to login. If you did not configure one , then just click Apply to login. o Network Settings Choose the NetAgent from t he right of the screen, t hen click “Configure”, woul ...

  • BlueWalker SNMP CP-504 - page 21

    For example, ) Set 81 as HTTP port number, then http://192.168.0.177:81 must be typed at the web address to proceed to Netagent UPS’s website. ) Set 23 as T elnet port number , then " 192.168.0.177:24" must be typed at T elnet to proceed to the T elnet screen of NetAgent UPS. Netility Password After password setting here, there is no wa ...

  • BlueWalker SNMP CP-504 - page 22

    p Firmware Upgrade NetAgent offer convenient firmware upgrade function. When you are going to upgrade firmware, click Download Firmware from NetAgent Setup menu, click “Browser” select new firmware file (*.bin) and press “Start”. Thus, Net Agent’s Red LE D and Yellow LED flashing alternative means the firmware is upgrading. After upgrade ...

  • BlueWalker SNMP CP-504 - page 23

    Chapter 5. UPS Web management by NetAgent Section1. Introduction After finishing NetAgent installation, including hardware installation and IP setting, you are now able to go to Ne tAgent web site to monitor and control UPS by inputting NetAgent IP address in Browser. n Starting the Web Brower (Netscape or Internet Explore) o Enter the NetAgent IP ...

  • BlueWalker SNMP CP-504 - page 24

    Section2. NetAgent UPS Web Interface Enter NetAgent UPS Web page,there are 4 ma in function items in the first Web page: 2.1 Information 2.2 Configuration 2.3 Log Information 2.4 Help Enter the main function item, the sub -menu items will be shown on the left side of the page. When using this NetAgent for the first time, please enter the [Config] m ...

  • BlueWalker SNMP CP-504 - page 25

    2.1 Information Sub-Menu : 2.1.1 System Status 2.1.2 Basic Information 2.1.3 Current Status 2.1.4 Remote Control 2.1.5 Meter/Chart 2.1.6 Modem Status 2.1.7 Environment Sensors-NetFeeler II Note: The options available on this menu depend on the NetAgent model. (e.g. “NetFeeler II” will not be display for one port.) 19 ...

  • BlueWalker SNMP CP-504 - page 26

    2.1.1 System St atus This page is to show NetAgent system in formation and Network settings. Values shown here are either provided by NetAgent it self or they are us er settings from the Configuration pages. System Information This section is to show NetAgent system information. Values in Hardware Version/Firmware Version/Serial Number/Sys tem Time ...

  • BlueWalker SNMP CP-504 - page 27

    2.1.2 Basic Informatio n This page is to show UPS basic information. Values here are either provided by the UPS or they are user settings from the Configuration pages. UPS Information Information about UPS Manufacturer/UPS Firmware Version/UPS Model are provided by the UPS. Battery Information Values here are user settings from the Configuration pa ...

  • BlueWalker SNMP CP-504 - page 28

    2.1.3 Current St atus This page is to show the UPS current status . Users can choose an interval from the drop-down box to refresh the status readings. UPS Status This section is to show the UPS power status. The abnormal status will be displayed in red when there is a power event. Input Status This section is to show the UPS input status, includin ...

  • BlueWalker SNMP CP-504 - page 29

    10 Second Test This to perform 10 seconds UPS self test Deep Battery Test This function is to execute XX minute deep battery test Test Until Battery Low When execute, UPS will test Battery until battery low Cancel Test This function is to abort a test when it is executin g. Turn off UPS when AC failed/Reboot UPS Selecting ' Turn off UPS when A ...

  • BlueWalker SNMP CP-504 - page 30

    2.1.5 Meter/Chart This page displays temperature, capacity, load, voltage..etc of the UPS by appearing with meters/chart diagram. Fig.20 Meter/Chart 24 ...

  • BlueWalker SNMP CP-504 - page 31

    2.1.6 Modem St atus (For 3 Ports NetAgent II only) This page displays Modem’s status and information. when 3 ports NetAgent II connects with modem. Modem Information This section displays the modem information. GSM Modem Operating Status This section displays the operating status between NetAgent and Modem. Fig.21 Modem Status 25 ...

  • BlueWalker SNMP CP-504 - page 32

    2.1.7 Environment Sensors- NetFeeler II 3 Ports NetAgent could be connected to NetFeeler II to detect the environmental status. NetFeeler II is to detect Temperature , Humidity and Water. It can receive signals from wireless smoke sensors, gas sensors and securi ty sensors to detect further environmental conditions. This page is to show details of ...

  • BlueWalker SNMP CP-504 - page 33

    2.2 Configuration Sub-Menu : 2.2.1 UPS Configuration 2.2.2 UPS On/Off Schedule 2.2.3 Network 2.2.4 SNMP 2.2.5 Email 2.2.6 SMS 2.2.7 Modem 2.2.8 WEB/Telnet 2.2.9 System Time 2.2.10 NetFeeler II 2.2.11 Language Please set each parameter correctly, so that NetAgent woul d operates properly. Note: This page’s selection would differ accord ing to the ...

  • BlueWalker SNMP CP-504 - page 34

    2.2.1 UPS Configuration This page is to set the UPS configurati on. Any wrong settings will cause incorrect display values or disconnection between the UPS and NetAgent. UPS Properties UPS Communication Type This section is to set up the communication interface of the UPS. (eg. Contact Closure/Megatec/Phoenixtec/ Megatec 3 phase etc.) Please refer ...

  • BlueWalker SNMP CP-504 - page 35

    Critical Capacity (%) This section is to set the UPS critical batte ry capacity (shown as % )NetAgent will send warning messages when UPS low battery occurs. Fig.23 UPS Configuration 29 ...

  • BlueWalker SNMP CP-504 - page 36

    2.2.2 UPS On/Off Schedule This page is to schedule On/Off time for the UPS and Wake On Lan. Weekly Schedule This section is to set the time to turn on/off the UPS each day in the week. Date Schedule This section is to set the time to tur n on/off the UPS on particular days. (Eg, holidays.) The settings here override the settings in Weekly Schedule ...

  • BlueWalker SNMP CP-504 - page 37

    2.2.3 Network This page is to set NetAgent Network settings. IP Address IP Address This section is to set NetAgent IP address. Subnet Mask This section is to set NetAgent Subnet Mask. Gateway This section is to set NetAgent Gateway. Obtain an IP address This section is to choose to set NetAgent IP address manually or via DHCP. The above 4 sections ...

  • BlueWalker SNMP CP-504 - page 38

    Domain Name This is the Domain Name you have created from the above selected DDNS provider. Login Name This is the Login / Account name that you have created with the selected DDNS pro vider. Login Password Enter the Password you have assigned to your DDNS Account. Use external STUN server to get Public IP to register Choose Yes to ensure that NetA ...

  • BlueWalker SNMP CP-504 - page 39

    Fig.25 Network 33 ...

  • BlueWalker SNMP CP-504 - page 40

    2.2.4 SNMP This page is to set NetAgent SNMP settings so it can be used by a NMS ( Network Management System). (Eg: SNMPVi ew, SNMPView can be found on the NetAgent Utility CD.) MIB System System Name This section is to give a name to a NetAgent. System Contact This section is to give a name to the administrator. System Location This section is to ...

  • BlueWalker SNMP CP-504 - page 41

    Fig.26 UPS Events 35 ...

  • BlueWalker SNMP CP-504 - page 42

    Device Connected This section is to set the usage po wer and connection status of other devices which connects to the same UPS as NetAgent uses. Fig.27 SNMP 36 ...

  • BlueWalker SNMP CP-504 - page 43

    2.2.5 Email This page is to set Email details for use by NetAgent. Email Setting Email Server This section is to set NetAgent Email Server . Note that free email server such as Hotmail, yahoo, Gmail is not allowed Email Port This is to configure the SMTP port to send email Sender’s Email Address This section is to set NetAgent’s Email address. ...

  • BlueWalker SNMP CP-504 - page 44

    Fig.28 Email 38 ...

  • BlueWalker SNMP CP-504 - page 45

    2.2.6 SMS When UPS events occurs, it allows Short Message Signals (“SMS”) to be sent and received using a GSM/GPRS/CDMA Modem. Operation information are as below for single and three ports of NetAgent. 2.2.6.1 To send SMS by single port of NetAgent It requires to use remote “SMSA gent” or freeware SMS Server SMS Settings Send SMS when Event ...

  • BlueWalker SNMP CP-504 - page 46

    2.2.7 Modem (For 3 Ports NetAgent II only) This section is to configure Modem’ s setting if 3 ports NetAgent connect s with GSM/GPRS Modem. Modem Setting Modem Communication Interface Communication Type Suitable Condition When NetAgent connects with Megatec’s GSM/GPRS Modem SMS When NetAgent connects with dial in modem PPP Dial-in SMS Setting S ...

  • BlueWalker SNMP CP-504 - page 47

    2.2.8 WEB/T elnet This page is to set up the User Account in NetAgent. User Account User Name This section is to set a user name for NetAgent web pages. It is valid for up to 8 users. Users have to input the user name to get access to NetAgent web pages from a web browser. Password This section is to set a password for NetAgent web pages. Users hav ...

  • BlueWalker SNMP CP-504 - page 48

    2.2.9 System Time This page is to set NetAgent system time. You can provide NetAgent with up to 2 time servers or you ca n set a time zone. System Time Time Between Automatic Updates This section is to set an interval for time synchronization. Time Server Choose the nearest Time Server to your NetAgent location. The Adminis trator can choose from t ...

  • BlueWalker SNMP CP-504 - page 49

    2.2.9 NetFeeler II (For 3 Ports NetAgent II only) This page is to set Environmental sens ors-NetFeeler II’s configurations. NetFeeler II Critical UnderRun This section is to set the lowest critical values for temperature and humidity. NetFeeler II will send a warning message when it detects temperature or humidity values below these settings. Cri ...

  • BlueWalker SNMP CP-504 - page 50

    2.2.10 Language This page is to set the language interface for NetAgent. Interface Language This section is to set the language for NetAgent web pages. When users first start to open the webpage of NetAgent, NetAgent will auto detect the language in the computer system and show the same language on its web pages. Users can also choose the languages ...

  • BlueWalker SNMP CP-504 - page 51

    2.3 Log Information Sub-Menu : 2.3.1 Event Log 2.3.2 SMS 2.3.3 Data Log 2.3.4 Save Data Log NetAgent Log Record Model Log Information Single Port(DP,CP) 3Ports (BP) Event Log 100 logs 1000 logs SMS Log --- 1000 logs Data Log 500 logs 5000 logs Fig.34 NetAgent Log Record 2.3.1 Event Log This page is a UPS Event log. It shows a re cord of all events, ...

  • BlueWalker SNMP CP-504 - page 52

    Fig.35 Event Log 46 ...

  • BlueWalker SNMP CP-504 - page 53

    2.3.2 SMS This page is a SMS Event log. It shows a record of all mobile number, giving the Date/Time of the SMS sent and a detailed description of each. When reach to the limit, it rewrites on the previous logs Fig.36 SMS Log 47 ...

  • BlueWalker SNMP CP-504 - page 54

    2.3.3 Dat a Log This page is a UPS data log. It reco rds UPS Input Voltage/Output Voltage/ Frequency/ Loading/Capacity/ Tem perature. When reach to t he limit, it rewrites on the previous logs. Logs can be saved in CSV format by clicking on “Save Data Log”. Date/Time This is a record of the Date (yyyy/mm/dd) and Time (hh:mm:ss) that the data wa ...

  • BlueWalker SNMP CP-504 - page 55

    Fig.37 Date Log 49 ...

  • BlueWalker SNMP CP-504 - page 56

    2.3.3 Save Dat a Log This function is to record RS232 UPS’ s voltage, frequency, load, capacity, temperature..etc to save as another file for the other purpose to the manager. Fig.38 Save Data Log 50 ...

  • BlueWalker SNMP CP-504 - page 57

    2.4 Help Sub-Menu : 2.4.1 Search NetAgent 2.4.2 Serial Port Debug 2.4.3 Help 2.4.4 About 2.4.1 Search NetAgent This to display all the found NetAgent wit hin network with its serial number; Mac Address; Hardware/Firmware version and its IP address. Double clicking on the highlighted unit to open the webpage of such device. Refresh T his will re-sea ...

  • BlueWalker SNMP CP-504 - page 58

    2.4.3 Help This to help to illustrate the operation of NetAgent 2.4.4About About This to check Netagent’ s Firmware/Hardware version and serial number Save/Restore Settings Click Save to save the confi guration to your PC. The te xt file will have a default format of YYYY_MMDD_#### . cfg. Administrator permission required. Restore previous config ...

  • BlueWalker SNMP CP-504 - page 59

    Firmware Update Setting Default FTP server is set as ftp.icv99.com with its username/password. Click on Update Now, NetAgent will connects to t he FTP server and upgrade to the latest firmware version accordingly. Auto Update This is to configure the period of time to check if any updated firmware in FTP and upgrade automatically. Firmware Update W ...

  • BlueWalker SNMP CP-504 - page 60

    Chapter 6. Telnet (Remote Configuration) Section1. Introduction NetAgent supports multiple Network Management systems and LAN protocols. After finishing hardware installation, you are now able to choose any utilities that provided by NetAgent to monitor and control UPS. Here are introduction for using Telnet. Section2. Telnet Configuration n Select ...

  • BlueWalker SNMP CP-504 - page 61

    Fig.42 NetAgent T elnet window 1. Set IP Address. This function allows you to setup IP Address, Gateway Address, Subnet Mask parameters. 2. Set SNMP MIB System. This function allows you to set the MIB system group parameters. 3. Set SNMP Access Control. This function allows you to set the Manager IP, Community, Access Permission. N o t e : The conf ...

  • BlueWalker SNMP CP-504 - page 62

    Chapter 7. ClientMate - Windows Shutdown Utility ClientMate is a utility for connecting to Ne tAgent. This utility is for the Windows platform. When the ClientMate get the power failure si gnal from the NetAgent. The ClientMate will save the f iles and shutdown the system gracefully. When the hardware installation of the NetAgent has been completed ...

  • BlueWalker SNMP CP-504 - page 63

    2.1 Config When the ClientMate gets the signal from the NetAgent about the AC power failure or battery low signals, the Client Mate will based on the configuration below to initiate the shutdown process. The deta ils of the configuration are here below. Fig.45 ClientMate: Configuration i. Host Connection Configure the Host connection IP address. ii ...

  • BlueWalker SNMP CP-504 - page 64

    vi. Shut down Windows To configure if shutdown or Sleep the Windows system when power failure. vii. When AC failed, commence computer shut down sequence in xx Min. To configure the time delay between the AC failure and the system shutdown. viii. When Battery Low , commence computer shut down sequence in xx Min. To configure the time delay between t ...

  • BlueWalker SNMP CP-504 - page 65

    2.3 About Press this button could review the versi on information of the ClientMate, as here bellowed. Fig.47 ClientMate:About 2.4 Event log Press this button could review all the network status and UPS status happened. Shown as below. Fig.48 ClientMate:About 59 ...

  • BlueWalker SNMP CP-504 - page 66

    2.5 IP address of connection Status ICON Description Already connect to NetAgent UPS at IP 211.21.67.51 Does not connect to any NetAgent. 2.6 AC power status Status ICON Description The connected NetAgent UPS AC power is normal. The connected NetAgent UPS AC power is failed. 2.7 Battery Status Status ICON Description The connected NetAgent UPS batt ...

  • BlueWalker SNMP CP-504 - page 67

    Chapter 8. SNMPView – Windows Based UPS M anagement System Section1. Introduction SNMPView is a software to remotely m onitor and control multiple UPS connected to a network. When an event occurs, SN MPView can be programmed to send an email or a pager to inform the designated network manager. It can also inform the user of the UPS current condi ...

  • BlueWalker SNMP CP-504 - page 68

    Section3. Install SNMPView n Put the NetAgent Utility CD into the CD driver. And execute the SNMPView program. o After installation, there will be a NetA gent group in the Windows Start group. p Click “NetAgent” Æ “SNMPView” Æ “SNMPView for Windows” to start using SNMPView. 62 ...

  • BlueWalker SNMP CP-504 - page 69

    Section4. Using SNMPView When use SNMP view at the first time, the system will ask for input the user's name and password. Please enter the default valu e as follows to st art the SNMPView. User Name: Admin Password: <blank> (just press <Enter>) After the SNMPView program start up the main windows will be displayed. The left panel ...

  • BlueWalker SNMP CP-504 - page 70

    Section5. SNMPView Buttons When use SNMPView, configuration could be done by all function icons displayed or right click on the mouse to show functions list. Followings are the explanation of each f unction icon: Enumerate : Search all SNMP hosts that s upports Public group and display them on the screen Add UPS : Manually add a host into the windo ...

  • BlueWalker SNMP CP-504 - page 71

    Following is the main function ic ons and its reference chapter. Main List Sub List • 5.1.1 Enumerate • 5.1.2 Add Group • 5.1.3 Add UPS • 5.1.4 Delete • 5.1.5 Browse Device • 5.1.6 Expor t Configurations 5.1.7 Import Configuration • 5.1.8 Open archive Event Log • 5.1.9 Open archive Data Log 5.1 Device(D) • 5.1.10 Quit 5.2 V iew (S ...

  • BlueWalker SNMP CP-504 - page 72

    5.1 ENUMERA TE(D) Start SNMPView and press the “Enumerate” button, SNMPView will start a search for all the NetAgent on network and list them in the main window. 5.1.1 Enumerate When press , SNMPView will start a sear ch for all the NetAgent on network and list them in the main window. 5.1.2 Add Grou p This is to edit or display all the group s ...

  • BlueWalker SNMP CP-504 - page 73

    5.1.4 DELETE UPS Highlight the unit to be delet ed from main list and right click on it to choose Delete or use click on the Delete icon from main function list. Hold On “Shift” to select multi NetAgent UPS 5.1.5 Browse Devi ce Highlight the unit to be browsed and cli ck it to enter NetAgent’s webpage. 5.1.6 Export Configurati on This is to s ...

  • BlueWalker SNMP CP-504 - page 74

    5.1.7 Import Configuration This is to import the configurat ion of NetAgent UPS that saved 68 ...

  • BlueWalker SNMP CP-504 - page 75

    5.1.8 Open archive Event Log Open up “SnmpElog.dat”, SNMPV iew would show the event log of all NetAgent UPS: Open up “SnmpElog.dat”, event log would show as below: 69 ...

  • BlueWalker SNMP CP-504 - page 76

    5.1.9 Open archive Data Log Open up “SnmpDlog.dat”, SNMPV iew would show the event log of all NetAgent UPS: Open up “SnmpDlog.dat”, data log would show as below: 5.1.10 Quit Exit SNMPV iew 70 ...

  • BlueWalker SNMP CP-504 - page 77

    5.2 View(S) This is to choose the presentat ion format of NetAgent UPS. 5.2.1 Large Icons Large icon view to display IP address and it s location. 5.2.2 Small Icons Small icon view to display NetAgent UPS’ s IP address, Name, location…etc 71 ...

  • BlueWalker SNMP CP-504 - page 78

    5.2.3 Det ails Detailed Information displays NetAgent UPS’ s IP address, name, input volt age, output voltage, battery cap acity , load, frequency ..etc. 5.2.4 Map Background Import a map image (JPG) by right click on the main screen and move NetAgent UPS icon to its suit able location. 72 ...

  • BlueWalker SNMP CP-504 - page 79

    5.3 Tools(P) Highlight NetAgent UPS dev ice and configure. 5.3.1 Settings General This to configure UPS information, re cord UPS event, enable trap alarm..etc Email Send email notification when event occurs ♦ Sender Display name : Please enter sender display name ♦ Sender email address: Please enter sender email address ♦ SMTP server address: ...

  • BlueWalker SNMP CP-504 - page 80

    Trap List Double click on the trap that listed and configure UPS Loading To configure all the other devices and it s load that connects with NetAgent UPS. Double click on the device listed and configure 74 ...

  • BlueWalker SNMP CP-504 - page 81

    75 ...

  • BlueWalker SNMP CP-504 - page 82

    5.3.2 UPS Monitor Highlight NetAgent UPS devic e and configure. Or right click on the highlighted device and click on monitor device Meter Display NetAgent UPS information such as input voltage, output voltage, temperature, capacity ..etc in diagram. Digit al Display NetAgent UPS information such as input voltage, output voltage, temperature, capac ...

  • BlueWalker SNMP CP-504 - page 83

    Event Log This display event happened with date/time and its description Control • Tu rn Off UPS: T o shutdown UPS • Reboot UPS: UPS shuts down in 12 seconds, and reboot in 1 minute. • LED: Enable LED flas hes. (UPS must supports it) • Cancel Shutdown: T o cancel UPS shutdown. (UPS must supports it) • Simulate AC Fail: Simulate AC failed ...

  • BlueWalker SNMP CP-504 - page 84

    Once choose the function that to perform and click on “Execute” Note: UPS must supports those function to perform it T est Control • UPS Se lf T est: Execute UPS Self T est • UPS Calibration Test: Execute UPS Calibration Test T urn-Off Parameters • Turn-Of f Delay: T o set the buffering time for UPS before shutdown • Sleep T ime: T o se ...

  • BlueWalker SNMP CP-504 - page 85

    5.3.3 UPS Management To configure SNMP of its NetAgent UPS 79 ...

  • BlueWalker SNMP CP-504 - page 86

    5.4 System(S) T o view event log, data log and configuration 5.4.1 Event Log Display event log , date/time and description of all NetAgent UPS 5.4.2 Dat a Log Display input voltage, output voltage , frequency ,load..etc of all NetAgent UPS 80 ...

  • BlueWalker SNMP CP-504 - page 87

    5.4.3 SNMP Option T o set NetAgent UPS’ s parameter 81 ...

  • BlueWalker SNMP CP-504 - page 88

    5.5 User(U) T otal of 8 users account can be creat ed to manage and control it s NetAgent UPS 5.5.1 Change Password T o change existing user ’s password to login 5.5.2 User Management This only for Admin user to add, edit or remote other user ’s info 82 ...

  • BlueWalker SNMP CP-504 - page 89

    5.6 Help(H) Display the current SNMPView version, and operation information 5.6.1 HTML Help This to check the operation of SNMPV iew 5.6.2 About Display the current SNMPV iew version, Copyright information and product service contact. 83 ...

  • BlueWalker SNMP CP-504 - page 90

    Appendix A - Update the firmware of NetAgent UPS NetAgent provides the following convenient methods for user to update the latest firmware of the NetAgent 1. Click firmware upgrade under About of Ne tAgent webpage and it would link to Megatec’ s server to download the latest firmware. Then use Download Firmware from Netility to upgrade it. 84 ...

  • BlueWalker SNMP CP-504 - page 91

    2. Use FTP to up date (suit able for BK,CK,DK,BP ,CP ,DP using firmw are version 2.35 and later) The FTP is a easy and common way to upload the latest firmware into the NetAgent. Please follow the instruction below to update the firmware. If there is othe r FTP client application on your computer, that will also be fine to use it fo r updating the ...

  • BlueWalker SNMP CP-504 - page 92

    3. Use IE browser to up date (suit able for BK,CK,DK,BP ,CP ,DP version) This method is to enter the account, p assword and IP address of the NetAgent UPS which the user wish to update under the web site column. Once entered, user may see the current firmware version, and then please copy the latest firmware to here to comple te the updating proces ...

  • BlueWalker SNMP CP-504 - page 93

    Appendix B -3 Ports NetAgent II with SMS Modem BP506 & SMS MODEM Hardware Installation : 1: A : GSM MODEM 。 B : GSM MODEM Adaptor 。 C : NetAgent BP506 。 D : GSM MODEM Cable 。 E : RS232 to RJ45 Cable 。 2 : How hardware should be connected 3 : Before use GSM MODEM, insert SIM 4 : Once card inserted, Modem would detects ...

  • BlueWalker SNMP CP-504 - page 94

    card has password, invalid p assword. If such conditions happens, please unplug &plug the power on Modem and it shall ready SIM again. If Led doesn’t flash continuously (once ever y 8 seconds), then Modem is working properly 88 ...

  • BlueWalker SNMP CP-504 - page 95

    BP506 Modem Configuration : 1 、 BP506 Modem 2.Modem communication T ype → Select SMS 3 . S M S C o m m u n i c a t i o n → Select GPRS 4.Enter SIM Card PIN(leave blank if none) 。 5.Click on Apply 。 5: Under Modem status of BP506 webp age, it indicates the status of Modem 89 ...

  • BlueWalker SNMP CP-504 - page 96

    BP506 SMSConfiguration : BP506 → Configuration → 1.SMS 2 . S e l e c t L o c a l M o d e m 3.Enter BP506’ s username and password(leave none leave blank) 。 4.Enter Mobile number 。 5 . S e l e c t e v e n t s t o s e n d 。 6 . C l i c k o n A p p l y 。 1 : 90 ...

  • BlueWalker SNMP CP-504 - page 97

    Appendix C –SMS Server with SMS Modme GPRS MODEM Inst allation : 1. Insert Sim card 2 、 Connect DC adaptor to GPRS modem as well serial cable provided to PC com port 1 2 3 NOTE ※ : Please make sure there is no conflict port with the GPRS modem SMS SERVER Sof tware Inst allation : 1 、 Click on exe for installation 1 : 91 ...

  • BlueWalker SNMP CP-504 - page 98

    2 : Once installed, the icon would a ppear on the tool bar 3 : Right click on the SMS server icon and check modem status 2 、 SMS Server Software Configuration 92 ...

  • BlueWalker SNMP CP-504 - page 99

    3 、 NetAgent sends SMS via modem : 1. Click on SMS in the NetAgent Webp age 2. Enter the SMS server ’s IP S e r v i c e P o r t : NetAgent & SMS Server port that use for local connection Service account : Account authentication for sending SMS (Leave blank if no such setting) 。 S e r v i c e p a s s w o r d : Password authenticati ...

Manufacturer BlueWalker Category Network card

Documents that we receive from a manufacturer of a BlueWalker SNMP CP-504 can be divided into several groups. They are, among others:
- BlueWalker technical drawings
- SNMP CP-504 manuals
- BlueWalker product data sheets
- information booklets
- or energy labels BlueWalker SNMP CP-504
All of them are important, but the most important information from the point of view of use of the device are in the user manual BlueWalker SNMP CP-504.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals BlueWalker SNMP CP-504, service manual, brief instructions and user manuals BlueWalker SNMP CP-504. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product BlueWalker SNMP CP-504.

A complete manual for the device BlueWalker SNMP CP-504, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use BlueWalker SNMP CP-504 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of BlueWalker SNMP CP-504.

A complete BlueWalker manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual BlueWalker SNMP CP-504 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the BlueWalker SNMP CP-504, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the BlueWalker SNMP CP-504, that we can find in the current document
3. Tips how to use the basic functions of the device BlueWalker SNMP CP-504 - which should help us in our first steps of using BlueWalker SNMP CP-504
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with BlueWalker SNMP CP-504
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of BlueWalker SNMP CP-504 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning BlueWalker SNMP CP-504?

Use the form below

If you did not solve your problem by using a manual BlueWalker SNMP CP-504, ask a question using the form below. If a user had a similar problem with BlueWalker SNMP CP-504 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)